FL1C-H12RCE IDEC | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 14
Technical content
H IDEC SmartRelay www.idec.com/smartrelay for more information on this product family visit www.idec.com/smartrelay Additional Web Resources
- New and updated product information
- Downloadable software demos & upgrades
- Part configuration tool & cross reference
- Online stock check & ordering
- IDEC field sales & distributor search
- Online literature request
- Downloadable manuals & CAD drawings
- Manufacturer’s suggested retail price list
- Product training schedule & locations
- Advertising & trade show schedules
- Press releases & FAQs
Features
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC H IDEC SmartRelay Other Characteristics Digital/Analog Inputs (6 Digital plus 2 Digital or Analog) Multiple inputs provide direct communication with pushbuttons, sensors, switches, etc. (2kHz max. on I5 and I6). (Common use I/O for digital and analog: I7 and I8 on FL1C-H12RCE, FL1C-B12RCE, FL1C-H12SND.) Expandable up to 24 digital inputs. LCD Display Panel Display up to 48 characters as a text message. Monitor any of the 8 basic or 26 special function blocks, or confirm the status of the program for troubleshooting. Multifunction Interface A multifunction interface makes it easy to insert and remove the memory cartridge that controls the circuit program. It also supports the PC interface cable for upload- ing and downloading data from WindLGC. Operational Control Buttons Easy programming interface uses only six buttons. No tools necessary. Cursor keys can also be configured as inputs. Other Key Features
- Password protection
- Daylight savings time
- UL/c-UL listed, IEC61131/VDE0631, EMC Compliant, C-tick listed
- FM approved for Class 1, Div 2 Class 1, Zone 2 hazardous locations. Digital Outputs Use the outputs to control lights, small-sized motors and solenoid valves up to 10A. Expandable up to 16 digital outputs. Text Display It can display messages with background lighting up to 48 characters long from a selection of 97 character types. Operational Buttons Use the selection buttons for easy confirmation or modifi- cation of the circuit being displayed. The cursor keys can be configured as inputs. Memory Cartridge FL1C-PM3 is a memory cartridge with know-how protection. Not only is it possible to save your program, but also to protect it from unintended modification, copying or deletion. Not required for operation. Expansion Modules Optional expansion I/O mod- ules allow you to add digital input, output and LONWORKS® / AS-Interface communication modules as well as analog inputs to your system. Just snap-on and go – no special software or cables required. IDEC SmartRelay IDEC SmartRelay –the smart and expandable solution Get smart with the fully programmable IDEC SmartRelay, a compact, expandable CPU that can replace multiple timers, relays and counters. Each CPU houses a real-time clock and calendar, and supports optional expansion I/O modules to enhance your control and monitoring applications. Program and edit using either the "smart" on- board selection buttons and display interface, or our even "smarter" software, WindLGC. The IDEC SmartRelay is the ideal solution for managing automatic lighting, access control, watering sys- tems, pump control, or ventilation systems in fac- tory or home automation. HIghlights of the FL1C series
