135X601 MARATHON | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 3

Technical content

www.marathonsp.com POWER DISTRIBUTION BLOCK 135X601 Replace “X” with1, 2, 3 for number of poles Wire Range

  • Line Side: (1) 600 kcmil - 2 AWG Copper or Aluminum, Code Wire
  • Load Side: (24) #4-14AWG Copper, Code Wire Electrical Ratings:
  • 420 A maximum
  • 600V AC/DC (UL1059 User Groups; Class A, B, and C)
  • Factory and Field Wiring
  • CU9AL - 90°C connector terminal rating with copper and aluminim wire
  • Compliant to UL 508A Feeder Circuit Requirements
  • SCCR at 10,000 A (Default for terminal blocks) Agency Compliance
  • cURus, UL Recognized, Investigate to US and Canadian Standards (UL 1059 and CSA 22.2)
  • Files XCFR2.E62806 and XCFR8.E62806
  • CE Compliant to IEC 60947-7-1 Material Information
  • Insulator base: -Thermoplastic -Flammability rating of insulator base UL94V0 -Temperature rating: 257°F, 125°C
  • Connector - plated aluminum
  • Terminal screws - plated steel
  • RoHS Compliant

www.marathonsp.com REV-C 11/25/19 Product Data Sheet Termination Specifications Line Side Wire Size (CU + AL Stranded) Torque Wires/ Terminal Wire Class (UL)1 600kcmil - 2AWG 56.5 N·m (500 lbf·in) 1 B, C

  • Aluminum stranded wire range: 600kcmil - 2AWG
  • Solid Copper wire range : 600kcmil - 2AWG
  • Wire Strip Length: 1 1/2”
  • Terminal Screw Drive: Aluminum, tin plated, 1/2” hex Load Side Wire Size (CU + AL Stranded) Torque Wires/ Terminal Wire Class (UL)1 #4 - #14 AWG 4.0 N.m (35 lbf-in) 1 B, C #4 - #14 AWG 4.0 N.m (35 lbf-in) 1 G, H, I, K
  • Solid copper wire range: #4 - #14 AWG
  • Wire strip length (load side): - Top Row: 15/32” (12mm) - Center Row: 29/32” (23mm) - Bottom Row: 29/32” (23mm)
  • Terminal Screw Drive: Aluminum, Tin Plated, 1/8” hex
  • For information on copper stranded wire classes please reference - http://www.marathonsp.com/CatalogPDFs/Flexible-Stranded-Wire.pdf

www.marathonsp.com REV-C 11/25/19 Product Data Sheet Installation & Accessories

  • Mounting (Panel): - For use with 1/4” Fasteners (4-pole) -Mounting torque to be determined in end use application, not to exceed 30 in.lbs (3.4 N.)
  • Safety Guidelines: - Use specified hardware (washers & nuts). - Accessory cover (optional) is not intended to provide insulation for electrical spacings. - Stack lugs in decreasing width order. Ensure contact is maintained throughout the connection.
  • Covers - Catalog number CH1351 - One Cover per pole (Ex: 1353601 ) would need (3) CH1351’s - Covers are black polycarbonate Drawing