TX7008 TANDAUK | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 4
Technical content
8 Loop Intelligent Addressable
(GCVWTGUCPF$GPGƂVU
- Compliance EN54-2 and EN54-4
- Using advance microprocessor technology with Large memory capacity
- Built-in USB port for commissioning purpose
- Enhance user interface combining LCD Touch screen and keypad access
- Support real time visual algorithm
- Enhance false alarm prevention
- Keypad and PC programming
- Built-in Multiple interface protocol such as USB/Ethernet/CanBus/ Serial/RS485 (Avail- able only in TX7004/4 Panel)
- Support Loop Powered devices for extra saving on cable cost
- Built-In Printer and 160 LED Zones Indica- tors Commissioning Advantage
- Auto Enrolling of Devices
- Loop Mapping with colour coding status
- Monitor device mismatch and dual address VyVÌ
- Command Builder to create requirements
- With Loop protection against power surge
- One-man test with On/Off sounder Program- ming Protection System Capacity
- Maximum 8 loop in network application
- Support 254 Devices (1,524 ideal)
- Network up to 512 Node
- Programmable Capacity
- Zones up to 3000
- Sounders Groups 1-1000
- Modules Groups 1001- 2000
- Built-in 160 LED Zones Indicator Overview The TX7008 comprise of a range of analogue design and operation. The System is modular concept for easy tailoring of system design, to meet the full requirements of the project. The TX7008 Intelligent Fire Alarm Control Panel is designed and manufactured to meet the requirement of BS EN54 Part 2&4. The TX7008 is designed to provide early i informing the occupants of the building of potential smoke spread. Simultaneously, the TX7008 will alert and evacuate the occupants, and control all necessary auxiliary command functions such as elevator control, air handling shut down, gas shut off & damper control, as «iÀÌ ured though Command Builder Set-up.
Addressing T&A, Value range from 1 to 254 No. of Loop 6-to-8 Loop Protection Built-in 4kV Surge protection Power rating 16 to 24Vdc / 120mA Cabling 1.0Km Max Length/2 x 1.5mm²solid core Fire resistance Programmable Relays 4 circuits: Normally Open/Close Programmable Input
1 Circuit: Power limited 24Vdc
(for future use) Programmable Auxiliary Power 19 to 28 VDC (Note: Current Limited) Fixed Outputs (FPE/Sounder)
2 Circuits: 18 t0 28 VDC (Note:
Current Limited) Indicator 24 LED Status/ 160 Zone Indica- tors Display 7” TFT Touch Screen Keypad 5 Brigade buttons and Program- ming Keypad Dimension Lx W x H 550 mm x 510 mm x 222 mm Weight 23 Kgs Humidity 0 to 95% Relative Humidity, Non condensing Flat sheet Metal / with outer glass door, Orange stripe .QQR5RGEKƂECVKQPU Input/outputs Material / Color Compliance EN54-2:1997 +A1:2006, EN54-4:1997 + A1:2002 + A2:2006 Power Rating Networking and Interfaces Input Voltage 240VAC +10%-15%, 50/60Hz Input Current Consumption 1.3 A Panel to panel communication Can Bus [loop] Number of Panels 512 Interface Card USB, Optional: RS485 Serial, RS232 Serial, Ethernet Memory [Non-Volatile] 1000 Fire Events, 10,000 General Event Zones 3,000 programmable Total Group 3,000 programmable Sounder Group 1,000 programmable Common Group 2,000 programmable PSU Output to CIE 21.5 to 28.5 VDC Batteries 2 x 12V / 45AH (Recharge- able-Lead acid type battery) System Capacity 6GEJPKECN5RGEKƂECVKQP Cabinet Details www.tandauk.com +44 345 116 2945
Loop and Network Wiring Details Input/output Wiring Details www.tandauk.com+44 345 116 2945
Ordering Information
Part Number Image System Description Wall-mount. Fitted 4 loop card, up to 2032 addressable devices. Built-in Communication Card. Built-in 160 LED Zones Indicator. Ideal for Network Repeater Panel application. 550 mm x 510 mm x 222 mm Cabinet Size. Excluding Batteries. Optional Accessories: TX7814 Wall-mount. Fitted 3 loop card, up to 1524 addressable devices. Built-in Communication Card. Built-in 160 LED Zones Indicator. Ideal for Network Repeater Panel application. 550 mm x 510 mm x 222 mm Cabinet Size. Excluding Batteries. Optional Accessories: LC7008 , TX7814 Dual Loop Card for TX7008, capacity of 508 devices. CANBUS Network connection. Communication cable for connecting with up to 512 network FACP . USB Dongle Access control of TX7 panel series. Intelligent Addressable Fire Alarm Control Panel Intelligent Addressable Fire Alarm Control Panel Dual Loop Card Network card Dongle for TX7 www.tandauk.com +44 345 116 2945