GT5P IDEC | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 11

Technical content

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC G Timers Specifications Rated Operating Voltage 100 to 120V AC (50/60Hz) 200 to 240V AC (50/60Hz) 24V AC/DC 12V DC Voltage Tolerance AC type: ±15% DC type: ±10% (ripple 10% maximum) Contact Rating Resistive load 120V AC/24V DC, 5A 240V AC, 3A Inductive load 240V AC, 0.8A 120V AC, 1.4A 24V DC, 1.7A Allowable Contact Power (resistive load) 960VA AC 120W DC Contact Form SPDT Voltage 250V AC, 150V DC Repeat Error ±0.2% ±10msec Voltage Error ±0.5% ±10msec Temperature Error ±3% maximum (over –10 to 50°C, reference temperature 20°C) Setting Error ±10% maximum Reset Time When turning power off after time up: 0.1 sec maximum When turning power off before time up: 1 sec maximum Insulation Resistance 100M Ω minimum Dielectric Strength 2000V AC, 1 minute (except between contacts of the same pole) Vibration Resistance 100N (approximate 10G) Shock Resistance Operating extremes: 100N (approximate 10G) Damage limits: 500N (approximate 50G) Power Consumption 100V AC type: 1.5VA (at 50Hz) 200V AC type: 1.6VA (at 50Hz) 24V DC type: 0.9W Electrical Life 100,000 operations minimum (at rated load) Mechanical Life 20,000,000 operations minimum Operating Temperature –10 to +50°C Operating Humidity 45 to 85% RH GT5P Series — ON Delay Timers 1.Inductive load (reference), cosθ =.3 to .4 or L/R=15msec. 2.Minimum applicable load: 5VDC/10mA (reference). Key features of the GT5P series include:

  • SPDT, 5A contacts
  • 8-pin, octal base
  • 9 time ranges
  • Repeat error ±0.2% maximum
  • Control settings by hand or screwdriver
  • Power ON and timing out LED indicators
  • Uses the same sockets and hold down clips as IDEC’s RR2P 8-pin relays UL Recognized File No. E55996 CSA Certified File No. LR66809 GT5P Table of Contents Specifications — G-58 Part Numbering List — G-59 Timing Diagrams / Schematics — G-60 GT5P Accessories — G-61 GT5P Dimensions — G-62 Timing Diagrams Overview — G-4

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC G-59 G Timers Mode of Operation Contact Output Rated Voltage Time Range Complete Part No. ON-Delay SPDT 24V DC/ 120V AC, 240V AC, 100 to 120V AC 1S — 3S GT5P-N3SA100 6S — 10S GT5P-N10SA100 30S GT5P-N30SA100 60S GT5P-N60SA100 3M GT5P-N3MA100 6M GT5P-N6MA100 10M GT5P-N10MA100 200 to 240V AC 1S GT5P-N1SA200 3S — 6S GT5P-N6SA200 10S GT5P-N10SA200 30S GT5P-N30SA200 60S GT5P-N60SA200 3M GT5P-N3MA200 6M GT5P-N6MA200 10M GT5P-N10MA200 24V AC/DC 1S GT5P-N1SAD24 3S — 6S GT5P-N6SAD24 10S GT5P-N10SAD24 30S — 60S GT5P-N60SAD24 3M — 6M GT5P-N6MAD24 10M GT5P-N10MAD24 12V DC 1S — 3S — 6S — 10S GT5P-N10SD12 30S GT5P-N30SD12 60S GT5P-N60SD12 3M — 6M — 10M GT5P-N10MD12 Part Numbering List For sockets and accessories, see page G-61.

