AQ0400IUXT SYNQOR | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 14

Technical content

Product # AQ0400IUxT Phone 1-888-567-9596 www.SynQor.com Doc.# 005-005053 Rev. C 08/24/15 Page 1 Technical Specification

400 W Triple Vout Series

  • High efficiency (91% for 48 VOUT Model at 400 W)
  • Universal input voltage range
  • Semi-regulated output for bus stability
  • Parallel operation supported
  • Integral fan cooling with speed control
  • Active PFC; EN61000-3-2 compliant
  • Low leakage; EN60601-1 compliant
  • Low noise; EN55011 / EN55022 Class B compliant
  • Over–current, over–voltage, & over–temp protection
  • DC Power Good / AC Power Good signals
  • Remote enable input
  • Fan status output / Fan enable input
  • Small size: 3" x 5" x 1.45"(open frame)
  • RoHS 6/6 compliant
  • 5 V (10 W) and 12 V (50 W) standby outputs Product Features Industrial Grade AC/DC Power Supply With PFC 85-264 Vrms 12/24/36/48 V 400 W 500 W Up to Up to 91 % Input Voltage Semi-Regulated Output Output Continuous Output Transient Full Load Efficiency Includes 5 V (10 W) and 12 V (50 W) “Always On” Standby Power Outputs Configurations
  • 400 W Encased or Open Frame
  • 800 W Encased Flat or Stacked
  • 1200 W Encased Flat or Stacked

1200 W Encased Stacked

400 W Encased

400 W Open Frame

800 W Encased Flat

Product # AQ0400IUxT Phone 1-888-567-9596 www.SynQor.com Doc.# 005-005053 Rev. C 08/24/15 Page 2 AC Input: 85-264 Vrms DC Output: 12/24/36/48 V Semi-reg. Power: 400 W Grade: Industrial GENERAL SPECIFICATIONS Fundamental ripple freq. Input Output 500 kHz 250 kHz Audible noise Fan speed varies with temp. 39 dBA @ 1 m max. Weight (EA \\ EC) (SC \\ RC) (UC \\ TC) 343 g (12.1 oz) \\ 446 g (15.7 oz) 846 g (29.8 oz) \\ 879 g (31 oz) 1224 g (43.2 oz) \\ 1298 g (45.8 oz) MTBF MIL-217 Demonstrated 343.6 kHours TBD kHours ISOLATION SPECIFICATIONS Isolation voltage Input to output Input to ground Output to ground

3000 Vrms

1500 Vrms

500 Vrms

Insulation resistance Output to ground 10 MΩ min. Leakage currents See Note 2 ENVIRONMENTAL CHARACTERISTICS Thermal performance Operating ambient (see Figure 2) Non-operating ambient -40 ºC to +70 ºC -40 ºC to +85 ºC Relative humidity Non-condensing 5-95% RH Altitude Operating Non-operating 10,000 ft max. 30,000 ft max. Random vibration 5-500 Hz 0.03 g2/Hz Shock Half-sine, 10 ms, 3 axes 20 g peak EMC CHARACTERISTICS Conducted emissions EN55011 and EN55022, FCC part15 Level B Line frequency harmonics EN61000-3-2 Class A Voltage fluctuations EN61000-3-3 Clause 5b ESD air EN61000-4-2 Level 3 ESD contact EN61000-4-2 Level 3 Radiated immunity EN61000-4-3 Level 3 Fast transients EN61000-4-4 Level 3 Line surge immunity EN61000-4-5 Level 3 Conducted immunity EN61000-4-6 Level 3 Power freq. mag. field EN61000-4-8 3 A/m Voltage dip immunity EN61000-4-11 Perf Criteria A, A, B <5% UT 10 ms, 70% UT 500 ms, 40% UT 100 ms NOTES: 1. Main output power rating always includes 5 V and 12 V standby outputs. 2. Leakage currents see page 5. ACuQor 400W Triple Vout Series Electrical Characteristics All specifications typical with TA = 25 °C, unless otherwise specified. Specifications subject to change without notice. MAIN OUTPUT SPECIFICATIONS Output power (continuous) (5 s transient) 85-132/170-264 Vrms 85-132/170-264 Vrms 132-170 Vrms

