FB4201B2 PF | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 3
Technical content
< 1-channel < Output Ex ia < Installation in suitable enclosures in Zone 1 < Module can be exchanged under voltage (hot swap) < Analog output module for 0/4 mA ... 20 mA < Simulation mode for service operations (forcing) < Line fault detection (LFD) < Permanently self-monitoring Function The device drives positioners, proportional valves, I/P converters, or local indicators. Open and short-circuit line faults are detected. The output is galvanically isolated from the bus and the power supply. Connection Zone 1 COM I Zone 0, 20 I P Technical Data Slots Occupied slots 1 Supply Connection backplane bus Rated voltage Ur 12 V DC , only in connection with the power supplies FB92** Power dissipation 0.8 W Power consumption 0.95 W Internal bus Connection backplane bus Interface manufacturer-specific bus to standard com unit Analog output Number of channels 1 Release date: 2021-11--
16 Date of
Release date: 2021-11-16 Date of issue: 2021-11-16 Filename: 239398_eng.pdf Germany: +49 621 776 2222 Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091
Field device Proportional Valve Field device [2] I/P converters Field device [3] on-site display Connection channel I: 2/3+, 4/5- Current 0 ... 20 mA short-circuit protected Line fault detection can be switched on/off for each channel via configuration tool , configurable via configuration tool Short-circuit No Open-circuit deviation of preset output value > 0.5 mA Load max. 750 Ω at 20 mA HART communication no HART secondary variable no Watchdog within 0.5 s the device goes in safe state, e.g. after loss of communication Transfer characteristics Deviation After calibration 0.1 % of the signal range at 20 °C (68 °F) Influence of ambient temperature 0.1 %/10 K of the signal range Refresh time 100 ms Indicators/settings LED indication Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1) red: line fault (lead breakage or short circuit) Coding optional mechanical coding via front socket Directive conformity Electromagnetic compatibility Directive 2014/30/EU EN 61326-1:2013 Conformity Electromagnetic compatibility NE 21:2007 Degree of protection IEC 60529:2000 Environmental test EN 60068-2-14:2009 Shock resistance EN 60068-2-27:2009 Vibration resistance EN 60068-2-6:2008 Damaging gas EN 60068-2-42:2003 Relative humidity EN 60068-2-78:2001 Ambient conditions Relative humidity 95 % non-condensing Shock resistance shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 Vibration resistance frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 Mechanical specifications Degree of protection IP20 (module) , a separate housing is required acc. to the system description Connection removable front connector with screw flange (accessory) Mass approx. 350 g Dimensions 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch) Data for application in connection with hazardous areas EU-type examination certificate BVS 12 ATEX E 015 X Output Isolator FB4201B2 Release date: 2021-11-16 Date of issue: 2021-11-16 Filename: 239398_eng.pdf Germany: +49 621 776 2222 Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091
Marking 1 II 2(1) G Ex d [ia Ga] IIC T4 Gb
1 II (1) D [Ex ia Da] IIIC
Voltage Uo 27.3 V Current Io 87 mA Power Po 575 mW (linear characteristic) Galvanic isolation Output/power supply, internal bus safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V Directive conformity Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 EN 60079-1:2014 EN 60079-11:2012 International approvals ATEX approval BVS 12 ATEX E 015 X General information System information The module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate. Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. Assembly Front view Socket for removable plug blue (accessory) Space for labelling Status LED red Power LED green Diagnostic LED red/white Output Isolator FB4201B2 Release date: 2021-11-16 Date of issue: 2021-11-16 Filename: 239398_eng.pdf Germany: +49 621 776 2222 Pepperl+Fuchs Group Refer to "General Notes Relating to Pepperl+Fuchs Product Information". USA: +1 330 486 0002 Singapore: +65 6779 9091