Specifications are subject to change w ithout no tice C TD -9 S D S EN G 1 4 01 1 6 1

  • Bus-bar type split core current transform er
  • C lass 1 accuracy
  • C urrents from 4 00 A to 3200 A
  • U p to 10 Bus-bar isolated fixing screw s
  • D ouble screw term inals (up to 8-w ire connections)
  • Sealable term inal block covers
  • Sealable fixing split-core screw s Product De scrip tion M odel Prim ary current Secondary current O ption O rdering Key Split-core current transform er w ith bus- bar m ountng facility. Rated prim ary currents from 4 00 A to 32 00 A. Accessories AC Split-Core Current Transform er Type CTD-9S ( m ax 35x125 m m ) Type Selection Input Specifications O perating frequency 4 8 to 62 H z M ax. system voltage 0.72 kV Rated insulation level 3 kV/1 m in. @ 50 H z Insulation class E (m ax 75°C ) Short-tim e current rating Ith Typical 1 00 I n /1 s Idyn 2 .5 I th The short-tim e therm al current I th is anyw ay lim ited by the cable/bus-bar size Extended current rating refer to the R ange Table Security factor (FS) ≤ 5 (C lass: 1 and 3) CTD-9S 2000 5A XXX Prim ary current From 4 00A to 32 00A (R efer to the R ange Table) O ption XXX: none XTX: tropicalization (on request) Secondary current 1A (on request) R ated secondary current 5 A or 1 A O utput Specifications Standards According to EN61 869-2 Housing AB S, self-extinguishing: UL 94 V-0 M ounting B us-bar m ounting Standard accessories T w o term inal block screw s. T en cable/bus-bar fixing screw s. T en plastic caps for cable/bus-bar fixing screw s. T w o sealable term inal block covers. Special features 1 A secondary current, T ropicalization G eneral Specifications W orking tem perature -2 5°C to: refer to the R ange Table (-1 3°F to: refer to the R ange Table ) (R.H. < 90% non condensing @ 4 0°C ) Storage tem perature -30°C to +70°C (-2 2 °F to 1 58°F) (R.H. < 90% non condensing @ 4 0°C ) Approvals C E . cURus and C SA (4 00A to 2 000A) Connection Screw type C able cross section area From 1 .5 to 6 m m 2 M in/M ax screw s tightening torque relevant to term inal block screw s: From 1 to 2 Nm M ax screw s tightening torque relevant to the cable/bus-bar fixing screw s: 0,3 Nm Protection degree IP00 (w ithout sealable term inal covers) IP2 0 (w ith sealable term inal block covers + w ire term inals) Bus-bar size M ax. 35x1 2 5 m m W eight From 4 50 to 700 g

2 Specifications are subject to change w ithout no tice C TD -9 S D S EN G 1 4 01 1 6

M odel C TD -9S from 4 00A to 1200A Prim ary C urrent Tem perature Extended current rating Burden (VA) A C L 1 C L 3 4 00 (@ 60°C /1 4 0°F) 1 2 0% 3 500 (@ 60°C /1 4 0°F) 1 2 0% 2 4 600 (@ 60°C /1 4 0°F) 1 2 0% 4 6 700 (@ 60°C /1 4 0°F) 1 2 0% 4 8 750 (@ 60°C /1 4 0°F) 1 2 0% 4 8 800 (@ 60°C /1 4 0°F) 1 2 0% 4 8 1 000 (@ 60°C /1 4 0°F) 1 2 0% 6 1 0 1 2 00 (@ 50°C /1 2 2 °F) 1 2 0% 8 1 2 M odel C TD -9S from 1250A to 3200A Prim ary C urrent Tem perature Extended current rating Burden (VA) A C L 1 C L 3 1 2 50 (@ 50°C /1 2 2 °F) 1 2 0% 8 1 2 1 500 (@ 50°C /1 2 2 °F) 1 2 0% 1 0 1 5 1 600 (@ 50°C /1 2 2 °F) 1 2 0% 1 0 1 5 2 000 (@ 50°C /1 2 2 °F) 1 00% (+ ) 1 5 2 0 2 500 (@ 50°C /1 2 2 °F) 1 00% (*) 2 0 2 5 3000 (@ 4 0°C /1 04 °F) 1 00% (*) 2 5 30 32 00 (@ 4 0°C /1 04 °F) 1 00% (*) 2 5 30 Dim ensions (m m ) W iring Diagram S1 S2 L N P1 P2 Benefits 1 2 5 6 7 8

  • Easy w ay to open and close the C T core by the dedicate seleable screw s (see figure 1 ).
  • B ridging of current transform er output w ithout changing the connection of the secondary, so to avoid any output overvoltage during either the m aintenance or the installation procedure (see figure 2 ).
  • Easy output and earth connection (see fig. 3).
  • M ultiple screw s provided w ith isolation cap screw s to grant a strong and reliable fixing of the current transform er to the bus-bar (see figure 4 ).
  • Screw term inals com patible w ith any kind of w ire term inals and protection of screw term inals using specific sealable covers to assure alw ays the best safety (see figure 5- 6-7-8). (*) A m ax overload of 1 2 0% for 1 m in. every 30 m in. is allow ed. (+ ) A continuous overload of 1 2 0% of the range is allow ed @ am b. tem p. 4 0°C m ax.