400 W (Note 1)

500 W (Note 1)

voltage (at 250W) (Semi-regulated)

12 Vout (model 1T)

24 Vout (model 2T)

36 Vout (model 3T)

48 Vout (model 4T)

12.4 V 25 V 37.5 V 50 V Efficiency (see figs. 1, 3, 5, 7) (see Note 1)

12 Vout, 115 Vrms, 400 W

48 Vout, 115 Vrms, 400 W

12 Vout, 230 Vrms, 400 W

48 Vout, 230 Vrms, 400 W

88% typ. 90% typ. 89% typ. 91% typ. Hold-up time (to -20%) (see Note 1)

12 Vout

16 ms @ 400 W 20 ms @ 400 W Maximum load capacitance 12 Vout

24 Vout

36 Vout

48 Vout

16,000 µF 8,000 µF 4,000 µF 2,000 µF Output ripple voltage Switching frequency (20 MHz BW) Twice line frequency (at 300W) 0.5% p-p 5.0% p-p Turn-on delay 2 s max. Transient response Iout steps from 50-75% At 0.2 A/µs 3% typ / 6% max. dev. 100 ms recovery Overvoltage protection Cyclic restart 110-120% Short circuit protection Cyclic operation 115% rated Iout Total regulation Over line, load and temperature ±6.0% 12V_STANDBY cross-reg. ΔVout caused by 50 W step 0.5% 5V_STANDBY cross-reg. ΔVout caused by 10 W step 0.1% Thermal protection Automatic recovery +125 ºC (PCB Temp) REMOTE_ENABLE Input Low Voltage Input High Voltage

0.45 V (max)

4.15 V (min)

12V_STANDBY OUTPUT SPECIFICATIONS Output power 85-264 Vrms 50 W Nominal DC output voltage Semi-regulated 12.4 V Total regulation Over line, load and temperature ±6.0% Main output cross-reg. Δ12V_STANDBY caused by Δ350W on main output 400 mV Output ripple Switching frequency (20 MHz BW) Twice line frequency 10 mV

0.45 Vrms

Output current Continuous 4.2 A Short circuit protection Cyclic operation 5.0 A Maximum load capacitance 2,000 uF 5V_STANDBY OUTPUT SPECIFICATIONS Output power 85-264 Vrms 10 W Nominal DC output voltage Fully regulated 5.0 V Total regulation Over line, load and temperature ±5.0% Output current Continuous 2.0 A Short circuit protection Cyclic operation 2.5 A Maximum load capacitance 1,000 uF INPUT SPECIFICATIONS AC input voltage Universal range 85-264 Vrms Input frequency 47-63 Hz Input current (see Note 1)

115 Vrms @ 400 W

230 Vrms @ 400 W

4 Arms

2 Arms

Power factor >0.98 Input surge current 264 Vrms (cold start) 40 A max. Internal input fuses Both AC lines 6.3 A Technical Specification

Product # AQ0400IUxT Phone 1-888-567-9596 www.SynQor.com Doc.# 005-005053 Rev. C 08/24/15 Page 3 AC Input: 85-264 Vrms DC Output: 12/24/36/48 V Semi-reg. Power: 400 W Grade: Industrial 100 0 100 200 300 400 500 Efficiency (%) Output Power (W)

115 Vrms

230 Vrms

Efficiency (%) Output Power (W) Efficiency (%) Output Power (W) 10.0 10.5 11.0 11.5 12.0 12.5 13.0 13.5 14.0 0 4 8 12 16 20 24 28 32 36 Output Voltage (V) Output Load (A) 0 2 4 6 8 10 12 14 16 18 Output Voltage (V) Output Load (A) 0 2 4 6 8 10 12 Output Voltage (V) Output Load (A) EFFICIENCY, DERATING, AND VOUT DROOP CURVES Technical Specification Figure 1: 12 VOUT efficiency curves. Figure 2: 12 VOUT droop characteristic. Figure 3: 24 VOUT efficiency curves. Figure 4: 24 VOUT droop characteristic. Figure 5: 36 VOUT efficiency curves. Figure 6: 36 VOUT droop characteristic.

