MODEL: M2BS-8 M2BS-8 SPECIFICATIONS ES-5006 Rev.10 Page 1/4 http://www.m-system.co.jp/ Super-mini Signal Conditioners Mini-M Series INSTALLATION BASE (8 positions) Functions & Features

  • Receiving at the maximum of 8 modules of Mini-M series signal conditioners
  • Connector output
  • Power supplied through printed wiring on the base Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO MODEL: M2BS–8[1][2]

ORDERING INFORMATION

  • Code number: M2BS-8[1][2] Specify a code from below for each of [1] and [2]. (e.g. M2BS-8U2/D/UL) [1] FUNCTION U1: Fujitsu FCN type I/O connector (UL not available) U2: Omron I/O connector [2] OPTIONS (multiple selections) Mounting blank: Surface /D: DIN rail mounting adaptor Standards & Approvals blank: Without UL /UL: UL approval

RELATED PRODUCTS

  • Connector terminal block (model: CNT)
  • Special cable with 40-pin connector (model: FCN) GENERAL SPECIFICATIONS Capacity: 8 positions Connection Power input: M3 screw terminals (torque 0.8 N·m) Input and output: M3 screw terminals (torque 0.8 N·m) Screw terminal: Nickel-plated steel INSTALLATION Power input: Refer to signal conditioner data sheet. Choose the same power input specification for all units. Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: wall; optional DIN rail mounting available (in horizontal direction only) Weight: 780 g (1.72 lb) PERFORMANCE Insulation resistance: ≥ 100 MΩ with 500 V DC (input to output to power to FG) Dielectric strength: 2000 V AC @1 minute (input to output to power to FG) STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1 Installation Category II Pollution Degree 2 Input or output to power: Reinforced insulation (300 V) Input to output: Basic insulation (300 V) RoHS Directive EN 50581 Approval: UL/C-UL nonincendive Class I, Division 2, Groups A, B, C, and D (ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213) UL/C-UL general safety requirements (UL 3111-1, CAN/CSA-C22.2 No.1010-1) Voltage at the field I/O terminals (except power input terminals) limited within 30 V DC for UL.

MODEL: M2BS-8 M2BS-8 SPECIFICATIONS ES-5006 Rev.10 Page 2/4 http://www.m-system.co.jp/ CONNECTION DIAGRAM ■ MODEL: M2BS-8U1 (Fujitsu FCN type I/O connector FCN364P040-AU) CN1: output PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT A1 ch.1 + B1 ch.1 – A2 ch.2 + B2 ch.2 – A3 ch.3 + B3 ch.3 – A4 ch.4 + B4 ch.4 – A5 ch.5 + B5 ch.5 – A6 ch.6 + B6 ch.6 – A7 ch.7 + B7 ch.7 – A8 ch.8 + B8 ch.8 – A9 – A20, B9 – B20: Unused

  • Connector Pin Assignment ■ CONNECTION DIAGRAM FG CN1 Ch.1 INPUT1 Ch.8 INPUT U(+) V(–) POWER ■ MODEL: M2BS-8U2 (Omron I/O connector XG4A-3431) CN1: output PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT 1 ch.1 + 2 ch.1 – 3 ch.2 + 4 ch.2 – 5 ch.3 + 6 ch.3 – 7 ch.4 + 8 ch.4 – 9 ch.5 + 10 ch.5 – 11 ch.6 + 12 ch.6 – 13 ch.7 + 14 ch.7 – 15 ch.8 + 16 ch.8 – 17 – 34: Unused
  • Connector Pin Assignment

MODEL: M2BS-8 M2BS-8 SPECIFICATIONS ES-5006 Rev.10 Page 3/4 http://www.m-system.co.jp/ ■ CONNECTION DIAGRAM FG CN1 Ch.1 INPUT1 Ch.8 INPUT U(+) V(–) POWER EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) CN1 CONNECTOR 5 8 1 4 5 8 1 4 5 8 1 4 5 8 1 4 5 8 CH7CH1 5 8 FG 1 4 13 14 1 2 3 4 5 5 85 8 6 7 1 41 4 CH8 50 (1.97) 6 (.24) 235 (9.25) 255 (10.04) 275 (10.83) 27 (1.06) 2–M3 POWER TERMINALS CT PROTECTOR (CTM2)** 32–M3 INPUT TERMINALS DIN RAIL MTG ADAPTOR (provided only when option /D is selected.) DIN RAILDIN RAIL MTG ADAPTOR (provided only when option /D is selected.) (0.51) *165 (6.50) required for pneumatic tubing for M2PV. ** Attached to M2CA and M2CE.

MODEL: M2BS-8 M2BS-8 SPECIFICATIONS ES-5006 Rev.10 Page 4/4 http://www.m-system.co.jp/ MOUNTING REQUIREMENTS unit: mm (inch) 50 (1.97) 255 (10.04) 4–M5 SCREW (1.50) DIN RAIL* *Installed in horizontal direction only. Specifications are subject to change without notice.