- 32-bit processor
- 130 connectable blocks
- 4 new function blocks
- 4 x12 backlight display
- Timer and counter frequency up to 2KHz
- Online monitor
- Ladder programming
- Invert of inputs saves NOT function blocks
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC H-3 H IDEC SmartRelay Base Module Part Number Expansion Module Part Number Starter Kit Part Number Accessories Part Number Rated Voltage Input Signal Input Type Output Signal With Display With Clock Input/Output FL1C-H12RCE 12/24V DC DC I7and I8 are used for digital/analog PNP Relay Output Yes Yes FL1C-B12RCE — FL1C-H12SND 24V DC Transistor Source Output Yes — FL1C-H12RCA 24V AC/DC AC/DC PNP/NPN Relay Output Yes Yes FL1C-B12RCA — FL1C-H12RCC 100-240V AC/DC PNP Yes FL1C-B12RCC — Part No. Module Power Voltage Input Output Total I/O FL1B-M08B2R2 Combination I/O Module 12/24V DC DC input Relay output 8 (4 in/4 out) FL1B-M08B1S2 24V DC DC input Transistor output 8 (4 in/4 out) FL1B-M08C2R2 100-240V AC/DC AC/DC input Relay output 8 (4 in/4 out) FL1B-M08D2R2 24V AC/DC AC/DC input Relay output 8 (4 in/4 out) FL1B-J2B2 Analog Input Module 12/24V DC Analog input – 2 (2 in/0 out) FL1B-CL1C12 L ON W ORKS® Communication Module* 24V AC/DC – – – FL1B-CAS2 AS-Interface Communication Module* 30V DC _ _ _ Part Number Description SMARTSTART-BAC-C FL1C-B12RCC, WindLGC software, and programming cable SMARTSTART-BDC-C FL1C-B12RCE, WindLGC software, programming cable, and simulator switch SMARTSTART-HAC-C FL1C-H12RCC, WindLGC software, and programming cable SMARTSTART-HDC-C FL1C-H12RCE, WindLGC software, programming cable, and simulator switch Part Number Description Note FL1C-PM3 Memory Cartridge Memory cartridge with know-how protection FL9Y-LP1CDW Programming Software: WindLGC Ver. 4 CD w/Online Manual FL1A-PC1 PC Interface Cable Connection of SmartRelay to PC BAA1000 BNDN1000 35MM DIN Rail Aluminum, 1m/3.28ft BNL6 Mounting Clips MT-101 Memory Cartridge Removal Tool FL1B-PSP1 Direct Mounting Slides FL1B-Y1371-SW8 8pt simulator switch used with 12, 24V DC base module only FL9Y-B827 FL1C user’s manual FC4A-USB USB/RS232 converter * For more information see Section M, Communications & Networking. Part Numbers
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC H IDEC SmartRelay General Function Blocks Special Function Blocks Function Blocks Edge detection with edge evaluation (pos. edge) Edge detection with edge evaluation (pos. edge) Parallel connection of normally closed contacts Parallel connection of normally open contacts Series connection of normally open contacts Series connection of normally closed contacts Double changeover contact Connection of closed contact AND AND (Edge) NAND NAND (Edge) OR NOR XOR NOT Q Q Q 123 45 67 89 1 0Cycle Q AND Q 123 45 67 89 1 0Cycle NAND Q Q Q Q Q On-delay QQ TrgTrg Par T Off-delay Q Q Trg R Par Trg R T Seven-day time switch Q Q No1 No2 No3 No1 No2 Sa Su 1212 20 20 12 20 8 20 8 22 SaɹSu Su ONɹ12ɿ00 OFF 20ɿ00 ONɹ 8ɿ00 OFF 22ɿ00 Latching