Product # AQ0400IUxT Phone 1-888-567-9596 www.SynQor.com Doc.# 005-005053 Rev. C 08/24/15 Page 4 AC Input: 85-264 Vrms DC Output: 12/24/36/48 V Semi-reg. Power: 400 W Grade: Industrial 100 0 100 200 300 400 500 Efficiency (%) Output Power (W) Power (W) Ambient Temperature (ºC) 24 / 36 / 48 V with Fan Enabled

12 V with Fan Enabled

24 / 36 / 48 V with Fan Disabled

12 V with Fan Disabled

Power (W) Input AC Voltage (VRMS) Transient Continuous 0 1 2 3 4 5 6 7 8 9 Output Voltage (V) Output Load (A) EFFICIENCY, DERATING, AND VOUT DROOP CURVES Technical Specification Figure 7: 48 VOUT efficiency curves. Figure 8: 48 VOUT droop characteristic. Figure 9: Continuous power derating curve in natural convection Figure 10: Rated output power vs Input AC Voltage

Product # AQ0400IUxT Phone 1-888-567-9596 www.SynQor.com Doc.# 005-005053 Rev. C 08/24/15 Page 5 AC Input: 85-264 Vrms DC Output: 12/24/36/48 V Semi-reg. Power: 400 W Grade: Industrial Technical Specification AC Leakage Current from Input to Earth AC Line Connection Normal Condition Open Neutral Fault ACuQor Typical at 110% nominal input voltage 60 Hz

240 V L-N, 1 phase 400 µA 800 µA

208 V L-L, 120 V L-N, 1 of 3 phases 200 µA 400 µA

240 V L-N-L, 120 V L-N, split phase 200 µA 400 µA

Standard Testing Certifications SAFETY AGENCY CERTIFICATIONS CAN/CSA-C22.2 No. 60950-1:2007 UL 60950-1:2007 EN 60950-1/A1:2010 CE Marked

Product # AQ0400IUxT Phone 1-888-567-9596 www.SynQor.com Doc.# 005-005053 Rev. C 08/24/15 Page 6 AC Input: 85-264 Vrms DC Output: 12/24/36/48 V Semi-reg. Power: 400 W Grade: Industrial CONNECTOR DETAILS OUTPUT CONNECTOR PINOUT (top side) Pin 1 FAN_GOOD Open collector with internal 5V pullup. See Figure A. Pulsed low on fan failure, 100ms, 50% duty. Short to VOUT(-) to disable fan. Pin 2 AC_POWER_GOOD Open collector with internal 5V pullup. See Figure B. Pulled low on AC power dropout. Pin 3 DC_POWER_GOOD Open collector with internal 5V pullup. See Figure B. Pulled low during startup ramp and within 5 ºC of temperature shutdown threshold. Pin 4 5V_STANDBY 5 V @ 10 W available whenever AC power is applied. Pin 5 VOUT(+) Positive Output Voltage. Pin 6 VOUT(+) Positive Output Voltage. Pin 7 VOUT(+) Positive Output Voltage. Pin 8 VOUT(+) Positive Output Voltage. Pin 9 Reserved Reserved for future use. Pin 10 Reserved Reserved for future use. Pin 11 REMOTE_ENABLE Logic input. See Figure C. Pull high to enable main output. Pin 12 12V_STANDBY 12 V @ 50 W available whenever AC power is applied. Pin 13 VOUT(–) Negative Output Voltage. Pin 14 VOUT(–) Negative Output Voltage. Pin 15 VOUT(–) Negative Output Voltage. Pin 16 VOUT(–) Negative Output Voltage. INDIVIDUAL INPUT CONNECTOR PINOUT Pin 1 Ground Pin 3 AC Neutral Pin 5 AC Line

