CPM50FS05 XPPOWER | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

Industry Standard Footprint Wide Operating Temperature Parallel Operation Remote ON/OFF Adjustable Output Overvoltage & Overload Protection Input Input Voltage • 18-36 VDC 36-76 VDC 45-160 VDC 88-370 VDC 200-400 VDC (see tables) Output Output Voltage • See Tables Output Voltage • ±10% CPM50 & 100, Adjustment 60-110% CPM150 ,CPM200 & CPM400, 80-110% CPM600 Minimum Load • No minimum load required Start Up Delay • 200 ms max (100% load) Initial Set Accuracy • ±4.0% max Drift • ±0.5% max Line Regulation • ±0.5% max Load Regulation • ±0.9% max Ripple & Noise • 200 mV pk-pk (0°C to +85°C) Overload • Operates at >105% of rated current, Protection recovers automatically Overvoltage • Operates at between 115-140% of Protection rating recycle input to reset Remote Sense • Compensates for 300mV min if not required then sense connections must be made locally ie +S to +Vout and -S to -Vout Remote ON/OFF • Standard on all models General Efficiency • Up to 89% dependant on model Isolation • 3 kVAC Input to Output 2 kVAC Input to Baseplate

500 VDC Output to Baseplate

Switching Frequency • 500 kHz - CPM50 & 100 370 kHz - CPM150, CPM200, 400 & 600 Parallel Operation • Current share pin provided on all except 50 W models, derate max current by 10% per module Environmental Operating • -10 °C to +85°C CPM50 & CPM100, Temperature -20 °C to +85°C CPM150, CPM200, CPM400 & CPM600 (baseplate) Storage • -40 °C to +85 °C Temperature Relative Humidity • 20-95% non-condensing Shock • 20 G for 11 ms once each along X, Y & Z axis Vibration • 10-55 Hz 5 G for 3 min periods, over 60 mins along each X, Y & Z axis Safety Emissions • EN55022 Level A conducted EN55022 Level A radiated Contact sales for Application Note ESD Susceptibility • EN61000-4-2 Level 2 Radiated Susceptibility • EN61000-4-3 Level 3 EFT/Burst • EN61000-4-4 Level 3 Surge • EN61000-4-5 Level 3 Safety Approvals • UL1950, C-UL, EN60950, VDE0160 IEC950 50-700 Watts CPM Series Component Power DC-DC Modules Specification THE XP ERTS IN POWER www.xpplc.com sales@xpplc.com

  1. Measured with 220 µF capacitor at the output at 20 MHz bandwidth (0 °C to +85 °C). 2. Fixed (TRM pin open) ±10% adjustable by external VR. 3. 85-264 VAC with the CPH500 - See CPH Series. Notes Mechanical Details & Application Notes - 50 & 100 Watt Models www.xpplc.com sales@xpplc.com Pin Connection Function

1 DC IN + Positive Input Voltage

2 DC IN + 1 & 2 are internally connected

3 DC IN - Negative Input Voltage

4 RC Remote Control

5 TRM Ext. Adjustment of Output Voltage 6 +S + Remote Sensing Terminal

7 DC OUT + Positive Output Voltage

8 DC OUT + 7 & 8 are internally connected

9 DC OUT - Negative Output Voltage

10 DC OUT - 9 & 10 are internally connected

11 -S - Remote Sensing Terminal

12 CB Current Balance Terminals for

(CPM100) Parallel Operation NOTES: 1. All dimensions in mm tolerance ±0.3 mm. 2. Dimensions in brackets - CPM50. 3. Weight CPM50 = 120 g, CPM100 = 150 g CPM50 EXTERNALLY MOUNTED PARTS Output Value of externally Voltage mounted resistors ( Ω ) VR R1 R2

51 K 0 Ω 0Ω

12 1 K 820 0 Ω 24 1 K 2.4 K 0 Ω Remote Control The remote control circuit is controlled by using the RC and -ve DC IN terminals - example circuit shown opposite. 1. Between RC and -ve DC IN - terminals: “Low” level or short circuited (0-1.2 V) - Output: ON. 2. Between RC and -ve DC IN - terminals: “High” level or open circuited (2.4-5.5 V) - Output: OFF. 3. Output current from the RC terminal is 1 mA typical when the voltage at the RC terminal is at low level. Short-circuit the RC and -ve DC IN - terminal to disable remote control. CPM100 EXTERNALLY MOUNTED PARTS Output Value of externally Voltage mounted resistors ( Ω ) VR R1 R2 5 1 K 110 180 12 2 K 2.4 K 240 24 5 K 11 K 390 OUTPUT VOLTAGE ADJ. OUTPUT VOLTAGE & CURRENT RATINGS - 50 & 100 WATT MODELS CPM Output Input Output Output Regulation Ripple & Efficiency Model Power Voltage Voltage (2) Current Line Load Noise (1) Number 50 W 88-370 VDC (3) 5 V 10.0 A 20 mV 40 mV 150 mV 82% CPM50FS05 50 W 36-72 VDC 5 V 10.0 A 20 mV 40 mV 150 mV 80% CPM5048S05

