INSTALLA TION cont. WIR ING cont. Terminalconnections shown inFigure4 are fora standard SPD T sw itch.A ctuating the switch closesone circuit and simultaneously opens the second circuit.In thisdiagram, circuitbetwee n contacts 4 and 5 is mad e and circuit betwe en contact 5 and 6 isbroken at low liquid level.At high level,circuitbetween contacts 4 and 5 isbroken and circuitbetween contact5 and 6 ismade. DIFFERE NT IAL ADJUSTMENT The amou ntofleveltravelbetween “switchon” and “switch off” can be reduced from the m aximum factory settingby raising the low er setof jam nuts.Minimum free play(differ - ential)ofm agneticsleeve is1⁄32 ". 1. Disconnect wiringfrom supp lyside of switch me cha - nism and electricalconduit or operating m edium line connections to switchhousing. 2. Perform system shut-down as requiredto relievepres - sure from tank or vesseland drain offliqu id “head” above controlmo untingposition.Allowunittocool. 3. Re move sw itchhousingassem blyby loosening enclos - ing tube nut located immed iately below housing base. Re fertoFigure8 on page 7. 4. W ith switch housing remo ved,jam nuts and mag netic sleeve are now accessible, as show n in Figure 6. R aisingthelowerjam nuts willreduce thedifferential.As the firststep inany adjustment procedure,the position ofthe upper and lowerjam nuts shouldbe established. NEVER C H ANG E SETTI NG OF UPPER JAM NUTS AS THEY SUP POR T FLOAT ASSEM BLY SO THA T IT CA N - NOT TOUCH B OTT OM OF CHAM BER. 5. Loosen and remove upp er jam nuts,guide w asher,and m agneticsleeve.Lowerjam nuts may now be adjusted to reduce thedifferential. NO TE: Be certain totighten jam nuts securelyafteradjustme nt. 6. Replace ma gnetic sleeve on stem and position upperjam nuts to theiroriginalsetting.Lock upperjam nuts to guide w asher. 7. Reassem ble controlin reverse ofsteps 1 through 3,previ - ouslydescribed. 8. Testswitch actuationby varying liquidlevelintankorvessel. Figure 4 Figure 5 Figure 6 CA U TION: Before attemp ting any wo rk on the control, be certain to pu lldisconnect switch or otherwise assure that electrical circuit(s) throug h con trolis de activated. Close op eratingmediu m sup plyvalve on controls equ ip - me nt with pneu ma ticswitch mechan ism s. Receiver From Condenser To Evaporator INSTALLATION SHOWING LEVEL CONTROL (OR ALARM) ON A RECEIVER Desired Actuating Level Insulation End ViewSide View Chamber mark indicates actuating level DO NOT Insulate Switch Housing Mount controlso mark on chamber correspondsto leveldesired in vessel.When controlisused on a low temperature liquid, chamber and connectionlinesshould be insulatedas shown to prevent“boiling”inthefloatchamber and falselevelindications
4 RED
6 BLUE
Jam nuts. Slight play (gap) must be allowed (.03" [.8 mm] typical) Differential gap Magnetic sleeve
Periodic inspections are a necessarymean s to keep your Magnetrolcontrolingood wo rking order.Thiscontrol is,inreality,a safety deviceto protectthe valuableequipme nt itserves. Therefore,a systematicprogram of “Preventive Maintenance” should be implem ented wh en controlis placedinto service.Ifthe following sectionson “What To Do” and “Wh atTo Avoid” areobserved,yourcontrolw illprovidereliableprotection ofyourcapitalequipme nt. What To Do 1. K eep Co ntrolClean — B e sure the switchhousing cover is alw ays inplace on the control.Thiscover isdesigned to keep mois - ture laden airand corrosive gases as wellas dirt aw ay from the switchmech anism.In addition,itacts as a safetyfeatureby keeping bare wires and termi - nalsfrom being exposed.B e surecover istightened allthew ay dow n toensurecom pressionofquad ring seal.Should the housingcover becom e damaged or misplaced,ordera replacementimme diately. 2. Inspect Switch Me ch an isms, Te rmina ls, and Con nections M onthly — Switches shouldbe inspected forexcessive wear on actuating lever or m isalignment of adjustmentscrew at pointof contact betwee n screw and lever.Su ch w earcan cause falseswitchactuating levels. D o NO T operateyourcontrolwithdefectiveor maladjusted sw itch me chanisms (referto bulletinon switchm echanism furnished forserviceinstructions). — Mag netrolcontrols ma y sometimes be exposed to excessive heat or moisture.U nder such conditions, insulation on electricalwires may become brittle, eventuallybreaking or peelingawa y.The resulting “bare” w ires can cause shortcircuits.Ch eck w iring carefully and replace atfirstsignorbrittleinsulation. — Vibration may sometim es cause terminalscrews to w ork loose. Check allterminalconn ections to be certain thatscrews aretight. W hatTo A void 1. N EVER leave switch housing cover off the control longerthannecessarytom ake routineinspections. 