12 V OUTPUT CONNECTOR PINOUT (bottom side)

Pin 1 VOUT(+) Positive Output Voltage. Pin 2 VOUT(+) Positive Output Voltage. Pin 3 VOUT(+) Positive Output Voltage. Pin 4 VOUT(+) Positive Output Voltage. Pin 5 VOUT(–) Negative Output Voltage. Pin 6 VOUT(–) Negative Output Voltage. Pin 7 VOUT(–) Negative Output Voltage. Pin 8 VOUT(–) Negative Output Voltage MATING CONNECTORS Connector Type Contact OUTPUT (16 pins) Molex 430251600 Molex 430300008* 12V_OUTPUT (8 pins) Molex 436450800 Molex 430300008* INPUT JST VHR-5N JST SVH-41T-P1.1 * Each contact rated for a maximum of 5.5 A. Figure A: Fan status output / Fan enable input interface circuitry. N3904

10 Ohms

AC_POWER_GOOD or DC_POWER_GOOD 0.1 µF From AC/DC Monitor Circuitry VOUT(-) N4148 5V_STANDBY Figure B: Power good interface circuitry. REMOTE_ENABLE 10k

10 Ohms To Enable

VOUT(-) 0.1 µF 5 k 5V_STANDBY 5V_STANDBY Figure C: Remote enable interface circuitry.

Product # AQ0400IUxT Phone 1-888-567-9596 www.SynQor.com Doc.# 005-005053 Rev. C 08/24/15 Page 7 AC Input: 85-264 Vrms DC Output: 12/24/36/48 V Semi-reg. Power: 400 W Grade: Industrial Technical Specification MECHANICAL DRAWINGS (1 Module Open Frame Version — E Package Type) NOTES (applies to all mechanicals) 1) Recommended screw tightening torque of 6 in.lbs 2) Undimensioned components are shown for visual reference only 3) All dimensions in inches [mm] Tolerances: x.xx in ± 0.02 x.xxx in ± 0.010 .75 [19.1] 5.25 [133.4] 1.05 [26.6] 4.91 [124.7] 4.13 [104.8] .17 [4.3] 3.03 [76.8] Manufacturing Label PN# S/N DATE CODE 1.48 [37.5] 1.75 [44.5] 3.50 [88.9] 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 OUTPUT 3.59 [91.3] 3.04 [77.1] Ø .19 [4.75] PLASTIC RIVET OD. 6 - 32 SELF-CLINCHING INSERT MOUNTING SCREW SHALL NOT PROTUDE 3/8” INTO THE CHASSIS (4 PIECES) 1.63 [41.3] 1.63 [41.3] .70 [17.8] 1.31 [33.1] .11 [2.9] BottomTop Front Back Right 3.00 [76.2] 3.03 [77] OUTPUT CONNECTOR INPUT CONNECTOR 1.50 [38.1] INPUT CONNECTOR INPUT CONNECTOR .123 ±.019 [3.12 ±0.48] BOTTOMSIDE CLEARANCE 1.444 ±.053 [36.67 ±1.34] 6 - 32 STANDOFF 1/4" HEX BODY 3/16" INTERNAL THREAD (4 PIECES).70 [17.8] .13 [3.3] .20 [5.1] .13 [3.2] 1.03 [26.1] 1.06 [26.8] .68 [17.4] INPUT OUTPUT 2.60 [66] 2.90 [73.7] 5.00 [127] 4.60 [116.8] OUTPUT CONNECTOR Manufacturing Label PN# S/N DATE CODE BottomTop Front Back Right (1 Module Encased Version — E Package Type)

Product # AQ0400IUxT Phone 1-888-567-9596 www.SynQor.com Doc.# 005-005053 Rev. C 08/24/15 Page 8 AC Input: 85-264 Vrms DC Output: 12/24/36/48 V Semi-reg. Power: 400 W Grade: Industrial MECHANICAL DRAWINGS Technical Specification (2 Modules Flat Version - R Package Type) 6 - 32 Self - Clinching Insert Mounting Screw shall not Protude 3/8” into the chassis (6 pieces) Bottom 4.56 [115.7] 6.29 [159.6] 4.91 [124.7] .17 [4.3] 1.31 [33.1] .71 [18] 1.63 [41.3] 3.03 [76.8] 4.88 [123.8] 5.25 [133.4] 5.00 [127] 1.75 [44.5] 6.75 [171.5] 3.63 [92.1] .38 [9.5] 1.05 [26.7] INPUT 1.48 [37.5] TOP Right Front Back OUTPUT 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 OUTPUT 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 5 3 15 3 1 Ø.19 [4.75] PLASTIC RIVET OD.