relay RSS R Q Q S R Par Retentive on-delay QQ Trg R Par Trg R T T Up/down counter Q Q Cnt R Dir Par Cnt Dir Par R Interval time-delay relay/ Pulse output QQ Trg Par Trg T Twelve-month time switch No 02.25 No 04.15 Q Q No MM DD MM.DDt Fed. Mar. Apr. 25 25 Edge-triggered interval time-delay relay Q Trg Par R T Q Trg TStarts On-/Off-delay Q Q Trg Par Trg TH TL Current impulse relay Q Trg R RS S ParQ Trg R S Analog differential trigger Q Ax ParQ AX OFF=On+? on Q AX OFF=On+? Analog value monitoring Q En Ax Par Q AX En Aen+? Aen-? Aen Operating hours counter Q Q En R Ral Par En Ral Mi Mn OT R h Frequency trigger Fre G-T Q Q Fre Par fa=5Hz fa=3Hz 1s 1s Random generator Q Q En Par Trg T Starts TH TL Analog trigger 1000 SW SW 0A/1 or A/2 Q Q Ax Par Analog comparator 1000 A/1 0 1000 A/2 0 Q Q Ax Ay Par 1000 200 -200 A/1-A/2 0 tor ?=200 Stairwell light switch T Starts Q Q Trg Par Trg T 15s Message texts Par Q En P Asynchronous pulse generator EN Inv Q Q En Par Inv TH TL Softkey Q En Par Q Switch EN Dual-function switch Q Trg Par RQ TLTL TIL T Trg Analog amplifier Q Ax Par Shift register Q Trg In Dir Par Shift Up Shift Down S4=Q (Example) In Q Dir Trg
Specifications www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC H-5 H IDEC SmartRelay Base Module Specifications Item Specifications Compliant Standards General Specifications Dimensions (W x H x D) 72 x 90 x 55 mm — Weight Approx. 190g — Operating temperature Horizontal 0 to +55°C Cold: IEC60068-2-1 Hot: IEC60068-2-2Vertical 0 to +55°C Storage temperature -40 to +70°C — Relative humidity 10 to 85% IEC60068-2-30 Pressure 795 to 1080 hPa — Corrosion immunity Free from corrosive gases — Degree of protection IP20 Vibration resistance 5 to 9Hz (amplitude: 3.2mm) 9 to 150Hz (acceleration: 10m/s ) IEC60068-2-6 Shock resistance 150 m/s IEC60068-2-27 Dropping 50 mm (Drop height) IEC60068-2-31 Free fall (packaged) 1 m IEC60068-2-32 Emission Class B Group 1 EN55011EMC Emitted interference — EN50081-2, EN50082-2 Electrostatic discharge 8kV Air Discharge 6kV Contact Discharge IEC61000-4-2 Electromagnetic fields 10V/m IEC61000-4-3 Burst pulses 2KV (Supply and Signal Lines) IEC61000-4-4 Energy carriers single pulse (surge) 0.5kV(Power Lines): Symmetrical 1kV (Power Lines): Asymmetrical IEC61000-4-5 Communication cable 2 x 1.5 mm 1 x 0.5 to 2.5 mm Base Module Part Number FL1C-H12RCE FL1C-H12SND FL1C-H12RCA FL1C-H12RCC FL1C-B12RCE – FL1C-B12RCA FL1C-B12RCC Base Module Operating Specifications Power Supply Rated voltage 12/24V DC 24V DC 24V AC/DC 100-240V AC/DC 20.4V-28.8V DC 85-265 AC 100-253 V DC Rated Frequency — — 47-63Hz 50/60Hz (47-63Hz) Input Current 30-140 mA (12V DC) 20-75 mA (24V DC) 30-55 mA (24V DC) 40-110 mA (24V AC) 20-75 mA (24V DC) 10-40 mA (100V AC) 10-25 mA (240V AC) 5-25mA (100V DC) 5-15mA (240V DC) Allowable Momentary Power Interruption 2 ms (12V DC) 5 ms (24V DC) —5 ms 10 ms (100V AC) 20 ms (240V AC) Power Consumption 0.3-1.7W (12V DC) 0.4 to1.8W (24V DC) 1.1-4.6W (100V AC) 2.4-6.0W (240V AC) 0.5-2.9W (100V DC) 1.2-3.6W (240V DC) Reverse Polarity Protection Yes Yes — — Clock Backup Duration 80h at 25°C — 80h at 25°C 80h at 25°C Clock Accuracy ±2s / day maximum — ±2s / day maximum ±2s / day maximum Specifications