2. NE VER use lubricationon pivotsofswitchmechanisms. A sufficientam ount of lubricanthas been appliedatthe factory to ensure a lifetime of service.Further oiling is unnecessaryand willonlytend to attractdust and dirt which can interferewithm echanism operation. 3. NE VER place a jumper wire across terminalsto “cut- out” the control.If a “jumper”isnecessaryfortestpur - poses,be certainitisremoved before placingcontrol intoservice. 4. NE VER attempttom ake adjustmentsorreplaceswitch - es withoutreadinginstructionscarefully.Certainadjust - m entsprovidedforinMagnetrolcontrolsshouldnot be attempted in thefield.W hen indoubt,consultthefactory oryourlocalrepresentative.
Us uallythefirstindication ofimproperoperationisfailureof the controlled equipmentto function,i.e.pump willnot start (or stop),signallights failto light,etc.When these occur, wh etherattime ofinstallationorduringroutineservicethere - after,check the followingpotentialexternalcauses first. — Fuses m ay be blown. — R esetbutton(s)m ay need resetting. — Po w erswitch m ay be open. — C ontrolled equipmentm ay be faulty. — W iring lines leadingtocontrolmay be defective. If a thorough inspectionofthesepossibleconditions failsto locate the trouble,proceed next to a check of the controls sw itch m echanism. 1. Pulldisconnect switch or otherwiseassure thatelectri - calcircuit(s)through controldeactivated. 2. Re move sw itch housing cover. 3. Sw ing mag net assemb ly in and out by hand to check carefully for any sign of binding.Assembly should require a minimum of forceto mo ve itthrough its full sw ing. 4 . If binding exists,m agnet may be rubbing enclosingtube or pivot sockets may be overly tight.Read just pivot socketsas required untila slightam ount of sideplayis evident.If magn et is rubbing, loosen ma gnet clamp screw and shiftma gnetposition. 5. Ifsw itchmag netassem blyswings freelyand mechanism stillfailsto actuate,check installationof controlto be certain itiswithinthe specifiedthree degrees ofvertical (usespiritlevelon sideof enclosing tube in two places, 90° apart). 6. Check the continuityof m icroswitch with ohmm eter. Re place immed iatelyifdefective. NOTE :As a ma tterofgood practice,spare switchesshould be kepton hand atalltimes. If switch m echanism isoperatingsatisfactorily,a testofthe comp letecontrolsperforman ce isthenextlikelystep. 1. Re connec t power supply and carefullyactuateswitch me chanism ma nually(using a nonconduc tive tool)to determine wh ethercontrolledequipmen tw illoperate. 2. If controlled equipme nt responds to m anualactuation test,troublemay be locatedinthe levelsensingportion of the control (float,stem, and mag neticattraction sleeve). NOTE :Ch eck firstto be certainrefrigerant isenteringfloat ch amb er.A valve ma y be closed or pipe line plugged. 3. D epressurize and rem ove E-tube, proceed to check levelsensingactionby removingswitchhousingassem - bly,as described in “DifferentialAdjustment” instruc - tions. 4. Inspect attraction sleeve and inside of enclosing tube forexcessive corrosionor solidsbuildupwhich could restrictm ovem ent,preventing sleevefrom reachingfield ofswitchm agnet. 5. If differentialadjustment has been changed inthe filed by repositioningthe lower jam nuts on the floatstem, check fortightnessand positionofthejam nuts. NOTE :Differentialad justment affects a change in the am ount of level travelbetween “switch-on” and “switch-off”actuations.Do NOT attemptadjustment without first consulting factory for assistance in compu tingleveldifferentialchange foryourcontrol. 6. Check float to be certainitisbuoyant inthe refrigerant (floatcham ber m ust have adequate refrigerantlevel).If floatisdeterminedtobe filledwithliquidor collapsed,it m ustbe replaceimm ediately.Do NOT attem ptto repair a float. If allcom ponents inthe controlare inoperatingcondition, the troublemust be (andshouldbe)locatedexternallytothe control.R epeat inspectionofexternalconditionspreviously described. NOTE :W hen indoubt about the conditionor performance of a Magnetrolcontrol,return itto the factory.See “ServicePolicy”on the back page. C AU TIO N : W ith electrical powe r “on”, care sho uld be taken to avoid contact with switch leads and connections atterminalblocks.
