DSE3110 DSE | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 2
Technical content
The DSE 3 110 can be utilised as a M anual or Auto Start M odule for single gen-set applications or engine only applications. The m odule has been designed to w ork w ith electronic and non-electronic engines, providing advanced engine m onitoring and protection features. The DSE 3 110 includes a back-lit icon LC D display w hich clearly show s the status of the engine at all tim es. The m odule m onitors engine speed, frequency, voltage and engine run hours and also displays the w arning and shutdow n status. The m odule includes fixed and flexible outputs as w ell as configurable inputs m aking this product ideal for a w ide variety of applications. The m odule can either be program m ed using the front panel or by using the DSE C onfiguration Suite PC softw are. The m odule is available in tw o variants: CAN – For use w ith electronic engines only.
- O ptional frequency (H z) sensing from m ain AC alternator for gen- set applications. M PU/ALT. – For use w ith non- electronic engines only (m agnetic pick-up/alternator sensing).
- O ptional frequency (H z) sensing from m ain AC alternator for gen- set applications.
- O ptional M agnetic Pickup speed sensing. dse 3110 M ANUAL & AUTO START CONTROL M ODULE dse Genset COM PREHENSIVE FEATURE LIST TO SUIT A W IDE VARIETY OF G EN-SET APPLICATIONS 1 1ph N D + W/L FUEL & CRANK OUTPUTS (Flexible w ith CAN) OTHER PC USB PORT CONFIGURABLE INPUTS DC OUTPUTS DC POW ER SUPPL Y 8- 35V ISSUE 4 VOL TS GENERATOR SENSING DC OUTPUT CHARGE AL TERNATOR ELECTRONIC ENGINES OR M AGNETIC PICK-UP DSE3110 DEUTZ ISUZU PERKINS CATERPILLAR M TU VOLVO CUM M INS SCANIA
FEATURES
ENVIRONM ENTAL TESTING STANDARDS ELECTRO-M AGNETIC COM PATIBILITY BS EN 61000-6-2 EM C G eneric Im m unity Standard for the Industrial Environm ent BS EN 61000-6-4 EM C G eneric Em ission Standard for the Industrial Environm ent ELECTRICAL SAFETY BS EN 609 5 0 Safety of Inform ation Technology Equipm ent, including Electrical Business Equipm ent TEM PERATURE BS EN 60068-2 -1 Ab/Ae C old Test -3 0 o C BS EN 60068-2 -2 Bb/Be Dry H eat + 70 o C VIBRATION BS EN 60068-2 -6 Ten sw eeps in each of three m ajor axes 5 H z to 8 H z @ + /-7.5 m m ,
8 H z to 5 00 H z @ 2 gn
Db Dam p H eat C yclic 2 0/5 5 o C @ 9 5 % RH 48 H ours BS EN 60068-2 -78 C ab Dam p H eat Static 40 o C @ 9 3 % RH 48 H ours SHOCK BS EN 60068-2 -2 7 Three shocks in each of three m ajor axes 15 gn in 11 m S DEGREES OF PROTECTION PROVIDED BY ENCLOSURES BS EN 605 2 9 IP65 - Front of m odule w hen installed into the control panel w ith the supplied sealing gasket.
DEEP SEA ELECTRONICS PLC UK H ighfield H ouse, H unm anby Industrial Estate, H unm anby YO 14 0PH TELEPHONE + 44 (0) 172 3 89 009 9 FACSIM ILE + 44 (0) 172 3 89 3 3 03 EM AIL sales@ deepseaplc.com W EBSITE w w w.deepseaplc.com DEEP SEA ELECTRONICS INC USA 3 2 3 0 W illiam s Avenue, Rockford, IL 61101-2 668 U SA TELEPHONE + 1 (815 ) 3 16 8706 FACSIM ILE + 1 (815 ) 3 16 8708 EM AIL sales@ deepseausa.com W EBSITE w w w.deepseausa.com 055-064/07/10 (4) KEY FEATURES
- Back-lit icon LC D display
- Front panel editing
- LED and LC D alarm indication
- Pow er Save m ode
- C AN and M agnetic Pick-up/Alt. versions available (specify on ordering)
- PC configurable
- 6 Digital inputs
- 4 O utputs (2 configurable on M agnetic Pick up/Alt., 4 configurable on C AN version)
- C onfigurable tim ers and alarm s
- Alternative configuration
- Rem ote Start input
- G enerator voltage display
- G enerator frequency display
- Battery voltage display
- Engine speed display
- H ours counter
- Engine pre-heat
- C om prehensive shutdow n or w arning on fault condition KEY BENEFITS
- Tam per-proof hours counter provides accurate inform ation for m onitoring and m aintenance periods
- M ultiple engine param eters are m onitored sim ultaneously
- M odule can be configured to suit individual applications
- Suitable for engine only
applications
- C om patible w ith a w ide range of C AN engines
- U ses DSE C onfiguration Suite PC softw are for sim plified configuration
- IP65 rating (w ith optional gasket) offers increased resistance to w ater ingress
- Licence-free PC softw are RELATED M ATERIALS TITLE PART NO’S DSE3 110 Installation Instructions 05 3 -05 0 DSE3 110 Q uick Start G uide 05 7-104 DSE3 110 O perator M anual 05 7-086 DSE3 110 C onfiguration Suite PC Softw are M anual 05 7-087 SPECIFICATIO N DC SUPPLY CONTINUOUS VOLTAGE RATING
8 V to 3 5 V C ontinuous
Able to survive 0 V for 5 0 m S, providing supply w as at least 10 V before dropout and supply recovers to 5 V. This is achieved w ithout the need for internal batteries CHARGE FAIL/ EXCITATION 8 V to 3 5 V fixed pow er source 2 .5 W NOM INAL STANDBY CURRENT 2 3 m A at 12 V, 18 m A at 2 4 V M AXIM UM OPERATING CURRENT 3 5 m A at 12 V, 3 0 m A at 2 4 V O UTPUTS OUTPUT A (FUEL)
2 A DC at supply voltage
OUTPUT B (START) AUXILIARY OUTPUTS C,D
15 V - 3 3 3 V AC (L-N )
3 .5 H z to 75 H z M AGNETIC PICK UP VOL TAGE RANGE + /- 0.5 V to 70 V FREQUENCY RANGE 10,000 H z (m ax) DIM ENSIO NS OVERALL 9 8 m m x 79 m m x 40 m m PANEL CUT-OUT 80 m m x 68 m m 3 .1” x 2 .7” M AXIM UM PANEL THICKNESS 8 m m 0.3 ” dse 3110 M ANUAL & AUTO START CONTROL M ODULE dse Genset Registered in England & W ales N o.013 19 649 VAT N o.3 169 2 3 45 7 Deep Sea Electronics Plc m aintains a policy of continuous developm ent and reserves the right to change the details show n on this data sheet w ithout prior notice. The contents are intended for guidance only.