Specifications IDEC SmartRelay H-6 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC H IDEC SmartRelay Base Module Part Number FL1C-H12RCE FL1C-H12SND FL1C-H12RCA FL1C-H12RCC FL1C-B12RCE – FL1C-B12RCA FL1C-B12RCC Base Module Operating Specifications (con’t) Input Input Signal DC DC AC/DC AC/DC Input Points 8 (I1-I8) 8 (I1-I8) 8 (I1 - I8) 8 (I1-I8) Analog Input Points 2 (I7, I8)* 2 (I7, I8)* — — Fast Inputs 2 (I5, I6) Max 2KHz 2 (I5, I6) Max 2 KHz — — Analog Input Voltage Range 0 to10V DC (maximum rated voltage: 28.8V DC) 0 to 10V DC (maximum rated voltage: 28.8V DC) —— Rated Input Voltage 12/24V DC 24V DC 24V AC/DC 100-240V AC/DC 0-28.8V DC 85-253V AC, 100-253 VDC Isolation Not Isolated Not Isolated Not Isolated Not Isolated Operating Range Turn OFF Voltage < 5V DC < 5V DC < 5V AC/DC < 40V AC, < 30 VDC Turn ON Voltage > 8V DC > 8V DC > 12V AC/DC > 79V AC, > 79VDC Turn OFF Current < 1.0 mA (I1-I6) < 0.05 mA (I7-I8) < 1.0 mA (I1-I6) < 0.05 mA (I7-I8) < 1.0 mA < 0.03 mA Turn ON Current > 1.5 mA (I1-I6) > 0.1 mA (I7-I8) > 1.5 mA (I1-I6) Turn ON Time 1.5ms (Typ.) (I1-14) <1.0ms (I5, I6) 300ms Typ. (I7, I8) 1.5ms (Typ.) (I1-14) <1.0ms (I5, I6) 300ms Typ. (I7, I8) 1.5 ms (Typ.) 50 ms (Typ.) Wire Length 100m 100m 100m 100m Output Output Signal Relay Output Transistor Source Out- put Relay Output Relay Output Output Type 4NO contacts 4 points 4NO contacts 4NO contacts Isolation Isolated Not Isolated Isolated Isolated Dielectric Strength (between power/ input terminal and output terminals) 2,500V AC/1 minute 500V DC/1 minute — 2,500V AC/1 minute 500V DC/1 minute 2,500V AC/1 minute 500V DC/1 minute Output Voltage — Ext. power supply 20.4-28.8V DC —— Maximum Load Current Resistive Load 10A at 12/24V AC/DC 10A at 100/120V AC 10A at 230/240V AC Inductive Load 2A at 12/24V AC/DC 3A at 100/120V AC 3A at 230/240V 0.3A Resistive Load 10A at 12/24V AC/DC 10A at 100/120V AC/DC 10A at 230/240V AC/DC Inductive Load 2A at 12/24V AC/DC 3A at 100/120V AC/DC 3A at 230/240V AC/DC Resistive Load 10A at 12/24V AC/DC 10A at 100/120V AC 10A at 230/240V AC Inductive Load 2A at 12/24V AC/DC 3A at 100/120V AC 3A at 230/240V AC Short Circuit Protection External fuse 16A maximum Internal current limiting circuit: 1A External fuse 16A maximum External fuse 16A maximum Minimum Switching Load 10 mA, 12V DC — 10 mA, 12V DC 10 mA, 12V DC Initial Contact Resistance 100 m Ω maximum (at 1A, 24V DC) — 100 m Ω maximum (at 1A, 24V DC) 100 m Ω maximum (at 1A, 24V DC) Mechanical Life 10,000,000 operations minimum (no load, 10Hz) — 10,000,000 operations min (no load, 10Hz) 10,000,000 operations minimum (no load, 10Hz) Electrical Life 100,000 operations mini- mum (rated load 10A, 1,800 operations/hour) 100,000 operations min (rated load 10A, 1,800 operations/hour) 100,000 operations mini- mum (rated load 10A, 1,800 operations/hour) Switching Rate Mechanical Load 10 Hz — 10 Hz 10 Hz Electrical Load — 10 Hz — — Resistive Load/Lamp Load 2 Hz 10 Hz 2 Hz 2 Hz Inductive Load 0.5 Hz 0.5 Hz 0.5 Hz 0.5 Hz Specifications con’t * Input terminals 17 and 18 are used for digital and analog inputs. ** When selecting frequency trigger function.
