Specifications are subject to change without notice. These products are not intended for use as critical components in life support or nuclear systems. ACB-3000 Redundancy Static Transfer Switch Several references are subjected to special MOQs and lead times. Please consult Premium’s Sales Dept. and website. GENERAL FEATURES: Available in two variants (13 A rms and 21 A rms) with configurable nominal input voltage Switching time < 2 ms Designed for industrial and railway applications according to EN50155:2017 and EN45545-2 Safety according to norm IEC 62368-1 Local signaling by LED Remote signaling by solid state relays CANopen BUS port MODEL ACB-3000-9431 ACB-3000-9576 Voltage lines 230 VAC 230 VAC Maximum current 13 ARMS 21 ARMS Suitable for inverters ODS-750 ODS-1500 ODS-3000 ODS-750 ODS-1500 ODS-3000

Redundancy static transfer switch 22-09-2025 CA-637-15 www.premiumpsu.com Powering Your Challenge Note-1: ACB3000 input voltage protection will trigger when the difference between the input sine wave and an ideal one is ±0.2 p.u. Note-2: The ACB-3000 is designed to handle maximum instantaneous currents as specified by the Instantaneous Current Error Detection graph. Note-3: This option allows the user to maintain communication with the internal MCU in the event of an L1 + L2 failure. Note-4: Under no-load conditions (below 20W), the switching time is not guaranteed. MODEL 9431 9576 INPUTS Default nominal AC input voltage 230 V Minimum/Maximum AC input voltage1 ±20% of nominal Input Frequency 50/60 Hz ± 10 % Efficiency at nominal conditions >99% OUTPUT Output voltage 230 V (same as input) Maximum continuous current 13 ARMS 21 ARMS Maximum instantaneous current (100ms)2 26 Arms 42 Arms EXTERNAL CONTROL SUPPLY (optional)3 Nominal DC input voltage (Vbat) 15 – 139 Vdc ENVIRONMENTAL Storage temperature -40 … 85 °C Operating temperature: Full load Operating temperature: 70 % load Operating temperature: 50 % load -40 … 55 °C (EN50155 OT2) -40 … 70 °C (EN50155 OT4) -40 … 85 °C (EN50155 OT6) Cooling Natural convection Operating altitude 2000m at full load, 2500m at 90% of load Maximum Relative humidity 95 % with no condensation Shock and vibration EN61373:2011 Category 1 class B body mounted Service life > 20 years MTBF > 1Mh @ 40 °C according to IEC61709 EMC Emission EN50121-4 Immunity EN50121-4 SAFETY Safety according to norm IEC 62368-1 Dielectric strength Input-Output / Earth 1500 VAC 50 Hz Dielectric strength DC input / Earth 1500 VAC 50 Hz Protection Degree IP40 Pollution degree PD2 Overvoltage category OV2 Fire and smoke EN45545-2:2013 +A1:2015 MECHANICAL Dimensions 78,34 x 60 x 200 mm Weight 1,2 kg CONTROL Switching response time in case of failure4 < 2 ms Input 1 OK Green Input 2 OK Green Output OK Green Failure of the system Red Status Can Bus PROTECTIONS Against output overloads and short-circuits Current limiting by fuse and active protection of overcurrent with push-in button for system restart after a recurrent overcurrent situation. Failure in line 1 Solid state relay 1 closed if line 1 is OK. Failure in line 2 Solid state relay 2 closed if line 2 is OK. Failure in system Solid state relay 3 closed if all the system is OK.

Redundancy static transfer switch 22-09-2025 CA-637-15 www.premiumpsu.com Powering Your Challenge ORDERING CODES Several references are subjected to special MOQs and lead times. Please consult Premium’s Sales Dept. and website. Nominal mains voltage A 100V B 110V C 115V D 120V E 127V F 200V G 220V 230V (default) I 240V Model number

