365 Watts
- U Channel and Hotswap DC-DC Converter
- -48 VDC Input
- DC Input version of MFA350 AC-DC Converter
- -10 °C to + 70 °C Operation
- Power Fail and DC OK Signals
- High Power Density up to 11.1 W / in3
- 5 V Standby and 12 V Fan Supply Outputs DFA Series Input Input Voltage Range • 48 VDC nominal (36 - 75 VDC). Can be configured as -48 VDC input Input Current • 9.2 A typical, 12.5 A max Input Reverse Voltage• Continuous protection with Protection automatic recovery Undervoltage Lockout • 32 - 36VDC Protection Output Output Voltage • See table Output Voltage Trim • ±10% via potentiometer Minimum Load • No minimum load required. Line Regulation • ±0.5% of nominal with input variation of 36-75V DC Load Regulation • ±1% of nominal with load variation 0-100% Setpoint Accuracy • ±1% of nominal with 48 VDC input and 50% load Turn-on Time • 1 s typical from application of DC input Transient Response • <4% deviation with a 50-75-50% load change at 1 A/µs. Output returns to within 1% in less than 500 µs Ripple & Noise • 1% max pk-pk 20 MHz bandwidth, 0.1 µF capacitor connected across measurement points Overvoltage Protection• 115-140% of nominal, recycle input DC to reset Overcurrent Protection• 105-115% of max current Short Circuit Protection• Continuous protection, trip and restart (Hiccup mode) characteristic Temperature • 0.02%/°C (after 20 minute warm up) Coefficient xppower.com General Efficiency • 85% typical Isolation Voltage • 1500 VDC Input to Output,
1000 VDC Input to Ground,
500 VDC Output to Ground. Switching Frequency • 370 kHz typical Power Density • 11.1 W/In Environmental Operating Temperature• -10 °C to +50 °C with full load, derate linearly to 50% load at 70 °C forced cooled. Cooling • >20 CFM forced airflow required -H versions have integrated fan Operating Humidity • 0 to 95% RH non condensing. Storage Temperature • -40 °C to +80 °C. Storage Humidity • 0 to 95% RH non condensing. Operating Altitude • 3000m. Shock • ±3 shocks in each axis (total 18 shocks) 30 g 11ms (half sine). Vibration • 2 g, 10 - 500Hz 10 sweeps. EMC & Safety Emissions • Compliant with EN61204-3 2000, EN55022 class A conducted & radiated EFT/Burst • Compliant with EN61000-4-4 level 1 Perf Criteria A Surge • EN61000-4-5 level 1 Perf Criteria A, Conducted Immunity • Compliant with EN61000-4-6 level 2 Perf Criteria A Safety Approvals • UL60950-1 (2003), CE Marked to LVD
20 CFM Airflow
12 VDC 29.0 A 12 V/1 A 5 V/1 A 365 W DFA35048S12 24 VDC 14.5 A 12 V/1 A 5 V/1 A 365 W DFA35048S24 Mechanical Details (U Channel) 6.80 (172.7)
12 VOLT FAN CONNECTOR
V1 (+) V1 (- ) DC OUTPUT INTERFACE CONNECTOR LOGIC CONNECTOR VOLTAGE ADJUST
48 VDC
(PRIMARY INPUT) AIRFLOW 8 X M3-0.5 MOUNTING THREAD 0.236(6.0) MAX SCREW PENETRATION TYP ON ALL SIDES OF POWER SUPPLY AA AA A AA A 3.20 (81.3) 1.50 (38.1) 2 X 0.75 (19.1) 2 X 0.60 (15.2) 2 X 5.80 (147.3) 2 X 0.60 (15.2) 2 X 2.00 (50.8) 0.60 (15.2) 2 X 5.80 (147.3) Logic Connector Pin Function
1 DC IN OK
2 Inhibit / Enable
3 Not used
4 DC OK
5 Not used
8 Not used
Logic Connector: JST PN B10B-PHDSS(LF)(SN) Mating Plug: JST PN PHDR-10VS Contact, 26-22 AWG: JST PN SPHD-001T-P0.5
Models and Ratings DFA350-H Output Voltage Maximum Output Current Standby Supply Max Power Model Number 12.0 VDC 29.0 A 5 V/1 A 365 W DFA35048S12-H 24.0 VDC 14.5 A 5 V/1 A 365 W DFA35048S24-H OUTPUT CONNECTOR GUIDE PIN C/L 0.156 (3.96) EJECTOR PIN R0.225 (5.71) ROTATION RADIUS MAX CONNECTOR C/L 0.125 (3.18) 1.60 (40.6) 0.655 (16.65) 0.385 (9.78) 10.06 (255.52) 10.00 (254) 0.225 (5.72) 0.175 (4.45) 3.300 (83.82) 1.636 (41.54) INPUT & DC OUTPUT HEALTHY LED'S EJECTOR HANDLE INPUT CONNECTOR A B C D OUTPUT CONNECTOR PIN LOCATIONS MATING CONNECTOR FCI# 51762-10401200AA-LF + + - - PIN4 PIN1 INPUT CONNECTOR PIN LOCATIONS MATING CONNECTOR MOLEX# 39-01-2065 Ground Ground Pin Designator Pin Function A1 +Sense A2 Not used A3 DC OK B1 -Sense B2 Not used B3 DC IN OK C1 Not used C2 Not used C3 5 V Standby D1 Not used D2 Inhibit / Enable D3 5 V Standby Return P1 -V1 P2 -V1 P3 +V1 P4 +V1 Output Connector FCI# 51722-10401200AA-LF Mechanical Details (-H Hotswap)
DFA350Thermal Considerations (U Channel) In order to ensure safe operation of the PSU in the end-use equipment, the temperature of the components listed in the table below must not be exceeded. See drawing on 2nd page of this datasheet for component locations. The temperature should be monitored using K type thermocouples placed on the hottest part of the component (out of any direct air flow). See longform datasheet for further information of service life. AC OK Collector Pin 1 or B3 AC OK Emitter Pin 7 or B1 POWER SUPPLY Transistor On (<0.8 V): AC NOT OK Transistor Off (>4.5 V): AC OK J3 Logic Connector 330R
5 V Standby
Transistor On (<0.8 V): DC NOT OK Transistor Off (>4.5 V): DC OK J3 Logic Connector 330R or D2Jumper (JP1) fitted (standard) Open or TTL high=PSU On Short circuit or TTL Low=PSU Off Internal Vref JP1 See 2nd page of this datasheet Mechanical Details for location Jumper (JP1) removed Open or TTL high=PSU Off Short circuit or TTL Low=PSU On Signals DFA350 & DFA350-H Input Fail DC OK Remote On/Off (Inhibit/Enable) Temperature Measurements (Ambient≤50 ºC) Component Max Temperature ºC L1 90 ºC Q1 105 ºC HS1 85 ºC C25 75 ºC Q2 105 °C