CTH MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
MODEL: CTH CTH SPECIFICATIONS ES-1909 Rev.9 Page 1/4 https://www.m-system.co.jp/ Plug-in Signal Conditioners M-UNIT CT TRANSMITTER (inverter use) Functions & Features
- Converting an alternating current from a current transformer into a standard process signal
- Wide range of frequency can be accepted thanks to the incoporated wide-range CT
- Isolation up to 2000 V AC
- High-density mounting Typical Applications
- Monitoring load current of motors employing inverters
- Detecting failures of a pump or other device by monitoring abnormal load current of motors
- Monitoring current of electric welding machine (1.97) 127 (5) (3.15) mm (inch) MODEL: CTH–5[1]-[2][3]
ORDERING INFORMATION
- Code number: CTH-5[1]-[2][3] Specify a code from below for each of [1] through [3]. (e.g. CTH-5A-B/Q)
- Special output range (For codes Z & 0)
- Specify the specification for option code /Q (e.g. /C01/S01) INPUT Current 5: 0 – 5 A AC [1] OUTPUT Current A: 4 – 20 mA DC (Load resistance 750 Ω max.) B: 2 – 10 mA DC (Load resistance 1500 Ω max.) C: 1 – 5 mA DC (Load resistance 3000 Ω max.) D: 0 – 20 mA DC (Load resistance 750 Ω max.) E: 0 – 16 mA DC (Load resistance 900 Ω max.) F: 0 – 10 mA DC (Load resistance 1500 Ω max.) G: 0 – 1 mA DC (Load resistance 15 kΩ max.) Z: Specify current (See OUTPUT SPECIFICATIONS) Voltage 1: 0 – 10 mV DC (Load resistance 10 kΩ min.) 2: 0 – 100 mV DC (Load resistance 100 kΩ min.) 3: 0 – 1 V DC (Load resistance 100 Ω min.) 4: 0 – 10 V DC (Load resistance 1000 Ω min.) 5: 0 – 5 V DC (Load resistance 500 Ω min.) 6: 1 – 5 V DC (Load resistance 500 Ω min.) 4W: -10 – +10 V DC (Load resistance 2000 Ω min.) 5W: -5 – +5 V DC (Load resistance 1000 Ω min.) 0: Specify voltage (See OUTPUT SPECIFICATIONS) [2] POWER INPUT AC Power B: 100 V AC C: 110 V AC D: 115 V AC F: 120 V AC G: 200 V AC H: 220 V AC J: 240 V AC DC Power S: 12 V DC R: 24 V DC V: 48 V DC P: 110 V DC (CE marking unavailable) [3] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel GENERAL SPECIFICATIONS Construction: Plug-in Connection: M3.5 screw terminals Screw terminal: Chromated steel (standard) or stainless steel Housing material: Flame-resistant resin (black) Isolation: Input to output to power Input waveform: Up to 15 % of 3rd harmonic content Overrange output: 0 to 120 % at 1 – 5 V
MODEL: CTH CTH SPECIFICATIONS ES-1909 Rev.9 Page 2/4 https://www.m-system.co.jp/ Zero adjustment: -5 to +5 % (front) Span adjustment: 95 to 105 % (front) Input filter: Selectable with the front switch INPUT SPECIFICATIONS Frequency: 4 Hz – 200 kHz (-3 dB) or 4 Hz – 2 kHz (-3 dB) Input burden: 0.5 VA max. Overload capacity: 1000 % of rating for 3 sec., 200 % for 10 sec., 120 % continuous Operational range: 0 – 120 % of rating 104 100 1k 2k 10k 100k 200k (Hz) –10 (dB) Frequency Characteristics OUTPUT SPECIFICATIONS ■ DC Current: 0 – 20 mA DC Minimum span: 1 mA Offset: Max. 1.5 times span Load resistance: Output drive 15 V max. ■ DC Voltage: -10 – +12 V DC Minimum span: 5 mV Offset: Max. 1.5 times span Load resistance: Output drive 10 mA max.; 5 mA for negative voltage output; at ≥ 0.5 V INSTALLATION Power input
- AC: Operational voltage range: rating ±10 %, 50/60 ±2 Hz, approx. 2 VA
- DC: Operational voltage range: rating ±10 %, or 85 – 150 V for 110 V rating (ripple 10 % p-p max.) approx. 2 W (80 mA at 24 V) Operating temperature: -5 to +60°C (23 to 140°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Surface or DIN rail Weight: 300 g (0.66 lb) PERFORMANCE in percentage of span Accuracy: ±0.3 % at 20 Hz – 1 kHz ±7 % at 7 Hz – 100 kHz Temp. coefficient: Response time: Approx. 1.5 sec. (0 – 90 %) Ripple: 0.5 %p-p max.(The output ripple may increase when there is great difference between the frequencies of input signal and power supply) Line voltage effect: ±0.1 % over voltage range (input 5 - 100 %) Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @1 minute (input to output to power to ground) STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1 Installation Category II Pollution Degree 2 Input to output to power: Reinforced insulation (300 V) RoHS Directive
MODEL: CTH CTH SPECIFICATIONS ES-1909 Rev.9 Page 3/4 https://www.m-system.co.jp/ EXTERNAL VIEW Zero Adjustment Input Filter Selector (OFF) (ON)
4 Hz – 200 kHz
4 Hz – 2 kHz
EXTERNAL DIMENSIONS unit: mm [inch] 3456 2187 80 [3.15] 80 [3.15] [.79] 40 [1.57] 50 [1.97] 7.8 [.31] CLAMP (top & bottom) DIN RAIL 35mm wide2–4.5 [.18] dia. MTG HOLE 15 [.59] deep 8–M3.5 SCREW
- When mounting, no extra space is needed between units. TERMINAL ASSIGNMENTS unit: mm [inch] 2187 CT PROTECTOR (model: CTM) 20 (.79)
MODEL: CTH CTH SPECIFICATIONS ES-1909 Rev.9 Page 4/4 https://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM LOAD SOURCE k l CT L K CT PROTECTOR model: CTM Filter Base Socket R.M.S. Operation OUTPUT SZ Output Driver U(+) V(–) POWER WIDE RANGE TRANSFORMER INPUT FILTER SELECTOR Specifications are subject to change without notice.