Technical content
< 4-channel < Outputs Ex ic < Installation in Zone 2 and safe area < Line fault detection (LFD) < Positive or negative logic selectable < Simulation mode for service operations (forcing) < Permanently self-monitoring < Output with watchdog Function The digital output features 4 independent channels. It can drive solenoids, sounders, or LEDs. Line faults are detected. The outputs are galvanically isolated from the bus and the power supply (EN 60079-11). Connection Zone 2 COM I IV 24 V Technical Data Slots Occupied slots 2 Supply Connection backplane bus / booster terminals Rated voltage Ur 12 V DC , only in connection with the power supplies LB9*** Input voltage range U 18.5 ... 32 V DC (SELV/PELV) booster voltage Power dissipation 3 W Power consumption 0.15 W Internal bus Connection backplane bus Interface manufacturer-specific bus to standard com unit Release date: 2021-11--
16 Date of
Release date: 2021-11-16 Date of issue: 2021-11-16 Filename: 254823_eng.pdf Germany: +49 621 776 2222 Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091
Field device Solenoid Valve Field device [2] audible alarm Field device [3] visual alarm Connection channel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-; channel IV: 7+, 8- Current limit Imax 37 mA Internal resistor Ri max. 370 Ω Open loop voltage 24.5 V Line fault detection can be switched on/off for each channel via configuration tool also when turned off (every 2.5 s the valve is turned on for 2 ms) Short-circuit < 100 Ω Open-circuit > 15 kΩ Response time 10 ms (depending on bus cycle time) Watchdog within 0.5 s the device goes in safe state, e.g. after loss of communication Reaction time 10 s Indicators/settings LED indication Power LED (P) green: supply Status LED (I) red: line fault , red flashing: communication error Coding optional mechanical coding via front socket Directive conformity Electromagnetic compatibility Directive 2014/30/EU EN 61326-1:2013 Conformity Electromagnetic compatibility NE 21 Degree of protection IEC 60529 Environmental test EN 60068-2-14 Shock resistance EN 60068-2-27 Vibration resistance EN 60068-2-6 Damaging gas EN 60068-2-42 Relative humidity EN 60068-2-56 Ambient conditions Relative humidity 95 % non-condensing Shock resistance shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 Vibration resistance frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 Mechanical specifications Degree of protection IP20 when mounted on backplane Connection removable front connector with screw flange (accessory) Mass approx. 150 g Dimensions 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) Data for application in connection with hazardous areas Output Voltage Uo 27.8 V Current Io 90.4 mA Power Po 629 mW Internal capacitance Ci 1.65 nF Digital Output LB6010AR Release date: 2021-11-16 Date of issue: 2021-11-16 Filename: 254823_eng.pdf Germany: +49 621 776 2222 Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091
Internal inductance Li 0 mH Certificate PF 08 CERT 1234 X Marking 1 II 3 G Ex nA [ic] IIC T4 Gc Galvanic isolation Output/power supply, internal bus safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V Directive conformity Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 EN 60079-11:2012 EN 60079-15:2010 International approvals IECEx approval BVS 09.0037X Approved for Ex nA [ic] IIC T4 Gc General information System information The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure. Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. Assembly Front view LED red: Line fault/ Communication error LED green: Power supply Socket for removable plug green (accessory) Space for labelling Digital Output LB6010AR Release date: 2021-11-16 Date of issue: 2021-11-16 Filename: 254823_eng.pdf Germany: +49 621 776 2222 Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091
Release date: 2021-11-16 Date of issue: 2021-11-16 Filename: 254823_eng.pdf LB6010AR Germany: +49 621 776 2222Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091 Digital Output Remarks:
- R ext represents the operating range (coil resistance + cable resistance).
- U represents the open circuit voltage.
- R a represents the internal impedance.
- Output current = U / (R a + Rext)
- Lim. represents the functional electronic current limitation. Product Versions U (V) R a ()L i m . ( m A ) R ext ()U o (V) I o (mA) P o (mW) Type/Order No.