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC G Timers SPDT ON-Delay Timing Diagram/Schematic/Electrical Life Curves Operation Mode POWER (+)(-) Do not apply voltage to terminals 1, 3, and 4. OUT Item Power Delayed Indicator Terminal No. Operation 2-7(Power) 5-8(NC) 6-8(NO) POWER Set Time Contact 0 12345 Load Current (A) 100 Life (x 10,000 operations) 24V DC Resistance Load 120V AC Resistance Load 240V AC Resistance Load 24V DC Induction Load 120V AC Induction Load 240V AC Induction Load Electrical Life Curves

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC G-61 G Timers Installation of Hold-Down Springs Part Numbers: Mounting Accessories and Sockets Applicable Hold-Down Springs Style Appearance Use with Timers Part No. Appearance Part No. DIN Rail/ Surface Mounting Accessories 8-Pin Screw Terminal (dual tier) GT5P SR2P-05 SFA-203 8-Pin Fingersafe Socket GT5P SR2P-05C 8-Pin Screw Terminal GT5P SR2P-06 SFA-202 DIN Mounting Rail Length 1000mm — BNDN1000 Part Numbers: Mounting Accessories and Sockets Applicable Hold-Down Springs Mounting Accessories 8-Pin Solder Terminal SR2P-51 SFA-402 Mounting Accessories DIN Rail Mount Socket Panel Mount Socket Socket SR2P-06 Hold-down Spring (sold separately) SFA-202 (use two springs) Insert the springs into the outer slots with the projections facing inside. Socket SR3P-05 Insert the springs into the slots. Hold-down Spring (sold separately) SFA-203 (use two springs) 8-pin Socket SR2P-511 Hold-down Spring SFA-402 Insert

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC G Timers Dimensions: GT5P Series GT5P Timer, 8-Pin with SR2P-05 GT5P Timer, 8-Pin with SR2P-06 (When using DIN Rail) DIN Rail (BAA/BAP/BADA) Hold-down spring 98 maximum When using BAA/BAP: 102 maximum 16.5 28.5 523 ø25 7.5 61 13 (When using DIN Rail) Hold-down Spring DIN Rail 91.5 maximum When using BAA/BAP: 95.5 maximum 7.5 61 13 1.7 31.7 60118

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC G-63 G Timers GT5Y-2 GT5Y-4 Specifications Rated Operating Voltage 100 to 120V AC (50/60Hz) 200 to 240V AC (50/60Hz) 24V DC 24V AC 12V DC Contact Form DPDT 4PDT Rated Load Resistive Load 220V AC, 5A 30V DC, 5A 220V AC, 3A 30V DC, 3A Inductive Load 220V AC, 2A 30V DC, 2.5A 220V AC, 0.8A 30V DC, 1.5A Allowable Contact Power Resistive Load 1100VA AC 150W DC 660VA AC 90W DC Inductive Load Cos Ø = 0.3 L/r = 7msec 440VA AC 75W DC 176VA AC 45W DC Allowable Voltage 250V AC, 125V DC Allowable Current 5A 3A Temperature Error ±3% maximum (over –10 to 50°C, reference temperature 20°C) Setting Error ±10% maximum Reset Time When turning power off after time up: 0.1 second maximum When turning power off before time up: 1 second maximum Insulation Resistance 100M Ω minimum Dielectric Strength 2,000V AC, 1 minute (except between contacts of the same pole) Vibration Resistance 100N (approximate 10G) Shock Resistance Operating extremes: 100N (approximate 10G) Damage limits: 500N (approximate 50G) Power Consumption 100V AC type: 1.5VA (at 50Hz) 200V AC type: 1.6VA (at 50Hz) 24V DC type: 0.9W Electrical Life 500,000 operations minimum (220V AC, 5A) 200,000 operations minimum (110V AC, 3A) Mechanical Life 50,000,000 operations minimum 50,000,000 operations minimum Operating Temperature –10 to +50°C Operating Humidity 45 to 85% RH GT5Y Series — ON Delay Timers 1. Minimum applicable load: GT5Y-2: 5V DC, 20mA (reference value); GT5Y-4: 5V DC, 10mA (reference value). 2. Inductive load: cosθ =.3, L/R=7msec. Key features of the GT5Y series include:

  • 4PDT, 3A or DPDT, 5A contacts
  • 4 time ranges
  • Repeat error ±0.2% maximum
  • Control settings by hand or screwdriver
  • Power ON and timing out LED indicators
  • Uses the same sockets and hold-down clips as IDEC’s RY4S and RU series relays UL, c-uL Listed File No. E55996 GT5Y Table of Contents Part Number List — G-64 Timing Diagrams — G-65 GT5Y Accessories — G-66 GT5Y Dimensions — G-67

