CLSD MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 3
Technical content
MODEL: CLSD CLSD SPECIFICATIONS ES-9299 Rev.4 Page 1/3 http://www.m-system.co.jp/ CLAMP-ON CURRENT SENSOR (1A output) Functions & Features
- Easy-to-install, spring-loaded, clamp-on type current sensor
- Over-voltage clamp element for safety in open circuit
- 1 A output MODEL: CLSD–[1]-[2]-1
ORDERING INFORMATION
- Code number: CLSD-[1]-[2]-1 Specify a code from below for each of [1] and [2]. (e.g. CLSD-A-15-1) Special specifications are possible. Consult factory. (Input: 100 to 2000 A, Output: 1 A or Input: 500 to 2000 A, Output: 5 A) [1] INTERNAL DIAMETER A: 24 (Select 15 or 20 for Input suffix code.) B: 36 (Select 30 or 40 for Input suffix code.) C: 60 ( Select 80 or 100 for Input suffix code.) D: 100 (Select 200 for Input suffix code.) [2] INPUT 15: 150 A 20: 200 A 30: 300 A 40: 400 A 80: 800 A 100: 1000 A 200: 2000 A OUTPUT Current 1: 1 A CAUTION Before you remove the sensor module or mount it, turn off the input signal for safety. While the line is alive, the module’s cores, attracted to each other, may be hard to separate.
RELATED PRODUCTS
AC current, watt, power factor transducers with 1 A input
- CT input module (model: R3-CT4)
- Multi power input module (model: R3-WT1)
- AC power input module (model: R3-WT4)
- AC current transducer (model: 14CE)
- AC current transducer (model: LTCE)
- CT transmitter (model: CT)
- CT transmitter (model: KCE)
- CT transmitter (model: M2CE)
- CT converter (model: M8CT)
- CT transmitter (model: M5CT)
- Multi power monitor (model: 53U, 54U, 54UC, 54UL) GENERAL SPECIFICATIONS Construction: Clamp Housing material: Flame-resistant resin (black) Applicable wire: Min. 0.75 mm2 Output clamp voltage: ±1.4 Vp-p INPUT SPECIFICATIONS Max. working voltage: 480 V AC (primary side) Overload capacity: 120 % continuous, 4000 % for 1 minute Operational range CLSD-A-15: ≤ 150 A CLSD-A-20: ≤ 200 A CLSD-B-30: ≤ 300 A CLSD-B-40: ≤ 400 A CLSD-C-80: ≤ 800 A CLSD-C-100: ≤ 1000 A CLSD-D-200: ≤ 2000 A INSTALLATION Operating temperature: -20 to +60°C (-4 to +140°F) Operating humidity: 85 % RH max. (non-condensing) Mounting: Fix with a binding strap. Weight CLSD-A: 230 g (0.51 lb) CLSD-B: 350 g (0.77 lb) CLSD-C: 500 g (1.1 lb) CLSD-D: 950 g (2.1 lb) PERFORMANCE Rated primary current / rated secondary current CLSD-A-15: 150 A / 1 A CLSD-A-20: 200 A / 1 A CLSD-B-30: 300 A / 1 A CLSD-B-40: 400 A / 1 A CLSD-C-80: 800 A / 1 A CLSD-C-100: 1000 A / 1 A
MODEL: CLSD CLSD SPECIFICATIONS ES-9299 Rev.4 Page 2/3 http://www.m-system.co.jp/ CLSD-D-200: 2000 A / 1 A Rated VA: 0.5 VA Frequency: 50 / 60 Hz Ratio error: ±1.0 %, 1.0 In / ±1.5 %, 0.2 In Phase displacement error: ±80', 1.0 In / ±120', 0.2 In Insulation resistance: ≥ 100 MΩ with 500 V DC (sensor core to output) Dielectric strength: 2000 V AC @ 1 minute (sensor core to output) EXTERNAL DIMENSIONS mm (inch) ■ CLSD-A 70 (2.76) 77 (3.03) approx. 300 (11.81) 41 (1.61) 24 (.94) dia. k l (black) (white) 7 (.28) VCTF 0.75 mm 2 – 2C K L ■ CLSD-B 90 (3.54) 97 (3.82) 51 (2.01) 36 (1.42) dia. k l approx. 300 (11.81) 7 (.28) VCTF 0.75 mm 2 – 2C K L (black) (white) ■ CLSD-C 115 (4.53) ) 1 8 . 1 1 ( 0 0 3 . x o r p p a) 6 7 . 4 ( 1 2 17 (.28) 63 (2.48) 60 (2.36) dia. VCTF 0.75 mm 2 – 2C k l K L (black) (white)
MODEL: CLSD CLSD SPECIFICATIONS ES-9299 Rev.4 Page 3/3 http://www.m-system.co.jp/ ■ CLSD-D 155 (6.10) 162 (6.38) 83 (3.27) 100 (3.94) dia. k l approx. 300 (11.81) 7 (.28) VCTF 0.75 mm 2 – 2C K L (black) (white) Specifications are subject to change without notice.