Specifications www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC H-7 H IDEC SmartRelay Expansion I/O Part Number Combination I/O Module Analog Input Module FL1B-M08B2R2 FL1B-M08B1S2 FL1B-M08D2R2 FL1B-M08C2R2 FL1B-J2B2 Operating Specifications - Expansion Module Power Supply Rated voltage 12/24V DC 24V DC 24V AC/DC 100-240V AC/DC 12/24V DC 20.4V-28.8V DC 85-265V AC 100-253V DC 10.8-15.6V DC 20.4-28.8V DC Rated Frequency — — 47-63Hz 50/60Hz (47-63Hz) — Input Current 30-140 mA (12V DC) 22-75 mA (24V DC) 30-45 mA (24V DC) 40-110 mA (24V AC) 20-75 mA (24V DC) 10-30 mA (100V AC) 10-20 mA (240V AC) 5-15mA (100V DC) 5-10mA (240V DC) 25-50mA Allowable Momentary Power Interruption 2 ms (12V DC) 5 ms (24V DC) —5 ms 10 ms (100V AC) 20 ms (240V AC) 5 ms Power Consumption 0.3-1.7W (12V DC) 0.4 to 1.8W (24V DC) 1.1-3.5W (100V AC) 2.4-4.8W (240V AC) 0.5-1.8W (100V DC) 1.2-2.4W (240V DC) 0.3-0.6W (12V DC) 0.6-1.2W (24V DC) Reverse Polarity Protection Yes Yes — — Yes Input Input Signal DC DC AC/DC AC/DC Analog Input Points 4 4 4 4 — Analog Input Points — — — — 2 Input Impedance — — — 76 k Ω (0-10V DC) 155-250 Ω (0-20mA DC) Analog Input Range — — — 0-10V DC (28.8V max) 0-20mA (40mA max) Digital Resolution — — — 10 bits (0-1000) Rated Input Voltage 12/24V DC 24V DC 24V AC/DC 100-240V AC/DC — Allowable Voltage Range 10.8-15.6V DC 0-28.8V DC 85-253V AC 100-253V DC — Isolation Not Isolated Not Isolated Not Isolated Isolated Not Isolated Operating Range Turn OFF Voltage < 5V DC < 5V DC < 5V AC/DC < 40V AC < 30V DC — Turn ON Voltage > 8V DC > 8V DC > 12V AC/DC > 79V AC > 79V DC — Turn OFF Current < 1.0 mA < 1.0 mA < 1.0 mA < 0.3 mA — Turn ON Current > 1.5 mA > 1.5 mA > 2.5 mA > 0.08 mA — Turn OFF Time 1.5ms 1.5 ms 15 ms (Typ.) 50 ms (Typ.) — Analog Value Conversion Interval —— — 50ms Wire Length 100m 100m 100m 100m 10m (twisted-pair shielded cable) Output Output Signal Relay Output Transistor Source Output Relay Output Relay Output — Output Type 4NO contacts 4 points 4NO contacts 4NO contacts — Isolation Isolated Not Isolated Isolated Isolated — Dielectric Strength (between power/ input termi- nal and output terminals) 2,500V AC/1 minute 500V DC/1 minute 2,500V AC/1 minute 500V DC/1 minute 2,500V AC/1 minute 500V DC/1 minute 2,500V AC/1 minute 500V DC/1 minute — Output Voltage — Ext. power supply 20.4-28.8V DC —— — Maximum Load Current Resistive Load 10A at 12/24V AC/DC 10A at 100/120V AC 10A at 230/240V AC Inductive Load 2A at 12/24V AC/DC 3A at 100/120V AC 3A at 230/240V 0.3A Resistive Load 5A at 12/24V AC/DC 5A at 100/120V AC/DC 5A at 230/240V AC/DC Inductive Load 2A at 12/24V AC/DC 3A at 100/120V AC/DC 3A at 230/240V AC/DC Resistive Load 10A at 12/24V AC/DC 10A at 100/120V AC 10A at 230/240V AC Inductive Load 2A at 12/24V AC/DC 3A at 100/120V AC 3A at 230/240V AC Short Circuit Protection External fuse required 16A max Internal current limiting resistor: 1A External fuse 16A maximum External fuse 16A maximum — Minimum Switching Load 10 mA, 12V DC — 10 mA, 12V DC 10 mA, 12V DC — Initial Contact Resistance 100 m Ω maximum (at 1A, 24V DC) — 100 m Ω maximum (at 1A, 24V DC) 100 m Ω maximum (at 1A, 24V DC) — Mechanical Life 10,000,000 