  • Compact Size - High Power Density
  • Industrial & Medical Approvals
  • Low Leakage Current
  • Level B Conducted Emissions
  • EN61000-3-2, -3 Compliant
  • Convection-cooled
  • Class II Approved 40-60 W Models ECM Series Input Input Voltage • 90-264 VAC (120-370 VDC) Input Frequency • 47-63 Hz; 440 Hz Input Current • 40 W: 0.4 A max at 230 VAC 60 W: 0.6 A max at 230 VAC 100 W: 0.9 A max at 230 VAC Inrush Current • 40 A max at 230 VAC Earth Leakage Current • <125 µA at 115 VAC/60 Hz <210 µA at 230 VAC/50 Hz Input Protection • Internal 3.15 A fuse in line and neutral Output Output Voltage • See tables Output Voltage Trim • ±5% on 3.3 V & 5 V versions, ±10% on other single output models and V1 of multi-output models. See note 1 for ECM40/60 models Initial Set Accuracy • ±1.0% V1, ±5% V2, V3 & V4 Minimum Load • See tables Start Up Delay • 2 s max Start Up Rise Time • 50 ms Hold Up Time • 16/75 ms min at 115/230 VAC Line Regulation • ±0.5% Load Regulation • ±1% single output models; ±3% V1, ±5% V2 & V3 ECM40/60 multi-output models. ±1% V1 & V2, ±5% V3 & V4 ECM100 Cross Regulation • 2% on ECM40/60 only Over/Undershoot • None at turn on/off Transient Response • 4% max. deviation, recovery to within 1% in 500 µs for a 25% load change Ripple & Noise • 1% pk-pk, 20 MHz bandwidth Overvoltage Protection • 115-135% Vnom, recycle input to reset Overload Protection • 110-150% on primary power limit, auto recovery Short Circuit Protection • Trip and restart (Hiccup mode) Temperature • 0.05%/° C Coefficient xppower.com General Efficiency • 80-85% depending on model Isolation • 4000 VAC Input to Output

1500 VAC Input to Ground

500 VAC Output to Ground

Switching Frequency • 70 kHz typical Power Density • 60 W: 6.25 W/In 3 100 W: 7.40 W/In3 MTBF • 250 kHrs per MIL-HDBK-217F Environmental Operating Temperature • 0 °C to +70 °C. Refer to derating curves for specific operating limitations. Cooling • Convection & fan-cooled ratings (see derating curves) Operating Humidity • 95% RH, non-condensing Storage Temperature • -20 °C to +85 °C Operating Altitude • 3000 m Shock • 30 g pk, half sine, 6 axes Vibration • 2 g rms, 5 Hz to 500 kHz, 3 axes EMC & Safety Emissions • EN60601-1-2, EN61204-3, FCC 20780, EN55022 & EN55011, level B conducted Harmonic Currents • EN61000-3-2 Voltage Flicker • EN61000-3-3 ESD Immunity • EN61000-4-2, level 2 Perf Criteria A Radiated Immunity • EN61000-4-3, 10 V/m Perf Criteria A EFT/Burst • EN61000-4-4, level 3 Perf Criteria A Surge • EN61000-4-5, level 3 Perf Criteria A Conducted Immunity • EN61000-4-6, 10 V Perf Criteria A Dips & Interruptions • EN61000-4-11, 30% 10 ms, 60% 100 ms, 100% 5000 ms Perf Criteria A, B, B Safety Approvals • EN60950, UL60950, CSA 22.2 601.1, EN60601-1, UL60601-1, CCC pending, contact sales

