ECS130 XPPOWER | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 9

Technical content

  • IT & Medical Safety Approvals
  • Industry Standard 2.0” x 4.0 x 1.25” Format
  • < 0.5W Standby Power
  • Convection & Forced Cooled Ratings
  • -40° C to +70° C Operation
  • Class I & Class II Installations
  • Low Earth Leakage Current
  • Class B Emissions
  • 3 Year Warranty The ECS130 Series has been designed to minimise the no load power consumption (<0.5 W) and maximise efficiency in order to facilitate equipment design to the latest environmental legislation. Approved for Class I and Class II applications, the ECS130 range of single output AC-DC, 130 W power supplies feature high power supplies meet EN55022 Level B emissions with low earth leakage currents of 100 μA at 115 VAC or 215 μA at 230 VAC. Making these switchers ideal for industrial, IT and medical applications. The ECS130 series has single output versions from 12 V to 48 VDC, adjustable by ±10%. They are dual-fused for compliance with IEC60601-1 and efficiency is 88% typical, so minimal excess heat is generated. The ECS130 require only 10 CFM of cooling to delivers a full 130 W of power up to +50 °C and operates at up to +70 °C with derating or equally can supply 100 W when convection cooled up to +50 °C with operation to +70 °C with derating. PO WERGREEN

xppow er.com Input C haracteristics C haracteristic M inim um Typical M axim um U nits N otes & C onditions Input Voltage - O perating 8 0 115/230 264 VAC See derating curve. See fig 1. Input Frequency 4 7 50/60 63 H z Pow er Factor >0.5 230 VAC , 100% load EN 61000-3-2 C lass A C om pliant. Input C urrent - N o Load 0.03 A Input C urrent - Full Load 1.9/1.1 A 115/230 VAC Inrush C urrent 4 0 A 230 VAC cold start 25 °C N o Load Input Pow er 0.5 W Earth Leakage C urrent 260 µA 264 VAC /60 H z (M ax.) Input Protection F3.15 A /250 V internal fuse in both lines O utput C haracteristics C haracteristic M inim um Typical M axim um U nits N otes & C onditions O utput Voltage - V1 12 4 8 VD C See M odels and R atings table Initial Set A ccuracy ±1 % 50% load, 115/230 VAC O utput Voltage Adjustm ent -V1 ±10 % Via potentiom eter. See m ech. details, M inim um Load 0A Start U p D elay 1s 115/230 VAC full load H old U p Tim e 18 m s D rift ±0.2 % A fter 20 m in w arm up Line R egulation ±0.5 % 90-264 VAC Load R egulation % 0-100% load T ransient R esponse - V1 4% R ecovery w ithin 1% in less than 500 µs for a 50-7 5% and 7 5-50% load step O ver/U ndershoot - V1 5% R ipple & N oise - V1 1 % pk-pk 20 M H z bandw idth, 12V M odels 1.5% m ax O vervoltage Protection - V1 115 14 0 % Vnom D C . O utput 1, recycle input to reset O verload Protection - V1 110 160 % I nom See fig. 2. T rip and R estart Short C ircuit Protection - V1 C ontinuous T em perature C oefficient 0.05 % /˚C O vertem perature Protection °C N ot fitted M odels and R atings 1. For covered versions, add suffix ‘-C ’ to m odel num ber or order part no. EC M 40/60 C O VER for standalone cover, see derating curve. The cover is not suitable for C lass II installations. ‘-C ’. O utput Pow er O utput Voltage O utput C urrent M odel N um ber (1 ) Forced C ooled (1 0 C FM ) C onvection-cooled 130 W 100 W 12.0 VD C 10.9 A EC S130U S12 †^ 130 W 100 W 15.0 VD C 8 .7 A EC S130U S15 †^ 130 W 100 W 18 .0 VD C 7 .3 A EC S130U S18 130 W 100 W 24 .0 VD C 5.4 A EC S130U S24 †^ 130 W 100 W 28 .0 VD C 4 .7 A EC S130U S28 †^ 130 W 100 W 4 8 .0 VD C 2.7 A EC S130U S4 8 †^

xppow er.com Input Voltage D erating C urve O utput O verload C haracteristic Figure 1 100 110 120 130 80 100 90 264 Input Voltage (VAC) Output Power (W) Forced-cooled >10 CFM Convection-cooled Convection-cooled with cover Output enters Trip & Restart Mode 01 236789 10 Output Current (A) Output Volts (V) Figure 2 1 2V M odels

xppow er.com Efficiency Versus Load G eneral Specifications C haracteristic M inim um Typical M axim um U nits N otes & C onditions Efficiency 8 8 % 230 VAC Full load (see fig.3-5 ) Isolation: Input to O utput Input to G round O utput to G round 4 000 VAC

