Technical content
< 1-channel < Loop powered < NAMUR sensor simulator and pulse generator < Simulates line faults Function This simulator imitates a NAMUR proximity sensor by implementing a three-position switch. A three-position switch facilitates the selection of various test conditions. The first position (NAMUR voltage) simulates a 1 kΩ resistive load, while the second position (sensor static) offers various sensor-damping conditions, including a short circuit simulation. The third switch position (sensor dynamic) offers the user several frequency settings between 0.1 Hz ... 1 kHz using a rectangular wave with a 50 % duty cycle. Connection IS01 Zone 0, 1, 2 Div. 1, 2 NAMUR 0,4 mAJ > 2 mA J > 7 mAJ > 2 mA OK< 7 V > 9 VG Technical Data Supply Connection loop powered Indicators/settings Control elements slide switches Configuration via slide switches Directive conformity Electromagnetic compatibility Directive 2014/30/EU EN 61326-1:2013 (industrial locations) Conformity Electromagnetic compatibility NE 21 Degree of protection IEC 60529 Release date: 2020-09--
23 Date of
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 119114_eng.pdf Germany: +49 621 776 2222 Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091
Mass approx. 70 g Dimensions 40 x 130 x 25 mm (1.6 x 5.1 x 1 inch) Construction type gray ABS handheld housing Data for application in connection with hazardous areas EU-Type Examination Certificate DMT 02 ATEX E 008 Marking 1 II 1G EEx ia IIB T4 Voltage Ui 16 V DC Current Ii 55 mA Power Pi 245 mW Directive conformity Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 General information Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. Assembly > 9V OK < 7V 0,1 Hz 1 Hz 10 Hz 100 Hz 1000 Hz Front view LED red LED yellow: Switching state Switch position 1 "not damped" Switch position 2 "damped" Switch position 3 "short circuit" LED green LED yellow Function switch "NAMUR voltage" "Sensor, static" "Sensor dynamic" LED yellow Frequency adjustment switch Simulator IS01 Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 119114_eng.pdf Germany: +49 621 776 2222 Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 119114_eng.pdf IS01 Germany: +49 621 776 2222Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091 Simulator Additional Information Operation: The simulator is used instead of a sensor and is connected to an input to EN 60947-5-6 NAMUR. Three different test functions may be selected using the function switch. Switch position "NAMUR voltage" The voltage of the control circuit can be tested according to EN 60947-5-6 NAMUR. In this case the initiator simulator has an internal resistance of 1 k. Function switch position "sensor static"
- Switch position 1 control circuit J > 2.1 mA (Initiator not damped)
- Switch position 2 control circuit J about 0.4 mA (Initiator damped)
- Switch position 3 control circui t J > 7.0 mA (Lead short circuit) Function switch position "sensor dynamic" A quartz controlled rectangular wave controller produces a signal with a duty ratio of 50 % : 50 %. The frequency can be adjusted from 0.1 Hz up to 1 kHz using the slide switch.