Redundancy static transfer switch 22-09-2025 CA-637-15 www.premiumpsu.com Powering Your Challenge BLOCKS DIAGRAM CONNECTIONS Element Description Notes J7 - 1 Line input 1 (priority) Spring clamp terminals Maximum cross section cable: 6mm2 J7 - 2 Neutral input 1 (priority) J8 - 1 Neutral input 2 J8 - 2 Line input 2 J6 - 1 Line output J6 - 2 Neutral output J1 - 1 - Vbat auxiliar (optional)3 Recommended male connector: Phoenix Contact 1790124 J1 - 2 + Vbat auxiliar (optional)3 J1 - 3, 4 Relay of failure in line 2 J1 - 5, 6 Relay of failure in line 1 J1 - 7, 8 Relay of failure in system J4 - 2 CAN bus: CAN_L Sub-D9 J4 - 3 CAN bus: CAN_GND J4 - 7 CAN bus: CAN_H Earth Earth connection Stud M4 Torque <2.5 Nm Reset Restarts the system from a permanent overcurrent situation. Button

DESCRIPTION

The ACB-3000 is an ultrafast dual-line static transfer switch that selects the appropriate line when a failure occurs. It continuously monitors the waveform of both input lines and, if the active line deviates from specifications, switches to the other line within 2 ms. This rapid response is achieved through a fully digital control combined with advanced SiC MOS power switches. Designed for both industrial and railway environments, the ACB-3000 is compatible with the Premium ODS -750, ODS - 1500, and ODS-3000 inverter families. In case of any failure, the unit indicates it locally via an LED and remotely via a solid-state relay and a CANopen bus port. During normal operation, the active input line is indicated by a blinking LED. When the other input line is properly powered, its LED remain s illuminated. Similarly, an illuminated output LED confirms proper operation. The switching occurs when the active input line has any of the following events: 1. Frequency out of range (10%). 2. Instantaneous undervoltage detection (20% of voltage). The response time is 1ms. 3. Voltage out of the safe zone: As indicated by the ITI curve in the figure, if the active line voltage moves beyond the defined “Safe Zone” for longer than the permissible duration, the system triggers a switching to the other line. The yellow zone represents a warning area, where a rapidly blinking LED alerts that the voltage has deviated more than 10% from its nominal value. 1 2 3 4 5 6 7 8

Redundancy static transfer switch 22-09-2025 CA-637-15 www.premiumpsu.com Powering Your Challenge When both input lines are within their specified ranges, input 1 is automatically selected as the active input by default (this setting can be configured via CAN). Conversely, if both input lines fall outside the acceptable ranges, the output is disconnected from both inputs. OVERLOAD PROTECTION The device is protected against overloads and short-circuits through a current-limiting circuit. When an overcurrent is detected, the failure LED is on, and the power switches turn off. The unit will attempt to restart every second, up to 3 times after the overload detection (configurable by CAN) . If the overload persists, the output remains disabled until a manual reset is performed by pressing the RESET button. The device can handle demanding conditions, sustaining twice the RMS current for 100 ms. Furthermore, as shown in the lower graph, it can withstand higher transient surges for shorter durations, ensuring robust and reliable performance during transient load conditions.

Redundancy static transfer switch 22-09-2025 CA-637-15 www.premiumpsu.com Powering Your Challenge OUTPUT WAVEFORMS Example of line disconnection. Line fault at 0V. Example of line disconnection at no load condition (<20W). Example of line disconnection. Line fault at high voltage. Example of reconnection to the priority line.

