LB3102A2 PF | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

HART Transmitter Power Supply, Input Isolator LB3102A2 < 1-channel < Input Ex ia < Mounting in Zone 2, Class I/Div.2 or in the safe area < Power supply for 2- or 3-wire transmitters with 4 mA ... 20 mA < Supply circuit 15 V (20 mA) < Input from active signals of 4-wire transmitters < HART communication via field bus or service bus < HART communication also for separately powered devices < Simulation mode for service operations (forcing) < Line fault detection (LFD) and Live Zero monitoring < Permanently self-monitoring < Module can be exchanged under voltage Function The transmitter power supply feeds 2- and 3-wire transmitters. Active signals from separately powered field devices and 4-wire transmitters can be connected. Open circuit, short circuit, and Live Zero status are detected. The intrinsically safe input is galvanically isolated from the bus and the power supply. Connection Zone 2 Div. 2 Zone 0, 20 Div. 1 COM I HART HART HART mA mA Technical Data Slots Occupied slots 1 Supply Connection backplane bus Rated voltage Ur 12 V DC , only in connection with the power supplies LB9*** Power dissipation 0.75 W Power consumption 1.1 W Internal bus Release date: 2021-12--

01 Date of

Release date: 2021-12-01 Date of issue: 2021-12-01 Filename: 254707_eng.pdf Germany: +49 621 776 2222 Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091

Interface manufacturer-specific bus to standard com unit Analog input Number of channels 1 Suitable field devices Field device pressure converter Field device [2] flow converter Field device [3] level converter Field device [4] Temperature Converter Field device interface Connection 2-wire transmitter Connection [2] 3-wire transmitter Connection [3] 4-wire transmitter Connection 2-wire transmitter (HART): supply circuit: 2/3+, 4/5- 3-wire transmitter (HART): supply circuit: 2/3+, 6- measuring circuit: 4/5+, 6- 4-wire transmitter (separately powered): measuring circuit: 4/5+, 6- HART measuring circuit: 1+, 6- Transmitter supply voltage min. 15 V at 20 mA ; 21.5 V at 4 mA Input resistance 15 Ω (terminals 5, 6) <P></P> 236 Ω (terminals 1, 6) HART Line fault detection can be switched on/off for each channel via configuration tool , configurable via configuration tool Short-circuit factory setting: > 22 mA configurable between 0 ... 26 mA Open-circuit factory setting: < 1 mA configurable between 0 ... 26 mA HART communication yes HART secondary variable yes Transfer characteristics Deviation After calibration 0.1 % of the signal range at 20 °C (68 °F) Influence of ambient temperature 0.1 %/10 K of the signal range Resolution 12 Bit (0 ... 26 mA) Refresh time 100 ms Indicators/settings LED indication Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1) red: line fault (lead breakage or short circuit) Status LED (2) yellow: Live Zero monitoring Coding optional mechanical coding via front socket Directive conformity Electromagnetic compatibility Directive 2014/30/EU EN 61326-1:2013 Conformity Electromagnetic compatibility NE 21:2007 Degree of protection IEC 60529:2000 Environmental test EN 60068-2-14:2009 Shock resistance EN 60068-2-27:2009 Vibration resistance EN 60068-2-6:2008 Damaging gas EN 60068-2-42:2003 Relative humidity EN 60068-2-78:2001 Ambient conditions Relative humidity 95 % non-condensing HART Transmitter Power Supply, Input Isolator LB3102A2 Release date: 2021-12-01 Date of issue: 2021-12-01 Filename: 254707_eng.pdf Germany: +49 621 776 2222 Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091

Shock resistance shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 Vibration resistance frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 Mechanical specifications Degree of protection IP20 when mounted on backplane Connection removable front connector with screw flange (accessory) Mass approx. 90 g Dimensions 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) Data for application in connection with hazardous areas EU-type examination certificate BVS 12 ATEX E 100 X Marking 1 II 3(1) G Ex nA [ia Ga] IIC T4 Gc

1 I (M1) [Ex ia Ma] I

1 II (1) D [Ex ia Da] IIIC

Power Po 619 mW (linear characteristic) Connection 1-6 Voltage 8.9 V Current 4 mA Power 24 mW (trapezoid characteristic curve) Input Voltage Uo 0.7 V Current Io 7 mA Power Po 5 mW (trapezoid characteristic curve) Internal capacitance Ci 242 nF Internal inductance Li 0 mH Galvanic isolation Input/power supply, internal bus safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V Directive conformity Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 EN 60079-11:2012 EN 60079-15:2010 International approvals ATEX approval BVS 12 ATEX E 100X UL approval E106378 IECEx approval BVS 13.0043X Approved for Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I General information System information The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure. Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. HART Transmitter Power Supply, Input Isolator LB3102A2 Release date: 2021-12-01 Date of issue: 2021-12-01 Filename: 254707_eng.pdf Germany: +49 621 776 2222 Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091

I P Front view Power LED green Diagnostic LED red/white Status LED red Status LED yellow Socket for removable plug blue (accessory) HART Transmitter Power Supply, Input Isolator LB3102A2 Release date: 2021-12-01 Date of issue: 2021-12-01 Filename: 254707_eng.pdf Germany: +49 621 776 2222 Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091