135X601 MARATHON | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 3
Technical content
www.marathonsp.com POWER DISTRIBUTION BLOCK 135X601 Replace “X” with1, 2, 3 for number of poles Wire Range
- Line Side: (1) 600 kcmil - 2 AWG Copper or Aluminum, Code Wire
- Load Side: (24) #4-14AWG Copper, Code Wire Electrical Ratings:
- 420 A maximum
- 600V AC/DC (UL1059 User Groups; Class A, B, and C)
- Factory and Field Wiring
- CU9AL - 90°C connector terminal rating with copper and aluminim wire
- Compliant to UL 508A Feeder Circuit Requirements
- SCCR at 10,000 A (Default for terminal blocks) Agency Compliance
- cURus, UL Recognized, Investigate to US and Canadian Standards (UL 1059 and CSA 22.2)
- Files XCFR2.E62806 and XCFR8.E62806
- CE Compliant to IEC 60947-7-1 Material Information
- Insulator base: -Thermoplastic -Flammability rating of insulator base UL94V0 -Temperature rating: 257°F, 125°C
- Connector - plated aluminum
- Terminal screws - plated steel
- RoHS Compliant
www.marathonsp.com REV-C 11/25/19 Product Data Sheet Termination Specifications Line Side Wire Size (CU + AL Stranded) Torque Wires/ Terminal Wire Class (UL)1 600kcmil - 2AWG 56.5 N·m (500 lbf·in) 1 B, C
- Aluminum stranded wire range: 600kcmil - 2AWG
- Solid Copper wire range : 600kcmil - 2AWG
- Wire Strip Length: 1 1/2”
- Terminal Screw Drive: Aluminum, tin plated, 1/2” hex Load Side Wire Size (CU + AL Stranded) Torque Wires/ Terminal Wire Class (UL)1 #4 - #14 AWG 4.0 N.m (35 lbf-in) 1 B, C #4 - #14 AWG 4.0 N.m (35 lbf-in) 1 G, H, I, K
- Solid copper wire range: #4 - #14 AWG
- Wire strip length (load side): - Top Row: 15/32” (12mm) - Center Row: 29/32” (23mm) - Bottom Row: 29/32” (23mm)
- Terminal Screw Drive: Aluminum, Tin Plated, 1/8” hex
- For information on copper stranded wire classes please reference - http://www.marathonsp.com/CatalogPDFs/Flexible-Stranded-Wire.pdf
www.marathonsp.com REV-C 11/25/19 Product Data Sheet Installation & Accessories
- Mounting (Panel): - For use with 1/4” Fasteners (4-pole) -Mounting torque to be determined in end use application, not to exceed 30 in.lbs (3.4 N.)
- Safety Guidelines: - Use specified hardware (washers & nuts). - Accessory cover (optional) is not intended to provide insulation for electrical spacings. - Stack lugs in decreasing width order. Ensure contact is maintained throughout the connection.
- Covers - Catalog number CH1351 - One Cover per pole (Ex: 1353601 ) would need (3) CH1351’s - Covers are black polycarbonate Drawing