Product # AQ0400IUxT Phone 1-888-567-9596 www.SynQor.com Doc.# 005-005053 Rev. C 08/24/15 Page 9 AC Input: 85-264 Vrms DC Output: 12/24/36/48 V Semi-reg. Power: 400 W Grade: Industrial MECHANICAL DRAWINGS Technical Specification 6-32 SELF-CLINCHING INSERT MOUNTING SCREW SHALL NOT PROTRUDE .200” INTO THE CHASSIS (4 PIECES) 6-32 SELF-CLINCHING INSERT MOUNTING SCREW SHALL NOT PROTRUDE 3/8” INTO THE CHASSIS (4 PIECES) 3.04 [77.1] 4.91 [124.7] 4.85 [123.2] .17 [4.3] .20 [5.1].23 [5.9] .61 [15.4] 1.59 [40.5] .71 [18] 2.30 [58.5] 1.31 [33.1] 3.50 [88.9] 5.25 [133.4] 3.03 [76.8] .38 [9.5] 1.05 [26.7] 2.65 [67.2] 3.25 [82.6] INPUTINPUT OUTPUT OUTPUT 161514131211109 87654321 161514131211109 87654321 135 135 1.75 [44.5] (2 Modules Stacked Version - S Package Type)

Product # AQ0400IUxT Phone 1-888-567-9596 www.SynQor.com Doc.# 005-005053 Rev. C 08/24/15 Page 10 AC Input: 85-264 Vrms DC Output: 12/24/36/48 V Semi-reg. Power: 400 W Grade: Industrial MECHANICAL DRAWINGS Technical Specification 4.91 [124.7] 3.14 [79.8] 6.39 [162.4] 9.54 [242.2] .23 [5.9] .17 [4.3] 6 - 32 SELF-CLINCHING INSERT MOUNTING SCREW SHALL NOT PROTUDE 3/8” INTO THE CHASSIS (6 PIECES) 1.63 [41.3] .71 [18] 10.09 [256.4] 1.31 [33.1] 4.56 [115.7] 7.81 [198.2] 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 OUTPUTOUTPUT 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 OUTPUT 1.05 [26.7] 3.63 [92.1] 6.88 [174.6] .38 [9.5] INPUT 5 3 1 5 3 15 3 1 .75 [19.1] 4.88 [123.8] 1.48 [37.5] Ø .19 [4.8] PLASTIC RIVET OD. 3.03 [76.8] 5.25 [133.4] 5.00 [127] 1.75 [44.5] 8.25 [12.096] 10.00 [254] (3 Modules Flat Version - T Package Type)

Product # AQ0400IUxT Phone 1-888-567-9596 www.SynQor.com Doc.# 005-005053 Rev. C 08/24/15 Page 11 AC Input: 85-264 Vrms DC Output: 12/24/36/48 V Semi-reg. Power: 400 W Grade: Industrial MECHANICAL DRAWINGS Technical Specification 1 3 5 1 3 5 1 3 5 Manufacturing Label PN# S/N DATE CODE 3.50 [88.9] 1.75 [44.5] 3.21 [81.5] .61 [15.4] 3.04 [77.1] .38 [9.5] 1.05 [26.7] INPUT INPUT INPUT OUTPUT OUTPUT OUTPUT 2.66 [67.5] 4.26 [108.2] 4.875 [123.83] 6-32 SELF-CLINCHING INSERT MOUNTING SCREW SHALL NOT PROTRUDE .200” INTO THE CHASSIS (4 PIECES) 6-32 SELF-CLINCHING INSERT MOUNTING SCREW SHALL NOT PROTRUDE 3/8” INTO THE CHASSIS (4 PIECES) 3.92 [99.5] 2.31 [58.8] 1.31 [33.1] .71 [18] 5.25 [133.4] 3.03 [76.8] 4.85 [123.2] .23 [5.9] .20 [5.1] 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 (3 Modules Stacked Version - U Package Type)