operations (no load) — 10,000,000 operations min (no load, 10Hz) 10,000,000 operations (no load) — Electrical Life 100,000 operations (rated resistive load 1,800 operations/hr) 100,000 operations mini- mum (rated load 1,800 operations/hour) 100,000 operations (rated resistive load 1,800 operations/hr) Switching Rate Mechanical Load 10Hz — 10 Hz 10Hz — Electrical Load — 10Hz — — — Resistive Load/Lamp Load 2Hz 10Hz 2 Hz 2Hz — Inductive Load 0.5Hz 0.5Hz 0.5 Hz 0.5Hz — Specifications con’t
Specifications IDEC SmartRelay H-8 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC H IDEC SmartRelay Operating Specifications - L ON W ORKS Communication Module Operating Temperature 0 to 55°C (no freezing) Operating Humidity 10 to 85% RH (no condensation) Storage Temperature –40 to +70°C (no freezing) Storage Humidity 10 to 85% RH (no condensation) Rated Power Voltage 24V AC/DC Allowable Voltage Range 20.4 to 26.4V AC, 20.4 to 28.8V DC Current Draw 33 mA max. Dielectric Strength 500V DC, 1 minute (between power terminal and dead parts) Insulation Resistance 10 M Ω minimum (500V DC megger between power terminal and dead parts) EMC Electrostatic Discharge 8 kV air discharge 6 kV contact discharge Burst Pulses 2 kV (power terminal) Vibration Resistance 5 to 9 Hz, amplitude 3.5 mm 9 to 150 Hz, 9.8 m/s Shock Resistance 150 m/s Dimensions 35.5W 90H 58D mm Mounting Style DIN rail or panel surface Degree of Protection IP20 Terminal Style Screw-cage clamp terminal Weight 85g Communication System LON system Transceiver FTT-10A Topology Bus topology, free topology Transmission Rate 78 kbps Neuron Chip TMPN3120FE5M (Toshiba) CPU Clock Frequency 20 MHz Transmission Distance Bus topology: 1400m (only FTT-10A transceiver, using Level 4 AWG22 cable) Free topology: 500m total, 400m between nodes (when using Level 4 AWG22 cable) Network Variables Input Network Variable SNVT_obj_request: (Quantity 1) Request object mode SNVT_switch: (Quantity 14) Switch light, alarm, window contact, free inputs/outputs SNVT_occupancy: (Quantity 2) Occupancy SNVT_temp_p: (Quantity 1) Room temperature (°C) SNVT_lux: (Quantity 1) Brightness - lighting level (lux) SNVT_lev_percent: (Quantity 6) Position (%) Output Network Variable SNVT_obj_status: (Quantity 1) Output object status SNVT_switch: (Quantity 8) Switch light, alarm, window contact, free inputs/outputs SNVT_occupancy: (Quantity 2) Occupancy SNVT_tod_event: (Quantity 2) Scheduler program Just current state Configuration Property SCPTmaxSendTime: Send heartbeat (Q5 to Q16) Specifications con’t
Specifications www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC H-9 H IDEC SmartRelay Operating Specifications - AS-Interface Communication Module Operating Temperature 0 to 55°C Storage Temperature –40 to +70°C Relative Humidity 10 to 85% (no condensation) Rated As-interface Voltage 30 VDC (26.5VDC to 31.6VDC) Reverse Polarity Protection Yes Current Draw 70 mA max. EMC Electrostatic Discharge 8 kV air discharge (IEC61000-4-2) 4 kV contact discharge Electromagnetic filed Filed strength 10V/m (IEC61000-4-3) First Transient Burst Pulse 1kV (criteria A) (IEC61000-4-4) 1kV (criteria B) Radiated Emission Class A (EN55011) Vibration