NEMA 4X — 4.25 (108) NEMA 4X/7/9 — 6.00 (152) 1/2" NPT Conduit Connection may be rotated through 360° 24.00 (610) Long wires furnished 15.00 (381) 10.00 (254) 3/4" NPT 3/4" Socket weld 5.75 (146) 3/4" NPT 3/4" Socket weld 4.25 (108) 2.81 (71) RRISING LEVEL FALLING LEVEL L SPECIFICA TIONS Dimen sionalspecifications Inches (mm ) NOTES: 1. Floatchamber has floatcushioningspring. 2. Allow3.50(89)NEMA 4 or4.12 (105)NEMA 7/9 overhead clearanceforcoverremoval. 3. Alldimensionsin( )areinmillimeters. Agen cy approvals B asicelectricalratings Actuating LiquidSpecificGravity NO TE: A ctuatinglevelsare factory set for maximum differentialbetwee n sw itch actuation.Internaladjustment provided forreduced differential. Levels±0.25"(6mm) Agency Model Number Approval CSA J52-41X1-00X J52-41X2-00X Non-Hazardous TYPE 4X FM J52-41XX-00X Non-Hazardous NEMA 4X J52-41X2-00X ClassI,Div.1,Groups C & D ClassII ,Div.1 Groups E,F & G Voltage Non-inductiveAmpere Rating Dry Contact 120 VAC 15.00 240 VAC 15.00 24 VDC 6.00 120 VDC 0.50 240 VDC 0.25 Figure7
NOTES: 1. Replacement assemblieslistedare furnishedinkitform only forstandard base model. Consult localrepresentativefor orderingassistanceon specialmodel replacement partsor accessoriesnotincludedinabove listing. 2. Conduitcompression type sealfittingpartsnot availableform factoryforexplosionproofhousingwhich has 1"NPT outlet. IMPORTANT: When ordering,pleasespecify: A.Model and Serialnumber ofcontrol. B. Name and Number ofreplacementassembly. REP LACEMENT PARTS Figure8 Item D escription J52-4101 -002 J52-4102 -002 J52-4107 -004 J52-4111-0 02 J5 2-4112-00 2 1 Housing Cove r 089-6526-001 089-6582 -001 089-6522-001 089-6526-001 08 9-658 2-001 2 Housing B ase 089-6527 -001 089-6527 -001 089-6527-001
3 Sw itch Mechanism 089-74 01-102 089-74 01-102 089-74 01-102 089-7 401-102 08 9-74 01-102
4 E-Tube Z32-6301-038 Z32-6325-001 Z32-6325-007 Z32-6301-038 Z32-6325-001
5 E-Tube Gas ket 012-1301-002
6 AttractionSleeve 032-41 01-013
7 Cham berA ssembly Z33-3105-001 Z33-3107-001 Z33-3105-001
8 Jam Nuts (4) 010-2106-004
9 G uide Wa sher 010-3351-001
B ULLETIN: 46-627.4 EFFECTIV E: August 2010 SU PERSEDE S: August 2006 PR ODUCT WA R R A NTY A llMagnetrolme chanical leveland flow controlsare war - ranted free of defects inm aterialsor workman ship forfive fullyears from thedateoforiginalfactoryshipment. If returned w ithin the wa rranty period;and, upon factory insp ec tion of the con trol,the ca use of the claim is de termined to be cove red und er the warr an ty;then, Magnetrolw illrepairor replacethe controlatno costtothe purchaser(orow ner)otherthantransportation. Ma gnetrolshallno t be liableformisapplication,labor claims,directorconsequentialdamage or expense arising from the installationoruse ofequipment.There areno other w arranties expressed or implied,except specialwritten w arranties coveringsom e Magnetrolproducts. Q UA LITY A SSURANCE The quality assurance system inplace at Magnetrolguarantees the highest