MODEL: M2BS-16 M2BS-16 SPECIFICATIONS ES-5005 Rev.12 Page 1/5 http://www.m-system.co.jp/ Super-mini Signal Conditioners Mini-M Series INSTALLATION BASE (16 positions) Functions & Features

  • Receiving at the maximum of 16 modules of Mini-M series signal conditioners
  • Screw terminal or connector output
  • Power supplied through printed wiring on the base Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO Model SPAN ZERO MODEL: M2BS–16[1][2]

ORDERING INFORMATION

  • Code number: M2BS-16[1][2] Specify a code from below for each of [1] and [2]. (e.g. M2BS-16U2/D/UL) [1] FUNCTION U0: Screw terminal block U1: Fujitsu FCN type I/O connector (UL not available) U2: Omron I/O connector [2] OPTIONS (multiple selections) Mounting blank: Surface /D: DIN rail mounting adaptor (Not selectable for M2BS-16U0) Standards & Approvals blank: Without UL /UL: UL approval

RELATED PRODUCTS

  • Connector terminal block (model: CNT)
  • Special cable with 40-pin connector (model: FCN) GENERAL SPECIFICATIONS Capacity: 16 positions Connection Power input: M3 screw terminals (torque 0.8 N·m) Input and output: M3 screw terminals (torque 0.8 N·m) Screw terminal: Nickel-plated steel INSTALLATION Power input: Refer to signal conditioner data sheet. Choose the same power input specification for all units. Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Surface; optional DIN rail mounting available for M2BS-16U1, U2 (in horizontal direction only) Weight: 1.8 kg (4.0 lb) PERFORMANCE Insulation resistance: ≥ 100 MΩ with 500 V DC (input to output to power to FG) Dielectric strength: 2000 V AC @1 minute (input to output to power to FG) STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1 Installation Category II Pollution Degree 2 Input or output to power: Reinforced insulation (300 V) Input to output: Basic insulation (300 V) RoHS Directive EN 50581 Approval: UL/C-UL nonincendive Class I, Division 2, Groups A, B, C, and D (ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213) UL/C-UL general safety requirements (UL 3111-1, CAN/CSA-C22.2 No.1010-1) Voltage at the field I/O terminals (except power input terminals) limited within 30 V DC for UL.

MODEL: M2BS-16 M2BS-16 SPECIFICATIONS ES-5005 Rev.12 Page 2/5 http://www.m-system.co.jp/ CONNECTION DIAGRAM ■ MODEL: M2BS-16U0 (screw terminal block) ■ CONNECTION DIAGRAM FG Ch.1 INPUT Ch.1 OUTPUT Ch.2 OUTPUT 9 Ch.16 OUTPUT Ch.16 INPUT U(+) V(–) POWER ■ MODEL: M2BS-16U1 (Fujitsu FCN type I/O connector FCN364P040-AU)

  • Connector Pin Assignment CN1: output PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT A1 ch.1 + B1 ch.1 – A2 ch.2 + B2 ch.2 – A3 ch.3 + B3 ch.3 – A4 ch.4 + B4 ch.4 – A5 ch.5 + B5 ch.5 – A6 ch.6 + B6 ch.6 – A7 ch.7 + B7 ch.7 – A8 ch.8 + B8 ch.8 – A9 ch.9 + B9 ch.9 – A10 ch.10 + B10 ch.10 – A11 ch.11 + B11 ch.11 – A12 ch.12 + B12 ch.12 – A13 ch.13 + B13 ch.13 – A14 ch.14 + B14 ch.14 – A15 ch.15 + B15 ch.15 – A16 ch.16 + B16 ch.16 – A17 – A20, B17 – B20: Unused ■ CONNECTION DIAGRAM FG CN1 Ch.1 INPUT1 Ch.16 INPUT U(+) V(–) POWER

MODEL: M2BS-16 M2BS-16 SPECIFICATIONS ES-5005 Rev.12 Page 3/5 http://www.m-system.co.jp/ ■ MODEL: M2BS-16U2 (Omron I/O connector XG4A-3431)