Resistance 5 to 9 Hz, amplitude 3.5 mm 9 to 150 Hz, 9.8 m/s Shock Resistance 147 m/s 11ms (X, Y, Z each direction 3 times) Slave type Standard slave Profile I/O code 7 I/D code F I/D2 code F Degree of Protection IP20 Terminal Style Screw terminal (tightening torque: max. 0.5Nm) Applicable wire 0.5 to 1.5mm Instruction on a 35mm mounting rail according to DIN EN50022/wall mounting Dimensions 36W 90H 58D mm Weight 75g IDEC SmartRelay System AS-Interface System Inputs: Output data bits: In D0 I n+1 I n+2 I n+3 Outputs: Input data bits: Q n Q n+1 Q 2 D2 Q n+3 “n” depends on the plug-in position of the expansion module relative to the IDEC SmartRelay CPU. It indicates the number of the input or output in the IDEC SmartRelay program code. Specifications con’t Logic Assignments
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC H IDEC SmartRelay Inputs (CPU) FL1C-H12RCE/-B12RCE/H12SND FL1C-H12RCC/-B12RCC FL1C-H12RCA/-B12RCA Connection Diagrams The inputs of these devices are non-isolated and therefore require the same reference potential (ground) as the power supply. With the FL1B-H12RCE/-B12RCE and FL1B-H12SND you can tap the analog signal between the supply voltage and ground L+ M I1 I2 I3 I4 I5 I6 I7 I8 Input 8xDC L N I1 I2 I3 I4 I5 I6 I7 I8 Input 8xAC/DC The inputs of these devices are arranged in 2 groups with 4 inputs each. Different phases are only possible between, but not within the blocks. do not permit the connection of different phases to one input group (I1-4 or I5-8) of an AC model or on the inputs of one digit al module. 24V DC PNP Sensor Sensor PNP+ PNP 24V DC Sensor Sensor NPN – NPN NPN FL1C-H12RCA FL1C-H12RCA
IDEC SmartRelay General Information www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC H-11 HIDEC SmartRelay Outputs Connecting the load to the FL1C-*12R**: Protection with automatic circuit beaker (max. 16A) if desired Connecting the load to a IDEC SmartRelay with transistor outputs (FL1C-H12SND): Analog Input Expansion Module FL1B-J2B2 Connection Diagrams con’t Current measurement Voltage measurement Grounding terminal for connecting ground and shielding of the analog measuring line Ground Cable shielding DIN rail
General Information IDEC SmartRelay H-12 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC HIDEC SmartRelay Base Module Expansion Module LONWORKS® /AS-Interface Communication Module Mounting Hole Layout Dimensions L1 N I1 I2 I3 I4 I5 I6 I7 I8 Q1 Q2 Q3 Q4 35mm 4mm 36mm 90mm 53mm Q1 Q2 L+ M 11 12 13 14 Q312 Q412 1 2 RUN/STOP 35.5 24VAC/DC RUN/STOP FL1B-CL1C12 Service ABL O N M 2-ø4 Mounting Holes 98mm 53mm 35.5mm 35.5mm CPU Module Expansion Module Expansion Module Expansion Module
IDEC SmartRelay General Information www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC H-13 HIDEC SmartRelay Maximum Setup
- High-speed/Optimal Communication Performance For optimal and high-speed communication performance between the IDEC SmartRelay and the various modules, we recommend you install the digital modules first, then the analog modules (see example above). Setup With Different Voltage Classes
- Rules Digital modules can only be connected to devices of the same voltage class.