50 W 88-370 VDC

(3) 12 V 4.2 A 48 mV 100 mV 200 mV 82% CPM50FS12 50 W 36-72 VDC 12 V 4.2 A 48 mV 100 mV 200 mV 82% CPM5048S12 (3) 24 V 2.1 A 96 mV 150 mV 200 mV 82% CPM50FS24 100 W 88-370 VDC (3) 5 V 20.0 A 20 mV 40 mV 150 mV 82% CPM100FS05 100 W 36-72 VDC 5 V 20.0 A 20 mV 40 mV 150 mV 80% CPM10048S05

100 W 88-370 VDC

(3) 12 V 8.5 A 48 mV 100 mV 200 mV 82% CPM100FS12 100 W 36-72 VDC 12 V 8.5 A 48 mV 100 mV 200 mV 82% CPM10048S12 (3) 24 V 4.2 A 96 mV 150 mV 200 mV 82% CPM100FS24

Output Input Output Output Regulation Ripple & Noise Efficiency (3) Model Power Voltage Voltage (2) Current Line Load Pk-Pk (1) Number 100 W 45-160 VDC 13.8 V 7.3 A 60 mV 150 mV 150 mV 83% CPM100C2S13 150 W 66-160 VDC 12.0 V 12.5 A 40 mV 150 mV 150 mV 87% CPM150C2S12 150 W 66-160 VDC 15.0 V 10.0 A 60 mV 150 mV 150 mV 86% CPM150C2S15 151 W 66-160 VDC 24.0 V 6.3 A 95 mV 190 mV 150 mV 87% CPM150C2S24

165 W 200-400 VDC

(4) 3.3 V 50.0 A 16 mV 30 mV 100 mV 79% CPM200C3S03 200 W 200-400 VDC (4) 5.0 V 40.0 A 20 mV 40 mV 100 mV 83% CPM200C3S05 210 W 200-400 VDC (4) 7.5 V 28.0 A 30 mV 60 mV 140 mV 86% CPM200C3S07 240 W 200-400 VDC (4) 12.0 V 20.0 A 40 mV 100 mV 150 mV 87% CPM200C3S12 200 W 36-76 VDC 2.0 V 100.0 A 10 mV 20 mV 100 mV 73% CPM40048S02 330 W 36-76 VDC 3.3 V 100.0 A 16 mV 30 mV 100 mV 80% CPM40048S03 400 W 36-76 VDC 5.0 V 80.0 A 20 mV 40 mV 100 mV 84% CPM40048S05 405 W 36-76 VDC 7.5 V 54.0 A 30 mV 60 mV 140 mV 87% CPM40048S07 500 W 36-76 VDC 12.5 V 40.0 A 40 mV 100 mV 150 mV 89% CPM40048S12 510 W 36-76 VDC 15.0 V 34.0 A 60 mV 150 mV 150 mV 89% CPM40048S15 504 W 36-76 VDC 24.0 V 21.0 A 95 mV 190 mV 150 mV 89% CPM40048S24 504 W 36-76 VDC 28.0 V 18.0 A 95 mV 190 mV 150 mV 89% CPM40048S28

