Specifications are subject to change without notice (20.05.05) 1 Proximity Sensors Inductive Thermoplastic Polyester Housing Types IA, M12, M18 and M30, NAMUR
- Euronorm thermoplastic polyester housing, cylindrical
- Short or long versions
- Diameter: M12, M18, M30
- Sensing distance: 2 to 15 mm
- Output: NAMUR EN 50 227
- Protection: Reverse polarity
- LED-indication
- 2 m cable or M12 plugProduct Description EN 60 947-5-2. For metal ver- sions refer to type IA 12 E... able. Proximity switch in M12, M18 and M30 polyester housings. Made in accor dance with euronorms EN 50 227 and Type Housing size Housing type Sensing function Sensing distance Output type Plug Type Selection Housing Body Connection Rated operating Ordering no. diameter style distance (S n) NAMUR M12 Short Cable 2 mm 1) IA 12 CSF 02 UC M12 Short Plug 2 mm 1) IA 12 CSF 02 UC M1 M12 Long Cable 2 mm 1) IA 12 CLF 02 UC M12 Long Plug 2 mm 1) IA 12 CLF 02 UC M1 M12 Short Cable 4 mm 2) IA 12 CSN 04 UC M12 Short Plug 4 mm 2) IA 12 CSN 04 UC M1 M12 Long Cable 4 mm 2) IA 12 CLN 04 UC M12 Long Plug 4 mm 2) IA 12 CLN 04 UC M1 M18 Short Cable 5 mm 1) IA 18 CSF 05 UC M18 Short Plug 5 mm 1) IA 18 CSF 05 UC M1 M18 Long Cable 5 mm 1) IA 18 CLF 05 UC M18 Long Plug 5 mm 1) IA 18 CLF 05 UC M1 M18 Short Cable 8 mm 2) IA 18 CSN 08 UC M18 Short Plug 8 mm 2) IA 18 CSN 08 UC M1 M18 Long Cable 8 mm 2) IA 18 CLN 08 UC M18 Long Plug 8 mm 2) IA 18 CLN 08 UC M1 M30 Short Cable 10 mm 1) IA 30 CSF 10 UC M30 Short Plug 10 mm 1) IA 30 CSF 10 UC M1 M30 Long Cable 10 mm 1) IA 30 CLF 10 UC M30 Long Plug 10 mm 1) IA 30 CLF 10 UC M1 M30 Short Cable 15 mm 2) IA 30 CSN 15 UC M30 Short Plug 15 mm 2) IA 30 CSN 15 UC M1 M30 Long Cable 15 mm 2) IA 30 CLN 15 UC M30 Long Plug 15 mm 2) IA 30 CLN 15 UC M1 1) For flush mounting in metal 2) For non-flush mounting in metal Ordering Key IA 12 CSF 02 UC M1
2 Specifications are subject to change without notice (20.05.05) IA 12, IA 18 and IA 30, NAMUR Specifications Rated operational volt. (Ue) 8.2 VDC (UB) 7 to 9 VDC (6 to 35 VDC, all specifica- tions not observed in extended supply range) Self-inductance ≤ 500 µH Self-capacitance ≤ 120 nF No-load supply current (Io) Activated: ≤1 mA Not activated: ≥ 2.2 mA Max. 9.35 mA Protection Reverse polarity Transient voltage ≤ 1 kV/0.5 J EMC Approved according to EN 50 080, EN 50 081 Power ON delay < 10 ms Frequency of operating cycles (f) IA12xxF02 1.400 Hz IA12xxN04 1.200 Hz IA18xxF05 500 Hz IA18xxN08 200 Hz IA30xxF10 300 Hz IA30xxN15 100 Hz Indication not activated LED, yellow Assured operating dist. (Sa)0 ≤ Sa ≤ 0.81 Sn Repeat accuracy (R) ≤ 5% Dimensions Type A B C D E F SW Ø mm mm mm mm mm mm IA 12 CSF 02 UC M12 