  • Connector Pin Assignment CN1: output PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT 1 ch.1 + 2 ch.1 – 3 ch.2 + 4 ch.2 – 5 ch.3 + 6 ch.3 – 7 ch.4 + 8 ch.4 – 9 ch.5 + 10 ch.5 – 11 ch.6 + 12 ch.6 – 13 ch.7 + 14 ch.7 – 15 ch.8 + 16 ch.8 – 17 ch.9 + 18 ch.9 – 19 ch.10 + 20 ch.10 – 21 ch.11 + 22 ch.11 – 23 ch.12 + 24 ch.12 – 25 ch.13 + 26 ch.13 – 27 ch.14 + 28 ch.14 – 29 ch.15 + 30 ch.15 – 31 ch.16 + 32 ch.16 – 33, 34: Unused ■ CONNECTION DIAGRAM FG CN1 Ch.1 INPUT1 Ch.16 INPUT U(+) V(–) POWER

MODEL: M2BS-16 M2BS-16 SPECIFICATIONS ES-5005 Rev.12 Page 4/5 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) ■ M2BS-16U0 5 8 1 4 5 8 1 4 5 8 1 4 5 8 1 4 5 8 1 4 5 8 CH5CH1 5 8 1 4 5 8 1 4 5 8 1 4 5 8 1 4 5 8 FG 1 4 13 14 1 2 3 4 5 5 85 85 85 85 8 6 7 8 9 10 1 41 41 41 41 4 11 12 13 14 15 16 CH10CH6 CH16CH11 9 12 CH11 CH12 CH13 CH14 CH15 CH16 9 12 9 12 9 12 9 12 9 12 9 12 CH6 CH7 CH8 CH9 CH10 9 12 9 12 9 12 9 12 9 12 CH1 CH2 CH3 CH4 CH5 9 12 9 12 9 12 9 12 CT PROTECTOR (CTM2)** 130 (5.12) 100 (3.94) 6 (.24) 440 (17.32) 460 (18.11) 480 (18.90) 27 (1.06) 2–M3 POWER TERMINALS 64–M3 INPUT TERMINALS 125 (4.92) * *165 (6.50) required for pneumatic tubing for M2PV. Attached to M2CA and M2CE. 6 (.24) 32–M3 OUTPUT TERMINALS ■ M2BS-16U1, U2 CN1 CONNECTOR 5 8 1 4 5 8 1 4 5 8 1 4 5 8 1 4 5 8 1 4 5 8 CH5CH1 5 8 1 4 5 8 1 4 5 8 1 4 5 8 1 4 5 8 FG 1 4 13 14 1 2 3 4 5 5 85 85 85 85 8 6 7 8 9 10 1 41 41 41 41 4 11 12 13 14 15 16 CH10CH6 CH16CH11 CT PROTECTOR (CTM2) 100 (3.94) 50 (1.97) 6 (.24) 440 (17.32) 460 (18.11) 480 (18.90) 27 (1.06) 2–M3 POWER TERMINALS DIN RAIL MTG ADAPTOR (provided only when option /D is selected.) DIN RAIL DIN RAIL MTG ADAPTOR (provided only when option /D is selected.) 64–M3 INPUT TERMINALS 125 (4.92) * (0.51) *165 (6.50) required for pneumatic tubing for M2PV. ** Attached to M2CA and M2CE.

MODEL: M2BS-16 M2BS-16 SPECIFICATIONS ES-5005 Rev.12 Page 5/5 http://www.m-system.co.jp/ MOUNTING REQUIREMENTS unit: mm (inch) ■ M2BS-16U0 100 (3.94) 460 (18.11) 4–M5 SCREW ■ M2BS-16U1, U2 50 (1.97) (1.50) 460 (18.11) 4–M5 SCREW DIN RAIL* *Installed in horizontal direction only. Specifications are subject to change without notice.