Product # AQ0400IUxT Phone 1-888-567-9596 www.SynQor.com Doc.# 005-005053 Rev. C 08/24/15 Page 12 AC Input: 85-264 Vrms DC Output: 12/24/36/48 V Semi-reg. Power: 400 W Grade: Industrial Technical Specification Chassis confi gurations for Parallel Units ACuQor units are available either open-frame or pre-mounted at the factory. Up to 3 units can be mounted into a chassis, in either side-by-side or stacked confi gurations. For a complete list of options, see the “Part Numbering System” table on the last page, under “Package Type”, along with the Mechanical Drawings pages. Only side-by-side confi gurations can be populated with 500W units, since each includes a thermal pad underneath. Interconnection of Parallel Units ACuQor units mounted in 2 and 3 unit chassis are not connected together. This allows the physical routing and connectivity of the external wiring to be customized to each application. The following table summarizes the recommended wiring to operate multiple units in parallel: Specifi cations of Parallel Units As a rule, units wired in parallel behave the same as single units. Any specifi cation will remain unchanged that is expressed in units of voltage, time, frequency, or effi ciency. Specifi cations expressed in terms of power, current, or capacitance, should be scaled by the number of units wired in parallel. ACuQor units are individually calibrated at the factory, so that the output voltage vs. output current characteristic is always consistent (see Vout droop characteristic fi gures). As such, multiple units will share output current accurately. Full current is guaranteed from a bank of multiple units wired in parallel. Output Connector Signal Suggested Connection Behavior with Multiple Units REMOTE_ENABLE Wire in parallel Inputs activated simultaneously FAN_GOOD “ Wired-OR outputs – can be pulled low by any unit during an abnormal condition. AC_POWER_GOOD “ “ DC_POWER_GOOD “ “ VOUT(+), VOUT(-) “ Built-in droop characteristic ensures graceful current sharing. 12V_STANDBY* “ “ 5V_STANDBY Do not wire in parallel Fully regulated characteristic does not support current sharing. If placed in parallel, only the output with the highest set-point will drive current. *Note: Triple output models only. PARALLEL OPERATION - MULTIPLE UNITS

Product # AQ0400IUxT Phone 1-888-567-9596 www.SynQor.com Doc.# 005-005053 Rev. C 08/24/15 Page 13 AC Input: 85-264 Vrms DC Output: 12/24/36/48 V Semi-reg. Power: 400 W Grade: Industrial INSTALLATION INSTRUCTIONS General: ACuQor AC/DC power supplies are intended for use as components in industrial equipment. ACuQor units must be properly installed within end use equipment before they can be safely applied as described in this document. The suitability of the ACuQor/equipment combination must be verified through end product investigation. Mounting: Refer to the Mechanical Drawings section. ACuQor units are provided with threaded stainless-steel stand-offs or inserts for mounting. This mounting hardware is internally connected to the input connector protective-earth terminal for functional-earth EMC control. Any orientation (vertical, horizontal, etc.) may be used. Adequate air space should be provided over the fan intake (top) and exhaust (sides) to allow for exchange of cooling air. ACuQor is designed for a pollution degree 2 environment. The suitability of the enclosed ACuQor mechanical assemblies must be verified through end product investigation. Encased models: A minimum of 5 mm electrical clearance should be allowed from the connector ends of encased models. Input: Refer to the Connector Details section for input connec- tor wiring. ACuQor products require a single phase AC power source of 100-240V 50/60Hz nominal. Refer to nameplate label for input current ratings. A protective-earth connection is also required. Minimum wire size of 18 AWG (0.8mm 2) is recom- mended. Both sides of the AC line are internally fused (see table for specific models). These fuses are not user replaceable. MODEL Input Fuses (in Both AC Lines) Fuses Total AQ0300 Littelfuse 6.3A 250V 21606.3XEP 2 AQ0400 Littelfuse 6.3A 250V 21606.3XEP 2 AQ0500 Littelfuse 10.0A 250V 216010XEP 2 Output: Refer to the Connector Details section for output con- nector wiring and signal I/O functionality. Refer to nameplate label for output current ratings. Main DC output (Vout+, Vout-) pins should use 20 AWG (0.5mm 2) wire size. Individual main output pins should not be loaded to more than 5.5 A. For currents greater than 5.5 A, multiple main output pins/wires must be used in parallel. All signal I/O pins are referenced to Vout-. EMC: ACuQor products have been tested to the EMC specifica- tions listed in the Electrical Characteristics section. However, end use equipment must be tested to verify EMC compliance. Hipot Testing: ACuQor products are rated for Hipot testing levels of 1500 Vac input to protective-earth, 500 Vac output to protective-earth, and 3000 Vac input to output. When perform- ing the 3000 Vac input to output test, the test voltage must be balanced evenly 1500 Vac input and output to protective-earth. Two oppositely phased test voltage sources or a single test volt- age source with external balancing impedances (capacitors) may be used to prevent overstressing input or output to protective-earth insulation per IEC/ENC 60950-1.