levelof qualitythroughout the comp any.Magnetrol is com m itted to providing fullcustomer satisfactionboth inqualityproduc ts and qualityservice. Magnetrol’s qu al ity assurance system is registered to ISO 9001 affirming its com mitm ent to known international qu ality standa rds providing the stronges t assurance of product/servicequalityavailable. IMP ORTAN T SE RVICE POLICY Ow nersofMagnetrolm ay request the return ofa controlor any part of a controlforcomp lete rebuilding or replace - m ent.They willbe rebuiltor replaced promptly.Controls returned unde r our servicepolicy must be returned by Prepaid transportation.Magnetrolwillrepairor replace the controlat no cost to the purchaser (orowner)otherthan transportation if: 1. Re turned withinthewa rranty period;and 2. The factory inspection findsthe cause of the claimto be covered underthewarranty. If the troubleisthe resultof conditionsbeyond our control; or,isNOT covered by thewarranty,therewillbe charges for laborand the partsrequiredtorebuildorreplacetheequip - m ent. In some cases itmay be expedient to ship replacemen t parts;or,in extreme cases a complete new control,to replace the originalequipme ntbeforeitisreturned.If thisis desired,notify the factoryofboth the mod eland serialnum - bersof the controlto be replaced.In such cases,creditfor the m aterialsreturned willbe determinedon thebasisofthe applicabilityofourwarranty. No claims for m isapplication,labor,director consequential dam age willbe allowed. RE TURN M A TERIAL PROCE DURE So that we m ay efficientlyprocess any materialsthat are returned , it is essential that a “R eturn Ma terial A uthorization” (RMA)num ber be obtainedfrom the factory, prior to the mat erial’sreturn.This is availablethroug h Magnetrollocalrepresentativeor by contactingthe factory. Pleasesupplythefollowing information: 1. Com pany Nam e 2. D escription ofMaterial 3. SerialNu m ber 4. R eason forR eturn 5. A pplication An y unitthat wa s used in a process m ust be properly cleaned in accordance with O SH A standards,before itis returnedtothefactory. A Ma terialSa fety D ata Sheet (MSDS) must accompany m aterialthatwas used inany med ia. A llshipments returnedto the factorymust be by prepaid transportation. A llreplacementswillbe shippedF.O.B.factory. AS SURED QU AL ITY & SE RV ICE COST LESS 5300 Belmont Road • Downers Grove, Illinois 60515-4499 • 630-969-4000 • Fax 630-969-9489 • www.magnetrol.com
145 Jardin Drive, Units 1 & 2 • Concord, Ontario Canada L4K 1X7 • 905-738-9600 • Fax 905-738-1306
Heikens straat 6 • B 9240 Zele, Belgium • 052 45.11.11 • Fax 052 45.09.93 Regent Business Ctr., Jubilee Rd. • Burgess Hill, Sussex RH15 9TL U.K. • 01444-871313 • Fax 01444-871317 Copyright © 2010 Magnetrol International, Incorporated. All rights reserved. Printed in the USA. LO W VO LTAGE DIRECT IVE Foruse in C ategoryII installations.Ifequipme ntisused ina m anner not specifiedby m anufacturer,protectionprovided by equipmen tm ay be impaired.