www.marathonsp.com EPBCD42 Power Distribution Block

200 Amps 600 Volts AC/DC

  • Line: (1) 3/0 - #14 AWG (70 mm2 - 2.5 mm2)
  • Load: (1) 3/0 - #14 AWG (70 mm2 - 2.5 mm2) Electrical Ratings
  • 200 Amps
  • 600V per UL 1953 & CSA 22.2 No.158, class B & C requirements
  • 1000 V AC/DC per IEC 60947-7-1 (CE)
  • Short circuit current ratings (SCCR): See SCCR section below for specifications.
  • CU9AL - 90°C connector terminal rating with copper wire only
  • Touch protection: IP-20 (IEC 60529)
  • Factory & Field Wiring Agency Compliance
  • UL Listed, Investigated to UL 1953, File QPQS.E309401
  • CSA - certifed to C22.2 No. 158, File No. LR19766 (wire classes B & C only)
  • CE compliant to IEC 60947-7-1 Material Information
  • Insulator base:
  • Thermoplastic
  • Flammability rating of insulator base UL94V0
  • Insulator base temperature rating: -40°C to 125°C (UL RTI)
  • Connector: copper, tin plated
  • Terminal set screws: steel, nickel plated
  • Connector mounting screws: steel, zinc plated
  • RoHS compliant

www.marathonsp.com PDS 0386 REV-I 12/19/17 Termination Specifications

1 For information on copper stranded wire classes please reference:

http://www.marathonsp.com/CatalogPDFs/Flexible-Stranded-Wire.pdf Line & Load Side Wire Size (CU Stranded) Torque Wires / Terminal Wire Class (UL) 1 3/0 20.3 N·m (180 lbf·in) 1 B, C 2/0 - 2 20.3 N·m (180 lbf·in) 1 B, C, G, H, I (DLO) 4 20.3 N·m (180 lbf·in) 1 B, C, G, H, I (DLO) 4 20.3 N·m (180 lbf·in) 1 - 2 B, C 6 - 8 20.3 N·m (180 lbf·in) 1 - 2 B, C, G, H, I (DLO) 10 - 14 5.6 N·m (50 lbf·in) 1 - 2 B, C, G, H, I (DLO)

  • Copper solid wire range: 10 - 14 AWG
  • Wire strip length: 7/8 in. (18mm)
  • IP-20 protection: 3/0 - 2
  • Terminal screw drive: 6 mm. hex
  • IP-20 Protection: 2 - #14 AWG Short Circuit Current Ratings (SCCR)
  • The suitable conductor ranges are limited to the table values only for achieving the SCCR in excess of the default rating of 10,000A.
  • Other conductor combinations within the “Terminal Specifications” noted are suitable for achieving a SCCR of 10,000A (the default rating of terminal blocks).
  • Enclosure size – Investigated with a minimum 16X12X6 enclosure. Use in smaller enclosures is subject to end use evaluation. SCCR With Fuses Wire Class Suitable Conductors Max Overcurrent Protection Fuse Required Amp Rating / Class SCCR RMS Sym. Amps 600V. MaxLine Load J T RK1 RK5 G CC B, C 3/0 - 8 3/0 - 8 225 225 200 60 60 30 100,000 G, H, I 2/0 - 8 2/0 - 8 300 300 200 100 60 30 100,000 (*) 3/0 - 14 3/0 - 14 None 10,000 * Any wire class evaluated (see terminal specification section)

www.marathonsp.com PDS 0386 REV-I 12/19/17 Wire Class Suitable Conductors Overcurrent Protection Circuit Required Voltage AC MaxLine Load Manufacturer Type Max Amperage SCCR RMS sym AMPs B, C 3/0 - 4 3/0 - 8 Square D JDL32650 250 18kA 480JGL36250 250 35kA JJL36250 250 65kA JJL36250 250 65kA SCCR With Circuit Breakers Installation & Accessories

  • Mounting (Panel or DIN):
  • For use with #10 fastener.
  • Mounting torque to be determined in end use application not to exceed 30 lbf·in (3.4 N·m).
  • Din-Rail mountable on 35 X 7.5, 2m long, slotted: MN35-2
  • End Brackets: MSK35
  • Marker cards:
  • White plastic inserts: EPB Marker Card
  • Allen wrenches (6mm):
  • S & K tools 45956
  • Snap-on tools FAML6E
  • MAC tools XDLS6MM
  • McMaster Carr 8367A24
  • Armstrong 38-711

www.marathonsp.com PDS 0386 REV-I 12/19/17 Drawing