G-64 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC GTimers Timing Ranges Mode of Operation Contact Output Rated Voltage Time Range Complete Part No. ON-Delay DPDT 220V AC/ 30V DC, 5A 100 to 120V AC 1S/10S/1M/10M GT5Y-2SN1A100 3S/30S/3M/30M GT5Y-2SN3A100 6S/60S/6M/60M GT5Y-2SN6A100 200 to 240V AC 1S/10S/1M/10M GT5Y-2SN1A200 3S/30S/3M/30M GT5Y-2SN3A200 6S/60S/6M/60M GT5Y-2SN6A200 12V DC 1S/10S/1M/10M GT5Y-2SN1D12 3S/30S/3M/30M GT5Y-2SN3D12 6S/60S/6M/60M GT5Y-2SN6D12 24V DC 1S/10S/1M/10M GT5Y-2SN1D24 3S/30S/3M/30M GT5Y-2SN3D24 6S/60S/6M/60M GT5Y-2SN6D24 24V AC 1S/10S/1M/10M GT5Y-2SN1A24 3S/30S/3M/30M GT5Y-2SN3A24 6S/60S/6M/60M GT5Y-2SN6A24 4PDT 220V AC/ 30V DC, 3A 100 to 120V AC 1S/10S/1M/10M GT5Y-4SN1A100 3S/30S/3M/30M GT5Y-4SN3A100 6S/60S/6M/60M GT5Y-4SN6A100 200 to 240V AC 1S/10S/1M/10M GT5Y-4SN1A200 3S/30S/3M/30M GT5Y-4SN3A200 6S/60S/6M/60M GT5Y-4SN6A200 12V DC 1S/10S/1M/10M — 3S/30S/3M/30M GT5Y-4SN3D12 6S/60S/6M/60M — 24V DC 1S/10S/1M/10M GT5Y-4SN1D24 3S/30S/3M/30M GT5Y-4SN3D24 6S/60S/6M/60M GT5Y-4SN6D24 24V AC 1S/10S/1M/10M GT5Y-4SN1A24 3S/30S/3M/30M GT5Y-4SN3A24 6S/60S/6M/60M GT5Y-4SN6A24 Code Scale Time Range Indication Time Range 0 to 10 x 0.1 S 0.1 second to 1 second 10S x 1 S 0.2 second to 10 seconds 1M x 0.1 M 1.2 seconds to 1 minute 10M x 1 M 12 seconds to 10 minutes 0 to 3 x 1 S 0.1 second to 3 seconds 30S x 10 S 0.5 second to 30 seconds 3M x 1 M 3 seconds to 3 minutes 30M x 10 M 30 seconds to 30 minutes 0 to 6 x 1 S 0.1 second to 6 seconds 60S x 10 S 1 second to 60 seconds 6M x 1 M 6 seconds to 6 minutes 60M x 10 M 1 minute to 60 minutes Part Numbering List 1. For sockets and accessories, see page G-66.

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC G-65 GTimers GT5Y-2 GT5Y-4 DPDT 4PDT Internal Connections (bottom view) Operation Mode: ON-Delay Timing Diagram/Schematics/Electrical Life Curves POWER 9 12 14(-) (+) POWER 9 10 11 12 14(-) (+) OUT Item Power Delayed Indicator Terminal No. Operation 13-14(Power) 1-9, 2-10, 3-11, 4-12(NC) 5-9, 6-10, 7-11, 8-12(NO) POWER Set Time Contact For an explanation of timing modes, see page E-4. 5000 1000 500 100 Life (x 10,000 operations)

12345 Load Current (A)

Life (x 10,000 operations)

G-66 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC GTimers Part Numbers: DIN Rail/Surface Mount Sockets and Hold-Down Springs Part Numbers: Panel Mount Socket and Hold-Down Springs Part Numbers: PCB Mount Sockets with Applicable Hold-Down Springs DIN Rail Mount Socket Applicable Hold-Down Springs Style Appearance Part No. Appearance Part No. 14-Blade Screw Terminal SY4S-05 SFA-202 14-Blade Screw Terminal (fingersafe) SY4S-05C DIN Mounting Rail Length 1000mm BNDN1000 Panel Mount Socket Applicable Hold-Down Springs Style Appearance Part No. Appearance Part No. 14-Blade Solder Terminal SY4S-51 SFA-302 PCB Mount Socket Applicable Hold-Down Springs Style Appearance Part No. Appearance Part No.

