EC20-90 NOVARIS | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 1
Technical content
Novaris EC provides a means to electrically clamp different earthing systems during transient disturbances. Applications include computer rooms and in the bonding of cable sheaths to ground where direct bonding would introduce interference and “earth loops”. Electrical Specifications Active element Gas Discharge Tube (GDT) DC spark over voltage Uc 90V 230V 350V 600V Voltage tolerance ± 20% Discharge current 8/20µs Imax 20kA Voltage protection level @ 5kV (10/700µs) UP <640V <700V <850V <1200V Isolation resistance >1010W Capacitance <0.8pF Mechanical Specifications Operating temperature / humidity -40 to +70ºC / 5 to 95% non-condensing Connection type 6mm 2 flying leads Environmental IP 65 Weight 160g Dimensions Body diameter 20mm Body length 60mm Lead length 500mm each (Customizable on request) EC20-90 EC20-230 EC20-350 EC20-600 Standards Compliance AS/NZS 1768 IEEE C62.41 IEC 61643-11 IEC 62561-3 Product Series Uc Imax EC 20 - 90