1500 VAC

500 VD C

Sw itching Frequency 65 kH z Pow er D ensity 13 W /in 3 M ean Tim e B etw een Failure 7 15 kH rs M IL-H D B K -217 F , N otice 2 +25 °C G B W eight: O pen Fram e C overed U nit Figure 5 - 48V M odels Figure 3 - 1 2V M odels Figure 4 - 24V M odels 20% 25% 50% 75% 100% 115 V 230 V 0.00% 10.00% 20.00% 30.00% 40.00% 50.00% 60.00% 70.00% 80.00% 90.00% 100.00% Load % Efficiency (%) 0.00% 10.00% 20.00% 30.00% 40.00% 50.00% 60.00% 70.00% 80.00% 90.00% 100.00% 20% 25% 50% 75% 100% 115 V 230 V Load % Efficiency (%) 20% 25% 50% 75% 100% 115 V 230 V 0.00% 10.00% 20.00% 30.00% 40.00% 50.00% 60.00% 70.00% 80.00% 90.00% 100.00% Load % Efficiency (%)

xppow er.com Environm ental Therm al D erating C urve C haracteristic M inim um Typical M axim um U nits N otes & C onditions O perating T em perature -4 0 +7 0 °C See derating curve, fig. 6 Storage T em perature -4 0 +8 5 °C C ooling 10 C FM Forced C ooled >100 W H um idity 5 95 % R H N on-condensing O perating A ltitude 5000 m Shock ±3 x 30g shocks in each plane, total 18 shocks. 30g = 11m s (+/-0.5m sec), half sine. C onform s to EN 60068 -2-27 & EN 60068 -2-4 7 Vibration Single axis 10 - 500 H z at 2g sw eep and endurance at resonance in all 3 planes. C onform s to EN 60068 -2-6 Figure 6 Ambient Temperature (º C) Output Power (W) 100 110 120 130 -40 0-20 60 50 70 Forced-cooled >10 CFM Convection-cooled Convection-cooled with cover Some specification parame ters may not be met

xppow er.com Electrom agnetic C om patibility - Im m unity Phenom enon Standard Test Level C riteria N otes & C onditions Low Voltage PSU EM C EN 61204 -3 H igh severity level as below H arm onic C urrent EN 61000-3-2 C lass A ESD Im m unity EN 61000-4 -2 ±6 kV C ontact ±15 kV A ir D ischarge A R adiated EN 61000-4 -3 3A EFT EN 61000-4 -4 3A Surges EN 61000-4 -5 Installation class 3 A C onducted EN 61000-4 -6 3A D ips and Interruptions EN 55024 (100 VAC ) D ip >95% (0 VAC ), 8 .3m s B D ip 30% (7 0 VAC ), 4 16m s B D ip >95% (0 VAC ), 4 160m s B EN 55024 (24 0 VAC ) D ip >95% (0 VAC ), 10.0m s B D ip 30% (168 VAC ), 500m s B D ip >95% (0 VAC ), 5000m s B EN 60601-1-2 (100 VAC ) D ip >95% (0 VAC ), 10.0m s A D erate O utput Pow er to 100 W D ip 60% (4 0 VAC ), 100m s A D erate O utput Pow er to 12 W D ip 30% (7 0 VAC ), 500m s A D erate O utput Pow er to 100 W D ip >95% (0 VAC ), 5000m s B EN 60601-1-2 (24 0 VAC ) D ip >95% (0 VAC ), 10.0m s A D ip 60% (96 VAC ), 100m s A D ip 30% (168 VAC ), 500m s A D ip >95% (0 VAC ), 5000m s B Electrom agnetic C om patibility - Em issions Phenom enon Standard Test Level C riteria N otes & C onditions C onducted EN 55011/22 C lass B R adiated EN 55011/22 C lass A Voltage Fluctuations EN 61000-3-3 Safety Agency Approvals Safety Agency Safety Standard C ategory C B R eport IEC 60950-1:2005 Ed 2 Inform ation T echnology U L U L60950-1 (2007 ), C SA 22.2 N o.60950-1-07 Ed 2 Inform ation T echnology TU V EN 60950-1:2006 Inform ation T echnology C E LVD Safety Agency Safety Standard C ategory C B R eport IEC 60601-1 Ed 3 Including R isk M anagem ent M edical U L A N SI/A A M I ES60601-1:2005 & C SA C 22.2, N o.60601-1:08 M edical TU V EN 60601-1/A 12:2006 M edical Equipm ent Protection C lass Safety Standard N otes & C onditions C lass I & C lass II IEC 60950-1:2005 Ed 2 & IEC 60601-1 Ed 2 See safety agency conditions of acceptibility for details M eans of Protection C ategory Prim ary to Secondary 2 x M O PP (M eans of Patient Protection) IEC 60601-1 Ed 3 Prim ary to Earth 1 x M O PP (M eans of Patient Protection) Secondary to Earth 1 x M O PP (M eans of Patient Protection)

