APTE MSYSTEM | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

MODEL: APTE APTE SPECIFICATIONS ES-0235 Rev.2 Page 1/4 http://www.m-system.co.jp/ Limit Alarms (potentiometer adj.) A-UNIT PT ALARM (RMS sensing) Functions & Features

  • Providing SPDT relay outputs at preset AC voltage levels from a VT
  • RMS sensing
  • Dual (Hi/Lo) trip
  • Energized or de-energized coil at a tripped condition selectable
  • Hysteresis (deadband) adjustable
  • Enclosed relays
  • Relays can be powered 110 V DC
  • High-density mounting Typical Applications
  • Annunciator
  • Various alarm applications (1.97) 132 (5.20) (3.15) mm (inch) MODEL: APTE-[1]1[2][3]-[4]

ORDERING INFORMATION

  • Code number: APTE-[1]1[2][3]-[4] Specify a code from below for each of [1] through [4]. (e.g. APTE-1111-B) [1] INPUT Voltage 1: 0 – 110 V AC 2: 0 – 220 V AC 5: 0 – 150 V AC 6: 0 - 300 V AC [2] SETPOINT 1 OUTPUT 1: Hi (coil energized at alarm) 2: Hi (coil de-energized at alarm) 3: Lo (coil energized at alarm) 4: Lo (coil de-energized at alarm) [3] SETPOINT 2 OUTPUT 1: Hi (coil energized at alarm) 2: Hi (coil de-energized at alarm) 3: Lo (coil energized at alarm) 4: Lo (coil de-energized at alarm) [4] POWER INPUT AC Power B: 100 V AC C: 110 V AC D: 115 V AC F: 120 V AC G: 200 V AC H: 220 V AC J: 240 V AC DC Power S: 12 V DC R: 24 V DC V: 48 V DC P: 110 V DC GENERAL SPECIFICATIONS Construction: Plug-in Connection: M3.5 screw terminals Housing material: Flame-resistant resin (black) Isolation: Input to output 1 to output 2 to power Input waveform: Up to 15 % of 3rd harmonic content Zero adjustment: -5 to +5 % (front) Span adjustment: 95 to 105 % (front) Setpoint adjustments: 270°-turn screwdriver adjustments (front); 0 – 100 % independently Hysteresis (deadband) adjustments: 1 – 100 % (front) Front LEDs: LED turns on at a tripped condition; red for output 1, green for output 2 Power ON timer: Relays de-energized for approx. 2 seconds after power is turned on. INPUT SPECIFICATIONS Frequency: 50 or 60 Hz Input burden: 0.5 VA max. Overload capacity: 200 % of rating for 1 minute, 120 % continuous Operational range: 0 – 100 % of rating

MODEL: APTE APTE SPECIFICATIONS ES-0235 Rev.2 Page 2/4 http://www.m-system.co.jp/ OUTPUT SPECIFICATIONS ■ Relay Contact: 100 V AC @ 1 A (cos ø = 1)

120 V AC @ 1 A (cos ø = 1)

240 V AC @ 0.5 A (cos ø = 1)

30 V DC @ 1 A (resistive load)

Maximum switching voltage: 380 V AC or 125 V DC Maximum switching power: 120 VA or 30 W Minimum load: 5 V DC @ 10 mA Mechanical life: 5 x 107 cycles For maximum relay life with inductive loads, external protection is recommended. Output Code: 1 & 4: Terminals 1 – 2, 9 – 10 turn ON Alarm Trip Operation Terminal No. in parentheses Trip Operation in Power Failure

  • Output Code: 2 & 3 : Terminals 1 – 3, 9 – 11 turn ON 0 50 100 ▲ Input (%) Output 2 Setpoint Output 1 Setpoint Output 1 (9-10)ON Output 2 (1-2)ON (1-3)ON (9-11)ON INSTALLATION Power input
  • AC: Operational voltage range: rating ±10 %, 50/60 ±2 Hz, approx. 2 VA
  • DC: Operational voltage range: rating ±10 %, or 85 – 150 V for 110 V rating (ripple 10 % p-p max.) approx. 2 W (80 mA at 24 V) Operating temperature: -5 to +60°C (23 to 140°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Surface or DIN rail Weight: 450 g (0.99 lb) PERFORMANCE in percentage of span Trip point repeatability: ±0.5 % Temp. coefficient: ±0.05 %/°C (±0.03 %/°F) Response time: ≤ 0.7 sec. (0 – 100 % at 90 % setpoint) Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @1 minute (input to output 1 to output 2 to power to ground)

MODEL: APTE APTE SPECIFICATIONS ES-0235 Rev.2 Page 3/4 http://www.m-system.co.jp/ EXTERNAL VIEW No.1 LED No.1 Deadband (Hysteresis) Adj. No.2 Deadband (Hysteresis) Adj. No.2 LED No.1 Setpoint Adj. No.2 Setpoint Adj. Zero Adj. Span Adj. EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 80 (3.15) 132 (5.20) (.79)

  • When mounting, no extra space is needed between units. 5678 2111 10 [3.3 (.13)] 80 (3.15) 40 (1 .57) 50 (1 .97) 7 .8 (.31) CLAMP (top & bottom) DIN RAIL 35mm wide2–4.5 (.18) dia. MTG HOLE 25 (.98) deep 11 –M3.5 SCREW SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Base Socket Comparator *Relay status for output codes “1” & “4”, at power OFF. LOAD Inductive Load (Coil) Varistor or Spark Quenching Circuit ■ Relay Protection
  • AC Powered • DC Powered LOAD Inductive Load (Coil) Diode, Varistor or CR Circuit R.M.S. Operation V U v uFUSE VT LOAD SOURCE U(+) V(–) POWER Comparator Ry Ry SETPOINT HYSTERESIS (DEADBAND) SETPOINT HYSTERESIS (DEADBAND) H L C SETPOINT 1 OUTPUT H L C SETPOINT 2 OUTPUT INPUT TRANS- FORMER Low Drift Amplifier Resistance Divider SZ U

MODEL: APTE APTE SPECIFICATIONS ES-0235 Rev.2 Page 4/4 http://www.m-system.co.jp/ Specifications are subject to change without notice.