Redundancy static transfer switch 22-09-2025 CA-637-15 www.premiumpsu.com Powering Your Challenge CAN COMMUNICATION PORT It is possible to control and monitor the unit via SUB-D9 connector with CAN protocol. Protocol configuration: By default, CANopen devices start without CANopen Node-ID (0xFF) and baudrate of 250 kbit. Node ID must be set to communicate with the device. STANDARIZED DEVICE PROFILE AREA Index SubIndex Name Type Attribute Notes 0x6001 0x00 Active Line UINT8 ro 0x6002 0x00 State UINT8 ro 0x6003 0x00 Number of Failures UINT8 ro 0x6100 0x01 Input Voltage RMS 1 UINT32 ro 0x6100 0x02 Input Voltage RMS 2 UINT32 ro 0x6101 0x01 Input Current RMS 1 UINT32 ro 0x6101 0x02 Input Current RMS 2 UINT32 ro 0x6102 0x01 Input Frequency 1 UINT32 ro 0x6102 0x02 Input Frequency 2 UINT32 ro 0x6103 0x01 Input State 1 UINT8 ro 0x6103 0x02 Input State 2 UINT8 ro 0x6105 0x01 Input Frequency 1 (float) FLOAT ro 0x6105 0x02 Input Frequency 2 (float) FLOAT ro 0x6200 0x00 Output Voltage RMS UINT32 ro 0x6201 0x00 Output Current RMS UINT32 ro Measure in deciAmperes (dA) 0x6202 0x00 Output Frequency UINT32 ro 0x6203 0x00 Output Current (float) FLOAT ro 0x6300 0x00 Number of Startups UINT32 ro 0x6301 0x00 Number of Hours ON UINT32 ro 0x6302 0x00 Zero-Crossing Grid Transition Switch UINT32 rw Ensures grid transition at zero crossing (default: disabled) 0x6303 0x00 Nominal Voltage UINT32 rw Limited between 100 and 240 Vrms 0x6304 0x00 Frequency Mode Selection UINT32 rw 0 = 50 Hz, 1 = 60 Hz (default: 50 Hz) 0x6305 0x00 Allowed Number of Consecutive Overcurrents UINT32 rw Default: 3 0x6306 0x00 Overcurrent Clear Time (ms) UINT32 rw Time to reset the consecutive overcurrent counter (default: 10000 ms, min: 1000 ms) 0x6307 0x00 Overcurrent State Duration (ms) UINT32 rw Time before restarting the system after an overcurrent (default: 1000 ms, min: 16 ms) 0x6308 0x00 Recovery Time to Priority Grid (ms) UINT32 rw Time to switch back to the priority grid (default: 5000 ms, min: 200 ms) 0x6309 0x00 Configured Priority Mode UINT32 rw 1 = Grid 1, 2 = Grid 2 (default: grid 1) 0x630A 0x00 ITI Mode UINT32 rw Uses ITI curve as stability evaluation criterion (default: enabled)

Redundancy static transfer switch 22-09-2025 CA-637-15 www.premiumpsu.com Powering Your Challenge COMMUNICATION PROFILE AREA Index SubIndex Name Type Attribute Notes 0x1001 0x00 Error register UINT8 ro 0x1003 0x00 Number of errors DYNAMIC_TABLE rw 0x1003 0x01 Error messages DYNAMIC_TABLE ro 0x1008 0x00 Manufacturer device name ARRAY ro 0x100A 0x00 Manufacturer software version ARRAY ro 0x1017 0x00 Producer Heartbeat time UINT16 rw 0x1029 0x00 Error behavior object UINT8 - 0x1018 0x01 Vendor_ID UINT32 ro 0x1018 0x02 Product Code UINT32 ro 0x1018 0x03 Revision Number UINT32 ro 0x1018 0x04 Serial Number UINT32 ro

Redundancy static transfer switch 22-09-2025 CA-637-15 www.premiumpsu.com Powering Your Challenge DIMENSIONS Fixing holes 6 x M3 (screw torque < 1.6 Nm). Maximum screw penetration depth 5 mm. Earth screw M4 (nut torque < 2.5 Nm)

Redundancy static transfer switch 22-09-2025 CA-637-15 www.premiumpsu.com Powering Your Challenge ACESSORIES Description Notes CODE 2U 19" rack mounting tray kit. Allows to install an ACB-3000 and up to two inverters NP-9353 Base mounting plate Includes 3 screws NP-9636 DIN rail mounting Includes DIN rail adaptor, interface plate and screws NP-9637 NP-9353 Example for ODS-1500 Example for ODS-3000 NP-9636 NP-9637

