LB6115AR PF | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

< 4-channel < Outputs Ex ia < Installation in Zone 2 or safe area < Line fault detection (LFD) < Positive or negative logic selectable < Simulation mode for service operations (forcing) < Permanently self-monitoring < Output with watchdog Function The digital output features 4 independent channels. The device can be used to drive solenoids, sounders, or LEDs. Open and short-circuit line faults are detected. The outputs are galvanically isolated from the bus and the power supply. Connection Zone 2 Div. 2 COM I IV Zone 0, 20 Div. 1 24 V Technical Data Slots Occupied slots 2 Supply Connection backplane bus / booster terminals Rated voltage Ur 12 V DC , only in connection with the power supplies LB9*** Input voltage range U 18.5 ... 32 V DC (SELV/PELV) booster voltage Power dissipation 3 W Power consumption 0.15 W Internal bus Connection backplane bus Interface manufacturer-specific bus to standard com unit Release date: 2021-11--

16 Date of

Release date: 2021-11-16 Date of issue: 2021-11-16 Filename: 254843_eng.pdf Germany: +49 621 776 2222 Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091

Field device Solenoid Valve Field device [2] audible alarm Field device [3] visual alarm Connection channel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-; channel IV: 7+, 8- Current limit Imax 70 mA Internal resistor Ri max. 90 Ω Open loop voltage 16.6 V Line fault detection can be switched on/off for each channel via configuration tool also when turned off (every 2.5 s the valve is turned on for 2 ms) Short-circuit < 100 Ω Open-circuit > 15 kΩ Response time 10 ms (depending on bus cycle time) Watchdog within 0.5 s the device goes in safe state, e.g. after loss of communication Reaction time 10 s Indicators/settings LED indication Power LED (P) green: supply Status LED (I) red: line fault , red flashing: communication error Coding optional mechanical coding via front socket Directive conformity Electromagnetic compatibility Directive 2014/30/EU EN 61326-1:2013 Conformity Electromagnetic compatibility NE 21 Degree of protection IEC 60529 Environmental test EN 60068-2-14 Shock resistance EN 60068-2-27 Vibration resistance EN 60068-2-6 Damaging gas EN 60068-2-42 Relative humidity EN 60068-2-56 Ambient conditions Relative humidity 95 % non-condensing Shock resistance shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 Vibration resistance frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 Mechanical specifications Degree of protection IP20 when mounted on backplane Connection removable front connector with screw flange (accessory) Mass approx. 150 g Dimensions 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) Data for application in connection with hazardous areas EU-type examination certificate PTB 03 ATEX 2042 X Marking 1 II (1)G [Ex ia Ga] IIC

1 II (1)D [Ex ia Da] IIIC

1 I (M1) [Ex ia Ma] I

Release date: 2021-11-16 Date of issue: 2021-11-16 Filename: 254843_eng.pdf Germany: +49 621 776 2222 Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091

Voltage Uo 18.9 V Current Io 286 mA Power Po 1351 mW Internal capacitance Ci 1.65 nF Internal inductance Li 0 mH Certificate PF 08 CERT 1234 X Marking 1 II 3 G Ex nA IIC T4 Gc Galvanic isolation Output/power supply, internal bus safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V Directive conformity Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 EN 60079-11:2012 EN 60079-15:2010 International approvals ATEX approval PTB 03 ATEX 2042 X IECEx approval BVS 09.0037X Approved for Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I General information System information The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure. Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. Assembly Front view LED red: Line fault/ Communication error LED green: Power supply Sockets for removable plugs blue (accessory) Space for labelling Digital Output LB6115AR Release date: 2021-11-16 Date of issue: 2021-11-16 Filename: 254843_eng.pdf Germany: +49 621 776 2222 Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091

Release date: 2021-11-16 Date of issue: 2021-11-16 Filename: 254843_eng.pdf LB6115AR Germany: +49 621 776 2222Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091 Digital Output Characteristic Curve Load calculation Output characteristics Us Imax Rload Ie Ue Rload = Field loop resistance Us Ie U (V) I (mA) Ri Imax Ue = Us - Ri x Ie Ie = Us/(Ri + Rload)