- Overview: Connecting an expansion module to IDEC SmartRelay
- Overview: Connecting an additional expansion module to an expansion module I/O Configuration with LONWORKS® Communication Module Module Combination and Allocation Numbers 1. Maximum number of I/O points using LONWORKS® communication module 2. Using analog inputs on the base module 3. Using expansion I/O modules Base module, LONWORKS® communication module, Combination I/O module, Analog input module CPU Expansion Modules M08B2R2 M08B1S2 M08D2R2 M08C2R2 J2B2 AS-i/LON FL1C-H12RCE X X X – X X FL1C-H12SND X X X – X X FL1C-H12RCA X X X – X X FL1C-H12RCC – – – X X X FL1C-B12RCE X X X – X X FL1C-B12RCA X X X – X X FL1C-B12RCC – – – X X X Expansion Module Additional Expansion Modules M08B2R2 M08B1S2 M08D2R2 M08C2R2 J2B2 CAS2 CL1C12 FL1B-M08B2R2 X X X – X X X FL1B-M08B1S2 X X X – X X X FL1B-M08D2R2 X X X – X X X FL1B-M08C2R2 – – – X X X X FL1B-J2B2 X X X – X X X FL1B-CAS2 AS-Interface X X X–X– – FL1B-CL1C12 L FL1C-H12RCC FL1B-CL1C12 Digital Input:I 12345678 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Analog Input:AI 1 2 3 4 5 6 7 8 Digital Output:Q 1234 5 6 7 8 9 10 11 12 13 14 15 16 FL1C-H12RCE FL1B-CL1C12 Digital Input:I 1 2 3 4 5 678 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Analog Input:AI 1 2 3 4 5 6 7 8 Digital Output:Q 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 FL1C-H12RCE FL1B-M08B2R2 FL1B-CL1C12 Digital Input:I 1 2 3 4 5 678 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Analog Input:AI 1 2 3 4 5 6 7 8 Digital Output:Q 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 FL1B-J2B2 General Information
- Maximum Setup of IDEC SmartRelay With Analog Inputs FL1C-H12RCE/B12RCE/H12SND (CPU, 4 digital modules and 3 analog modules) AI1, AI2 CPU Q1,,,Q4 I9...I12 FL1B- M08B2R2 Q5...Q8 I13...I16 FL1B- M08B2R2 Q9...Q12 I17...I20 FL1B- M08B2R2 Q13...Q16 I21...I24 FL1B- M08B2R2 AI3, AI4 FL1B- J2B2 AI5, AI6 FL1B- J2B2 AI7, AI8 FL1B- J2B2
- M axim um Setup of IDEC SmartR elay Without A nalog Inputs FL1C-H12RCA/B12RCA/H12RCC/B12RCC (CPU, 4 digital modules and 4 analog modules) CPU Q1,,,Q4 I9...I12 FL1B-M08 Q5...Q8 I13...I16 FL1B-M08 Q9...Q12 I17...I20 FL1B-M08 Q13...Q16 I21...I24 FL1B-M08 AI1, AI2 J2B2 AI3, AI4 J2B2 AI5, AI6 J2B2 A17, A18 J2B2 1. The LON W ORKS ® communication module can be used with any base module and expansion I/ O module. 2. The L ON W ORKS ® communication module must be mounted at the right-most position of the row. 3. I/O numbers are automatically allocated start- ing with the base module.
Programming Software IDEC SmartRelay H-14 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC HIDEC SmartRelay WindLGC Programming Software Program Comparison Simulation Mode/Online Monitor Ladder Programming WindLGC is the exclusive programming software for the IDEC SmartRelay using Windows®. Edit, save, and print out your programs. WindLGC Ver. 4 Features:
- Ladder programming
- Online Monitor
- Program Comparison
- Time Simulation
- Simplified connection of the functions
- Programs can be saved in PDF or JPG format Just click the function blocks you need and link function blocks for easy wiring. Devise complicated circuits using the convenient func- tions of WindLGC. To configure IDEC SmartRelay FL1C series, you must upgrade to WindLGC version 4.0. WindLGC system requirements:
- OS: Windows95/98/ME/NT/2000/XP
- CPU recommendation: Pentium 266MHz or higher
- Memory: 64MB or more
- RAM recommendation: 128MB
- Hard disk space: 90MB or more for installing WindLGC software.
- Monitor Recommendation: Display more than 800 x 600 dots and 256 col- ors Free download service, if upgrading from WindLGC Version 3 to Version 4, available at www.idec.com/usa