Features
l Choice of Sensing Element l Op tional 4-20mA Output Signal l High Accuracy l Fle xible Probe l T rue Average for Pt100 Sensor l Cus tom Built Versions Available l Compa tible with Most Major BEMS 73mm 7.3mm 7.9mm OD 6.35mm OD 2000/5000mm 96mm DS2530 P age 1 of 2 Product Data Sheet DS2530 Duct Averaging Sensor Temperature 100mm Sensing Length
- Choose a location where there is a good mixed air flow. Avoid areas where the sensor may be subject to hot or cold radiation effects. 2. Drill a clearance hole in the duct for the stem and fix the terminal box directly to the duct using mounting slots provided. These are on 61mm centres. Connect the wires in accordance with the relevant wiring diagram. WIRING DIAGRAM (1) RTD (Non Polarised) How to Order Notes 1. Please specify system type to ensure compatibility. 2. F or higher accuracy or custom-built assemblies, please r efer to Sales Office. 3. F or large users of these items, an own labelling ser vice is available. Please contact Sales Office f or full details. RED RED WHITE T WHITE Optional Connection NTP1024 LENGTH SENSOR OPTIONS In mm PTB = P t100 Class B X Other mA = 4-20mA Output DMF Duct Moun ting Flange LPD In-head Loop P owered Display N = No Options Example: NTP1024/22000/PTB/mA is a Pt100 Class B Sensor, 22 Metre Sensing Length, with 4-20mA Output. Recommended cable is 7/0.2m (0.22sq mm) screened cable to DEF Stan 61-12 (Part 5) DS2530 Page 2 of 2
2 Downgate Drive, Sheffield, S4 8BT, England
Tel: +44(0)114 244 2521 Fax: +44(0)114 243 4838 Every effort has been made during the preparation of this document to ensure the accuracy of statements and specifications. However, we do not accept liability for damage, injury, loss or expense caused by errors or omissions made. We reserve the right to withdraw or amend products or documentation without notice. 03JOCSW0715