Redundancy static transfer switch 22-09-2025 CA-637-15 www.premiumpsu.com Powering Your Challenge EU, UKCA DECLARATION OF CONFORMITY The undersigned, representing the following: Manufacturer: PREMIUM, S. A., Address: C/ Dolors Aleu 19-21, 08908 L’Hospitalet de Llobregat, SPAIN herewith declares that the product: Type: AC/AC bypass Model: ACB-3000- 9431 - 9576 is in conformity with the provisions of the following EU directive(s): 2014/35/EU SI 2016 No 1101 Low voltage / The electrical equipment (safety) regulations 2014/30/EU SI 2016 No 1091 EMC / Electromagnetic compatibility regulations 2011/65/EU Annex II and its amendment 2015/863/EU SI 2012 No. 3032 RoHS / Restriction of the use of certain hazardous substances in electrical and electronic equipment and that standards and/or technical specifications referenced below have been applied: EN 60950-1: 2005 Safety. Information technology equipment EN 62368-1: 2014 Safety. Audio/video information and communication technology equipment EN 61000-6-3: 2007 Generic emission standard EN 61000-6-2: 2005 Generic immunity standard EN 50155: 2017* Railway applications. Electronic equipment used on rolling stock material EN 50121-4: 2017* Railway applications. EMC Rolling stock equipment * See annexe CE marking year: 2020; UKCA marking year: 2021 Notes: For the fulfillment of this declaration the product must be used only for the aim that has been conceived, considering the limitations established in the instructions manual or datasheet. L’Hospitalet de Llobregat, 31-05-2021 PREMIUM S.A. is an ISO9001and ISO14001 certified company by Bureau Veritas Miguel Angel Fernandez Chief Research & Development Officer

Redundancy static transfer switch 22-09-2025 CA-637-15 www.premiumpsu.com Powering Your Challenge ANNEXE Applicable values for the different sections of the norm EN50155: 2017

4.3.1 Working altitude Up to 2000m

4.3.2 Ambient temperature

Class OT1 (-25 to 55°C): load < 100% Class OT3 (-25 to 70°C): load <62.5% Class OT5 (-25 to 85°C): load <25% 4.3.3 Switch-on extended operating temp. Class ST1

4.3.4 Rapid temperature variations Class H1

4.3.5 Shocks and vibrations According EN61373:2010 Category 1 class B

4.3.6 EMC Electromagnetic Compatibility EN50121-4:2017 Test Norm Port Frequency Limits Radiated emissions IEC55016 Case 30MHz…230MHz 40dB(µV/m) Qpk at 10m 230MHz…1GHz 47dB(µV/m) Qpk at 10m 1…3GHz Do not apply Internal freq. < 108MHz 3…6GHz Conducted emissions IEC55016 Output 150kHz…500kHz 79dB(µV) Qpk 500kHz…30MHz 66dB(µV) Qpk Test Norm Port Severity Conditions P Electrostatic discharge IEC61000-4-2 Case ±8kV Air (isolated parts) B ±6kV Contact (conductive parts) Radiated high frequency IEC61000-4-3 X/Y/Z Axis 20V/m 0.08…1.0GHz M. 80% 1kHz A 10V/m 1.4…2.1GHz M. 80% 1kHz 5V/m 2.1…2.5GHz M. 80% 1kHz 3V/m 5.1…6Ghz M. 80% 1kHz Fast transients IEC61000-4-4 Input ±2kV Tr/Th: 5/50 ns A Output ±2kV Signal ±2kV P ±1kV Surge IEC61000-4-5 Input L to L ±1kV Tr/Th: 1.2/50µs B Input L to P ±2kV Conducted RF IEC61000-4-6 Input 10V Signal 10V P 10V Magnetic field IEC61000-4-8 X/Y/Z Axis 300A/m 0Hz, 16.7Hz, 50/60Hz A Pulse magnetic field IEC61000-4-9 X/Y/Z Axis 300A/m Tr/Th: 6.4/16µs B P= Performance criteria, L= Line, P= PE (Protective Earth)

4.3.7 Relative humidity Up to 95%

5.1.1.3 Temporary DC power supply

From 0.60 to 1.40 Un 0.1s From 1.25 to 1.40 Un 1s without damage

5.1.1.4 Interruptions of voltage supply S1

5.1.1.6 Input ripple factor 10% peak to peak with a DC Ripple Factor of 5 %

5.1.3 Supply change-over 0,6 Un duration 100 ms (without interruptions). Performance criterion A

7.2.7 Input reverse polarity protection By serial diode in the input

10.7 Protective coating for PCB assemblies Class PC2

13.3 Tests list

1 Visual Inspection

2 Performance test

3 Power supply test

4 Insulation test

5 Low temperature storage test

6 Low temperature start-up test

7 Dry heat test

8 Cyclic damp heat test

9 Salt mist test

10 Enclosure protection test (IP code)

11 EMC test

12 Shocks and vibrations test

13 Equipment stress screening test

14 Rapid Temperature variation test

Routine: 24h at 40°C and load 100% Type