x 1 x 30 10.7 30 11 5.0 8 17 IA 12 CLF 02 UC M12 x 1 x 50 10.7 50 11 5.0 8 17 IA 12 CSF 02 UC M1 M12 x 1 x 30 10.7 30 12.6 11.9 8 17 IA 12 CLF 02 UC M1 M12 x 1 x 50 10.7 50 12.6 11.9 8 17 IA 12 CSN 04 UC M12 x 1 x 30 10.7 34 11 5.0 8 17 IA 12 CLN 04 UC M12 x 1 x 50 10.7 54 11 5.0 8 17 IA 12 CSN 04 UC M1 M12 x 1 x 30 10.7 34 12.6 11.9 8 17 IA 12 CLN 04 UC M1 M12 x 1 x 50 10.7 54 12.6 11.9 8 17 IA 18 CSF 05 UC M18 x 1 x 30 16.7 30 11.6 15.4 8 24 IA 18 CLF 05 UC M18 x 1 x 50 16.7 50 11.6 15.4 8 24 IA 18 CSF 05 UC M1 M18 x 1 x 30 16.7 30 13.1 11.9 8 24 IA 18 CLF 05 UC M1 M18 x 1 x 50 16.7 50 13.1 11.9 8 24 IA 18 CSN 08 UC M18 x 1 x 30 16.7 38 11.6 15.4 8 24 IA 18 CLN 08 UC M18 x 1 x 50 16.7 58 11.6 15.4 8 24 IA 18 CSN 08 UC M1 M18 x 1 x 30 16.7 38 13.1 11.9 8 24 IA 18 CLN 08 UC M1 M18 x 1 x 50 16.7 58 13.1 11.9 8 24 IA 30 CSF 10 UC M30 x 1.5 x 30 28 30 13.6 15.4 10 36 IA 30 CLF 10 UC M30 x 1.5 x 50 28 50 13.6 15.4 10 36 IA 30 CSF 10 UC M1 M30 x 1.5 x 30 28 30 13.6 11.9 10 36 IA 30 CLF 10 UC M1 M30 x 1.5 x 50 28 50 13.6 11.9 10 36 IA 30 CSN 15 UC M30 x 1.5 x 30 28 42 13.6 15.4 10 36 IA 30 CLN 15 UC M30 x 1.5 x 50 28 62 13.6 15.4 10 36 IA 30 CSN 15 UC M1 M30 x 1.5 x 30 28 42 13.6 11.9 10 36 IA 30 CLN 15 UC M1 M30 x 1.5 x 50 28 62 13.6 11.9 10 36 Hysteresis (H) (Differential travel) 1 to 15% of sensing distance Effective operating dist. (Sr) 0.9 x Sn ≤ Sr ≤ 1.1 x Sn Usable operating dist. (S) 0.9 x S r ≤ Su ≤ 1.1 x Sr Ambient temperature Operating -25° to +70°C (-13° to +158°F) Storage -30° to +80°C (-22° to +176°F) Degree of protection IP 67 (Nema 1, 3, 4, 6, 13) Housing material Body Grey thermoplastic polyester Back Black polyester Connection Cable 2 m, 2 x 0.5 mm 2, grey PVC, oil proof Plug M12 x 1 Cables for plug (-1) CONH1A serie Weight (cable excluded) IA 12xx 10 g IA 18xxF05 18 g IA 18xxN08 20 g IA 30xxF10 50 g IA 30xxN15 70 g Tightening torque IA 12 1.8 Nm IA 18 2.6 Nm IA 30 7.5 Nm Approvals UL CE-marking Yes
Specifications are subject to change without notice (20.05.05) 3 NAMUR, Amplifier Relays > SD 110/210. > SD 170/270. IA 12, IA 18 and IA 30, NAMUR Cable C D E F SW A LED B Plug C D E F SW A LED M12 x 1 B Refer to Technical information. Dimensions (cont.) Installation Hints Relief of cable strain Protection of the sensing face Switch mounted on mobile carrierTo avoid interference from inductive voltage/ current peaks, separate the prox. switch pow- er cables from any other power cables, e.g. motor, contactor or solenoid cables Incorrect Correct The cable should not be pulled A proximity switch should not serve as mechanical stop Any repetitive flexing of the cable should be avoided Wiring Diagram BN R BU 1 K 8.2 V