14 Blade, PCB Terminal SY4S-61 SFA-302

14 Blade, PCB Terminal SY4S-62 SY4S-02F1

DIN Rail Mounting Accessories Panel Mounting Accessories PCB Mounting Accessories

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC G-67 GTimers GT5Y Timer, Blade with SY4S-05 When using DIN Rail Hold- down Spring DIN Rail 27.5 21 6 52.6 6.4 58.6 623 18.5 83.6 maximum When using BAA/BAP: 87.6 maximum M3 Screw 5.9max. ø3.2min. (TOP VIEW) 12 11 10 5678 4 3 2 18.5 4max. 4.8min. 4.2 623 0.7 2-ø4.2 Mounting Hole (M4 screw hole) Terminal Arrangement 28.5 whenusing BAA DIN Rail (BAA) Dimensions

General Instructions Timers G-68 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC GTimers Timing accuracies are calculated from the following formulas: Repeat Error Voltage Error Tv: Average of measured values at voltage V Tr: Average of measured values at the rated voltage Temperature Error Tt: Average of measured values at °C T20: Average of measured values at 20°C Setting Error General Instructions for All Timer Series Load Current With inductive, capacitive, and incandescent lamp loads, inrush current more than 10 times the rated current may cause welded contacts and other undes- ired effects. The inrush current and steady-state current must be taken into consideration when specifying a timer. Contact Protection Switching an inductive load generates a counter-electromotive force (back EMF) in the coil. The back EMF will cause arcing, which may shorten the con- tact life and cause imperfect contact. Application of a protection circuit is recommended to safeguard the contacts. Temperature and Humidity Use the timer within the operating temperature and operating humidity ranges and prevent freezing or condensation. After the timer has been stored below its operating temperature, leave the timer at room temperature for a sufficient period of time to allow it to return to operating temperatures before use. Environment Avoid contact between the timer and sulfurous or ammonia gases, organic solvents (alcohol, benzine, thinner, etc.), strong alkaline substances, or strong acids. Do not use the timer in an environment where such substances are prevalent. Do not allow water to run or splash on the timer. Vibration and Shock Excessive vibration or shocks can cause the output contacts to bounce, the timer should be used only within the operating extremes for vibration and shock resis- tance. In applications with significant vibration or shock, use of hold down springs or clips is recommended to secure a timer to its socket. Time Setting The time range is calibrated at its maximum time scale; so it is desirable to use the timer at a setting as close to its maximum time scale as possible. For a more accurate time delay, adjust the control knob by measuring the operat- ing time with a watch before application. Input Contacts Use mechanical contact switch or relay to supply power to the timer. When driving the timer with a solid-state output device (such as a two-wire proxim- ity switch, photoelectric switch, or solid-state relay), malfunction may be caused by leakage current from the solid-state device. Since AC types com- prise a capacitive load, the SSR dielectric strength should be two or more times the power voltage when switching the timer power using an SSR. Generally, it is desirable to use mechanical contacts whenever possible to apply power to a timer or its signal inputs. When using solid state devices, be cautious of inrushes and back-EMF that may exceed the ratings on such devices. Some timers are specially designed so that signal inputs switch at a lower voltage than is used to power the timer (models designated as “B" type). T iming Accuracy Formulas = ± 1 x Maximum Measured Value – Minimum Measured Value x 100% Maximum Scale Value2 = ± Tv - Tr x 100% Tr = ± Tt - T20 x 100% T20 = ± Average of Measured Values - Set Value x 100% Maximum Scale Value