3 RTN RTN

4 RTN RTN

5 NC -V3

6 NC +V2

  1. V2 will track a change in V1 by the same percentage change in voltage as V1 is trimmed. 2. To receive unit with cover fitted, add suffix ‘-C’ to model number. For Class I operation only. 3. A 120% peak load can be taken for up to 100 ms with a 25% duty cycle. Average load not to exceed 40 W. † Available from Farnell. See pages 204-206. ^ Available from Newark. See pages 207-208. Mechanical Details Notes 2. Cable harnessess with 300 mm wire available. For single output models, order part number ECM40/60S LOOM†. For multi-output models, order part number ECM40/60DT LOOM †. 3. Mating connector kit available. Order part number ECM40/60 CONKIT †. 4. Covers available. Order part number ECM40/60 COVER ^†. Cover dimensions are 4.49 x 2.52 x 1.52 (114 x 64 x 38.5) 4X ø0.156 (3.96) mounting holes ø0.312 (7.92) clearance top and bottom SMD component height V Adj. 1.20 (30.5) 0.14 (3.5) 4.00 (101.6) 2.00 (50.8) 1.75 (44.45) 3.75 (95.25) 1 J2 Input Connector J1 Pin 1 Line Pin 2 Neutral J1 mates with Molex housing 43061-0003 & Molex series 5194 crimp terminals J2 mates with Molex housing 43061-0006 & Molex series 5194 crimp terminals Weight: approx. 0.33 lb (150 g) Derating Curves 2010 30 40 50 60 70 80 0 % 50% 100%Output Power Ambient Temp (°C) 75% 25% 2010 30 40 50 60 70 80 0 % 50% 100%Output Power Ambient Temp (°C) 75% 25% Note: Derate by 10% if cover is fitted All ECM40 models convection-cooled All ECM40 models with 5 CFM Consult longform datasheet for installation information regarding optimum thermal ratings in convection-cooled applications. Max Power Output 1 Output 2 Output 3 Model Number(2)Voltage Current Min/Max(3) Voltage Current Min/Max Voltage Current Min/Max 40 W +5.0 V 0.0 A/8.0 A ECM40US05†^ +7.0 V 0.0 A/5.7 A ECM40US07 +9.0 V 0.0 A/4.4 A ECM40US09^ +12.0 V 0.0 A/3.5 A ECM40US12†^ +15.0 V 0.0 A/2.7 A ECM40US15†^ +18.0 V 0.0 A/2.2 A ECM40US18 +24.0 V 0.0 A/1.7 A ECM40US24†^ +33.0 V 0.0 A/1.2 A ECM40US33 +48.0 V 0.0 A/0.9 A ECM40US48†^

0 % 75%Output Power Ambient Temp (°C) 100% 25% 50% 2010 30 40 50 60 70 80 0 % 50% 100%Output Power Ambient Temp (°C) 75% 25% Note: Derate by 10% if cover is fitted All ECM60 models convection-cooled All ECM60 models with 5 CFM Output Connector J2 Pin Single Multi 1 +V1 +V1 2 +V1 +V1

  1. V2 will track a change in V1 by the same percentage change in voltage as V1 is trimmed. 2. To receive unit with cover fitted, add suffix ‘-C’ to model number. For Class I operation only. 3. A 120% peak load can be taken for up to 100 ms with a 25% duty cycle. Average load not to exceed 60 W. 4. 48 V DC input version of 12 V single output model available in OEM quantities (DCM6048S12). Contact sales for details. † Available from Farnell. See pages 204-206. ^ Available from Newark. See pages 207-208. 2. Cable harnesses with 300 mm wire available. For single output models, order part number ECM40/60S LOOM †. For multi-output models, order part number ECM40/60DT LOOM †. 3. Mating connector kit available. Order part number ECM40/60 CONKIT†. 4. Covers available. Order part number ECM40/60 COVER ^†. Cover dimensions 5. Selected single output models available in a 3” x 5” footprint for OEM quantities. Contact sales for details. 4X ø0.156 (3.96) mounting holes ø0.312 (7.92) clearance top and bottom SMD component height V Adj. 1.20 (30.5) 0.14 (3.5) 4.00 (101.6) 2.00 (50.8) 1.75 (44.45) 3.75 (95.25) 1 J2 Input Connector J1 Pin 1 Line Pin 2 Neutral J1 mates with Molex housing 43061-0003 & Molex series 5194 crimp terminals. Optional ground (0.25 faston) tab available, contact sales. J2 mates with Molex housing 43061-0006 & Molex series 5194 crimp terminals. Weight: approx. 0.33 lb (150 g) Derating Curves Notes Notes Consult longform datasheet for installation information regarding optimum thermal ratings in convection-cooled applications. Max Power Output 1 Output 2 Output 3 Model Number(2)Voltage Current Min/Max(3) Voltage Current Min/Max Voltage Current Min/Max 60 W +5.0 V 0.0 A/12.00 A ECM60US05†^ +7.0 V 0.0 A/8.60 A ECM60US07 +9.0 V 0.0 A/6.70 A ECM60US09^ +12.0 V 0.0 A/5.00 A ECM60US12†^ +15.0 V 0.0 A/4.00 A ECM60US15†^ +18.0 V 0.0 A/3.30 A ECM60US18 +20.0 V 0.0 A/3.00 A ECM60US20 +24.0 V 0.0 A/2.50 A ECM60US24†^ +33.0 V 0.0 A/1.80 A ECM60US33 +48.0 V 0.0 A/1.25 A ECM60US48†^ Mechanical Details