xppow er.com Xxxxxxxxxx M echanical D etails - EC C 1 00U Sxx N otes 1. A ll dim ensions in inches (m m ). 2. W eight: 0.38 6 lbs (17 5 g) M echanical D etails SMD COMPONENT HEIGHT 4X 0.156 (3.96) MOUNTING HOLES 0.312 (7.92) CLEARANCE TOP AND BOTTOM 3.750 (95.25) 4.00 (101.6) 0.15 (3.8) 0.125 (3.17) 0.20 (5.1) 0.20 (5.1) .25 FASTON GROUND TAB J1 1.75 (44.45) 0.12 (3.18) Voltage Adjust 1.28 (32.5) N L 2.00 +0.06/-0.00 (50.8 +1.5/-0.00) J1 m ates w ith M olex H ousing PN 09-50-1031, J2 m ates w ith M olex H ousing PN 09-50-104 1 and both w ith M olex Series 5194 C rim p T erm inals In put C onnector J1 M olex PN 09 -65-203 8 Pin 1 Line Pin 2 N eutral 0.25” Faston Earth O utput C onnector J2 M olex PN 09 -65-2048 Pin 1 +V1 Pin 2 +V1 Pin 3 RTN Pin 4 RTN

xppow er.com N otes 1. A ll dim ensions in inches (m m ). 2. W eight: 0.8 lbs (360 g) M echanical D etails - C overed (-C ) Input Connector Output Connector 0.25 (0.6) Ground Faston Terminal 4.49 (114.0) 2.52 (64.0) 1.54 (39.0) 2 x M3 x 0.5 THD 0.16 (4.0) Max Screw Penetration 0.807 (20.50) 4.055 (103.00) 0.22 (5.5) 0.79 (20.0) 4 x M3 x 0.5 THD 0.16 (4.0) Max Screw Penetration 4.055 (103.00) 0.984 (25.00) 0.22 (5.5)

xppow er.com Xxxxxxxxxx Therm al C onsiderations In order to ensure safe operation of the PSU in the end-use equipment, the temperature of the components listed in the table below must not be exceeded. Temperature should be monitored using K type thermocouples placed on the hottest part of the component (out of any direct air flow). See Mechanical Details for component locations. Tem perature M easurem ents (Am bient 50 ° C ) C om ponent M ax Tem perature ° C T1 C oil 120 ° C Q 1 B ody 120 ° C C 5 105 ° C C 4 105 ° C Service Life The estimated service life of the ECS130 Series is determined by the cooling arrangements and load conditions experienced in the end application. Due to the uncertain nature of the end application this estimated service life is based on the actual measured temperature of a key capacitor within the product when installed in the end application. The graph below expresses the estimated lifetime for a given component temperature and assumes continuous operation at this temperature. 5000 25000 45000 65000 85000 105000 125000 145000 165000 185000 105 95 85 75 65 C5 Temperature (°C) Lifetime (Hrs) Estim ated Service Life vs C om ponent Tem perature 20-Jan-1 7