264 W 200-400 VDC

(4) 3.3 V 80.0 A 16 mV 30 mV 100 mV 79% CPM400C3S03 400 W 200-400 VDC (4) 5.0 V 80.0 A 20 mV 40 mV 100 mV 83% CPM400C3S05 405 W 200-400 VDC (4) 7.5 V 54.0 A 30 mV 60 mV 140 mV 86% CPM400C3S07 408 W 200-400 VDC (4) 12.0 V 34.0 A 40 mV 100 mV 150 mV 87% CPM400C3S12 405 W 200-400 VDC (4) 15.0 V 27.0 A 60 mV 150 mV 150 mV 87% CPM400C3S15 396 W 200-400 VDC (4) 18.0 V 22.0 A 60 mV 150 mV 150 mV 89% CPM400C3S18 408 W 200-400 VDC (4) 24.0 V 17.0 A 95 mV 190 mV 150 mV 87% CPM400C3S24 406 W 200-400 VDC (4) 28.0 V 14.5 A 95 mV 190 mV 150 mV 88% CPM400C3S28 www.xpplc.com sales@xpplc.com Remote ON/OFF Remote ON/OFF circuits are built-in on both the input side (RC1) and output side (RC2 & RC3). The output can be controlled by either circuit. Input Side Remote ON/OFF (RC1) The ground pin of the input side Remote ON/OFF circuit is then ‘-V in’ pin. Between RC1 and -V in the output voltage is ON at ‘Low’ level (0 - 1.0 V). Between RC1 and -V in the output voltage is OFF at ‘High’ level (3.5 - 7.0 V). When Remote ON/OFF function is not used, short between RC1 and -V in. When the CPH Series (Power Factor & Harmonic Corrector Module) is used as a front end unit, connect between RC1-pin and PR-pin on CPH for the start-up timing of the CPM Series control. Output Side Remote ON/OFF (RC2 & RC3) 1. Measured at 20 MHz bandwidth & 0 °C to +85 °C. 2. Fixed (TRM pin open) adjustable by external VR or external resistor. 3. Measured at full load with 24 in 48 Vin & 280 Vin. 4. Compatible with CPH Series to provide 85-264 VAC input - See CPH Series. Notes RC2-RC3 Connection Example OUTPUT VOLTAGE & CURRENT RATINGS - 100, 150, 200 & 400 WATT MODELS CPM OUTPUT VOLTAGE & CURRENT RATINGS - 600 WATT MODELS CPM Output Input Output Output Regulation Ripple & Noise Efficiency (3) Model Power Voltage Voltage (2) Current Line Load Pk-Pk (1) Number 600 W 18-36 VDC 12.5 V 48 A 40 mV 100 mV 150 mV 83% CPM60024S12 616 W 18-36 VDC 28.0 V 22 A 95 mV 190 mV 150 mV 86% CPM60024S28 700 W 36-76 VDC 12.5 V 56 A 40 mV 100 mV 150 mV 89% CPM60048S12 700 W 36-76 VDC 28.0 V 25 A 95 mV 190 mV 150 mV 89% CPM60048S28 No Item RC2-RC3 1 Wiring method Fig.1 (a) Fig.1 (b) Fig.1 (c)

2 Function Power ON Power ON Power ON

3 Base pin RC2 -S -S and RC2

4 Power ON Open (0.1mA max) Short (0.5 V max)

5 Power OFF Short (3mA min) Open

(0.1mA max When output side remote ON/OFF function is used short between RC1 & -VIN. Do not connect RC2 and RC3 if remote ON/OFF is not used. Make sure that sink current of output side remote ON/OFF circuit is be <12 mA. Auxiliary power supply for remote ON/OFF (AUX) AUX is built in for operating the output side remote ON/OFF (RC2-RC3). If AUX is not used for RC2-RC3, AUX can be used for IOG or TMP signal output by opto coupler. Short protection resistance (2.2kΩ ) is built in. Output voltage decreases as the output current increases. (AUX voltage at open circuit: 16V) Specification of output side remote ON/OFF (RC2-RC3) Application Notes

www.xpplc.com sales@xpplc.com NOTES: 1. All dimensions in mm, tolerance ±0.3 mm. 2. Weight CPM100-200 = 150 g, CPM400 = 180 g NOTES: 1. All dimensions in mm, tolerance ±0.3 mm. 2. Weight 200g or less Mechanical Details - 100, 150, 200 & 400 Watt Models Mechanical Details - 600 Watt Model No. Connection Function 1, 2 +V IN + DC Input 3, 4 -V IN - DC Input

5 RC1 Remote ON/OFF (Input1)

6, 7, 8, 9 +V OUT + DC Output 10, 11, 12, 13 -V OUT - DC Output

14 CB Current Balance

15 VB Voltage Balance

16 TMP Thermal Detection Signal

17 RC3 Remote ON/OFF

18 RC2 Output Side

19 TRM Adjustment of Output Voltage

22 IOG Inverter Operation Monitor

23 AUX Auxiliary Power Supply

FG Mounting Hole (FG) No. Connection Function 1 +V IN + DC Input 2 -V IN - DC Input

3 RC1 Remote ON/OFF (Input1)

4, 5, 6, 7 +V OUT + DC Output 8, 9, 10, 11 -V OUT - DC Output

12 CB Current Balance

13 VB Voltage Balance

14 TMP Thermal Detection Signal

15 RC3 Remote ON/OFF

16 RC2 Output Side

17 TRM Adjustment of Output Voltage

20 IOG Inverter Operation Monitor

21 AUX Auxiliary Power Supply

FG Mounting Hole (FG) Rev 5.0