Product # AQ0400IUxT Phone 1-888-567-9596 www.SynQor.com Doc.# 005-005053 Rev. C 08/24/15 Page 14 AC Input: 85-264 Vrms DC Output: 12/24/36/48 V Semi-reg. Power: 400 W Grade: Industrial ACCESSORIES SynQor offers a series of assemblies that can be ordered according to the table below. Mechanical drawings for these accessories are available for download in pdf format from the SynQor website. Family Output Power Grade Range Output Voltage Package Type Thermal Design Options AQ: ACuQor series of AC-DC semi-regulated output power supplies 0300: 300 W 0400: 400 W 0500: 500 W 0600: 600 W (2 x 300 W) 0800: 800 W (2 x 400 W) 0900: 900 W (3 x 300 W) 1000: 1000 W (2 x 500 W) 1200: 1200 W (3 x 400 W) 1500: 1500 W (3 x 500 W) I: (Industrial) U: Universal (85-264 VRMS) 12: 12 V 1T: 12 V / 5 & 12 V STBY 24: 24 V 2T: 24 V / 5 & 12 V STBY 36: 36 V 3T: 36 V / 5 & 12 V STBY 48: 48 V 4T: 48 V / 5 & 12 V STBY E: 1 unit (3"x5") R: 2 units; flat S: 2 units; stacked T: 3 units; flat U: 3 units; stacked A: Open frame C: Encased Industrial Grade: IND: Industrial Part Number Description AQ-CBL-INPUT1C Input mating cable with pre-stripped wire ends (36” long). AQ-CBL-OUT1C Output mating cables with pre-stripped wire ends (18” long). AQ-CBL-OUT1CD Same as AQ-CBL -OUT1C with an additional 8-pins connector. AQ-CBL-OUT2C Output mating cable with connectors on both ends (18" long). AQ-CBL-OUT2CD Same as the AQ-CBL-OUT2C with an additional 8-pins connector. AQ-INSUL1M Single module bottom-side Mylar insulator for open frame mounting AQ-EVAL-PRL3 Evaluation board for up to three paralleled modules. Example: AQ0400IU2TRCIND APPLICATION NOTES A variety of application notes and technical white papers can be downloaded in pdf format from the SynQor website. Online Application Notes Online Library of Technical White Papers SynQor website. PART NUMBERING SYSTEM The part numbering system for SynQor’s ACuQor AC/DC power supplies follows the format shown in the table below. Not all combinations make valid part numbers, please contact SynQor for availability.

Ordering Information

SynQor offers a two (2) year limited warranty. Complete warranty information is listed on our website or is available upon request from SynQor. Contact SynQor for further information and to order: Phone: 978-849-0600 Toll Free: 888-567-9596 Fax: 978-849-0602 E-mail: power@synqor.com Web: www.synqor.com Address: 155 Swanson Road Boxborough, MA 01719 USA PATENTS SynQor holds numerous U.S. patents, one or more of which apply to most of its power converter products. Any that apply to the product(s) listed in this document are identified by markings on the product(s) or on internal components of the product(s) in accordance with U.S. patent laws. SynQor’s patents include the following: 5,999,417 6,222,742 6,545,890 6,594,159 6,731,520 6,894,468 6,896,526 6,927,987 7,050,309 7,072,190 7,085,146 7,119,524 7,269,034 7,272,021 7,272,023 7,558,083 7,564,702 7,765,687 7,787,261 8,023,290 8,149,597 8,493,751 8,644,027