MODEL: CSP CSP SPECIFICATIONS ES-4826 Rev.4 Page 1/4 http://www.m-system.co.jp/ Final Control Elements SERVO-TOP VALVE ACTUATOR TYPE C (linear type) Functions & Features

  • Actuator for a control valve
  • Lightweight, compact design
  • Simple field adjustments
  • Torque limiters
  • Electronic limiters for the full-open and -closed positions are easy to adjust.
  • ISO standard flange MODEL: CSP–[1]71-[2][3]

ORDERING INFORMATION

  • Code number: CSP-[1]71-[2][3] Specify a code from below for each [1] through [3]. (e.g. CSP-471-AK4) [1] MAXIMUM STROKE 4: 40 mm (1.57") 7: 75 mm (2.95") OPERATION TIME, MAXIMUM THRUST 7: 34 seconds / 20 mm, 12000 N OUTPUT STEM TYPE 1: M22 male screw, pitch 1.5 [2] INPUT Current A: 4 – 20 mA DC (Input resistance 250 Ω) Voltage 6: 1 – 5 V DC (Input resistance 1 MΩ min.) [3] POWER INPUT AC Power K4: 100 V AC, 50/60 Hz or 110 V AC, 60 Hz L4: 200 V AC, 50/60 Hz or 220 V AC, 60 Hz GENERAL SPECIFICATIONS Environmental protection: IP 56 Action: Direct or reverse; field selectable with DIP switches (factory set to “reverse”) (In “reverse” action with upright mount, the output stem goes up with an input signal increase.) Operation at abnormally low input: Extend, Retract or Stop; field selectable with DIP switches; default set to Stop. Detectable input drop level: 0.37 ±0.1 V DC; converted into voltage Wiring conduits: G 1 female thread (two) Material Body: Aluminum alloy Cover: Steel Terminal screws: Nickel-plated steel (torque 0.8 N·m) Paint color: Munsell N6 (handle: red) Drive: AC motor (15-minute rating) Startup current: 3.2A (power input code K4) 1.6A (power input code L4) Insulation class: B (thermal protector incorporated; 120 ±5°C) Power control element: Semiconductor switch Position detection: Potentiometer Deadband adjustment: 0.2 – 3.0 % (default set to approx. 1.5 %) Restart limiting timer adjustment: 0 – 30 sec. (default set to approx. 4 sec.) Isolation: Signals to power to sequential signals to metallic housing Zero adjustment: 0 – 25 % Span adjustment: 50 - 100 % Torque limiting mechanism: Incorporated Space heater: Incorporated Manual operation: Available INPUT SPECIFICATIONS ■ DC Current: Input resistor incorporated OUTPUT SPECIFICATIONS ■ Speed & Thrust (at rated power input voltage) Operation time (thrust 10000 N): 34 sec./20 mm (50 Hz), 29 sec./20 mm (60 Hz) Maximum thrust: 12000 N ■ Position Signal: 4 – 20 mA DC Load resistance: 300 Ω maximum (The output signal increases when the stem retracts.)

MODEL: CSP CSP SPECIFICATIONS ES-4826 Rev.4 Page 2/4 http://www.m-system.co.jp/ ■ Sequential Control Signal: "Full-open", "full-closed" and "Alarm" NPN open collector: 30 V DC @ 100 mA max. Saturation voltage: 1 V DC INSTALLATION Supply voltage Operational voltage range: Code K4: 100V AC ±10% at 50 Hz, 90 – 121V AC at 60 Hz Code L4: 200V AC ±10% at 50 Hz, 180 – 242V AC at 60 Hz Power consumtpion: Code K4: 200 VA at rated current Code L4: 240 VA at rated current Operating temperature: -10 to +60°C (14 to 140°F) Operating humidity: 30 to 85 %RH (non-condensing) Vibration: ≤ 19.6 m/s2 (2G) at 50 Hz Mounting position: Standing to horizontal Weight: 15 kg (33.1 lb) PERFORMANCE Hysteresis: 1 mm or less Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @ 1 minute (signal to power to sequential signals)

2000 V AC @ 1 minute

(sequential signals to metallic housing)

1500 V AC @ 1 minute

(power to metallic housing)

1000 V AC @ 1 minute

(signal to metallic housing) TERMINOLOGY

  • Torque Limiting Mechanism Torque switches are equipped to protect the motor from overload caused by foreign objects stuck in the valve. The switches can be activated within 2 to 98 % range to stop the motor and to output an alarm signal, with the RUN LED flashes in 0.5 sec. intervals.
  • Restart Limiting Timer A timer is incorporated to protect the motor and other incorporated components from overheating. The timer prevents the motor from restarting for a certain interval (0 to 30 sec. selectable) once the motor has been stopped within deadband.
  • Electronic Limiter This model is equipped with electronic limiters in order to prevent mechanical locks when the input goes below 0 % or above 100 %. Limiters are set at approx. -1.5 % for the full-closed side, approx. 101.5 % for the full-open side.

MODEL: CSP CSP SPECIFICATIONS ES-4826 Rev.4 Page 3/4 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS unit: mm (inch) 150 (5.91) 81 (3.19) (1.57) 10 (.39) 2x2–M8x16 2–G1 WIRING CONDUIT Handle knob position at use 130 (5.12) Space required to remove cover ø216 (8.50) (1.57) 79 (3.11) 196 (7.72) 336 (13.23) 140 (5.51) (1.18) 11 (.43) 2.5 (.10) (1.38) max. 121 (4.76) [max. 86 (3.39)] YOKE SURFACE M22, 1.5 pitch [ ] for CSP-4 (2.56) (2.56) ø70 –0.076 (2.753) –0.030 (2.755) 4–ø11 ø102 (4.02) ø125 (2.92) Yoke Mounting Requirements

MODEL: CSP CSP SPECIFICATIONS ES-4826 Rev.4 Page 4/4 http://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM CPU Current Output Driver RUN INP *Input shunt resistor incorporated for current input.

10 COM2

SIGNAL (retracted) FULL-OPEN/-CLOSED SIGNAL (extended) ALARM SEQUENTIAL CONTROL SIGNALS 21 3 4 MODE SELECTOR Position Input Circuit SZ U V AC MOTOR M TORQUE SW (extended) TORQUE SW (retracted) DEADBAND ADJ. SSR for Braking SSR SSR INPUT POSITION OUTPUT POWER min. max. Isolation Fuse Specifications are subject to change without notice.