4X ø0.1 56 [3.96] mounting holes ø0.312 [7. 92] clearance top and bottom SMD component height 1.20 (30.5) 0.14 [3.5] 4.50 (114.3) 2.50 (63.5) 2.25 (57.15) 4.25 (107.95) V Adj. Weight: approx. 0.4 lb (180g) ECM100Models and Ratings Output Connector J2 Pin Single Multi 1 +V1 +V1 2 +V1 +V1 3 +V1 +V1 4 +V1 +V1

5 V1 RTN RTN

6 V1 RTN RTN

7 V1 RTN RTN

8 V1 RTN RTN

9 NOT USED +V2

10 NOT USED +V2

11 NOT USED ±V3

12 NOT USED -V4

  1. Cable harnessess with 300 mm wire available. For single output models, order part number ECM100S LOOM†. For multi-outputs, p/n ECM100DT LOOM†. 3. Mating connector kit available for single output models. Order part number ECM100S CONKIT†. 4. Covers available. Order part number ECM100 COVER †^. 5. Available in a 3” x 5” footprint for OEM quantities. Contact sales for details. Input Connector J1 Pin 1 Line Pin 2 Neutral J1 mates with Molex housing 43061-0003 and Molex series 5194 crimp terminals. Optional ground (0.25 faston) tab available. J2 mates with Molex housing 43061-0012 and Molex series 5194 crimp terminals. Derating Curves 2010 30 40 50 60 70 80 100 Output Power (W) Ambient Temp (°C) A D C A B C D B US24-48 US12-18US05US03 20 10 30 40 50 60 70 80 50% 100%Output Power Ambient Temp (°C) 75% 25% Note: 1. Derate by 10% if cover is fitted. 2. For multi output convection- cooled operation above +50 ºC derate linearly to 50% at +70 ºC. All ECM100 models with 5 CFM Notes Multi Output Models Single Output Models 1. To receive unit with cover fitted, add suffix ‘-C’ to model number. 2. Output 3 available with opposite polarity for OEM quantities. 3. ‘*’ denotes ECM100 models are class I only, contact sales for class II. 4. 48 VDC input version of 12 V single output model available in OEM quantities (DCM10048S12). † Available from Farnell. ^ Available from Newark. See pages 204-208. Consult longform datasheet for installation information regarding optimum thermal ratings in convection-cooled applications. Output Power Output 1 Output 2 Output 3 Output 4 Model Number(1,3) Convection Cooled Forced Air

5 CFM Voltage Current

Number(1,3)Minimum Maximum with 5 CFM Cooling +3.3 V 0.0 A 15.0 A 20.0 A ECM100US03*†^ +5.0 V 0.0 A 15.0 A 20.0 A ECM100US05*†^ +7.0 V 0.0 A 11.4 A 14.3 A ECM100US07* +9.0 V 0.0 A 8.8 A 11.1 A ECM100US09*† +12.0 V 0.0 A 7.5 A 8.3 A ECM100US12*†^ +15.0 V 0.0 A 6.0 A 6.6 A ECM100US15*†^ +18.0 V 0.0 A 5.0 A 5.5 A ECM100US18* +24.0 V 0.0 A 4.1 A 4.1 A ECM100US24*†^ +33.0 V 0.0 A 3.0 A 3.0 A ECM100US33* +48.0 V 0.0 A 2.1 A 2.1 A ECM100US48*†^ All ECM100 single output models convection-cooled