885RZXX MARATHON | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 3
Technical content
www.marathonsp.com
885 RZ XX
Replace “xx” with 01 to 12 for number of poles Terminal Block
85 Amps 600 Volts AC/DC
- Line: #4 - #18 AWG Cu
- Load: #4 - #18 AWG Cu Electrical Ratings
- 85 Amps
- 600V per UL 1059 & CSA 22.2 No.158, class B & C requirements
- SCCR of 10,000 A (default for terminal blocks).
- CU7 - 75°C connector terminal rating with copper wire
- Factory & Field Wiring Agency Compliance
- UR - UL Recognized Terminal Block, Evaluated to UL 1059, File No.XCFR2.E62806
- cUR - UL Evaluated to C22.2 No. 158, File No. XCFR8.E62806
- CE compliant to IEC 60947-7-1
- RoHS Compliant Material Information
- Insulator base:
- Thermoplastic
- Flammability rating of insulator base UL94V0
- Insulator base temperature rating: -40°C to 130°C (UL RTI)
- Collar: aluminum, tin (over copper) plated
- Screws: steel, tin plated
- RoHS compliant
www.marathonsp.com REV-C 07/13/2020 Termination Specifications Installation & Accessories
- Mounting (Panel):
- For use with #8 fastener.
- Mounting torque to be determined in end use application not to exceed 20 lbf·in Wire Size T orque Copper Wire Stranding Classes - Number of Conductors Solid Class B Class C 4 16 in. lbs N/A 1 1 6 16 in. lbs N/A 1 1 8 16 in. lbs N/A 1 or 2* 1 or 2* 10 16 in. lbs 1 to 4 * 1 to 4* 1 to 4* 12 16 in. lbs 1 to 4 * 1 to 4* 1 to 4* 14 16 in. lbs 1 to 6 * 1 to 6* 1 to 6* 16 16 in. lbs 1 to 6 * 1 to 6* 1 to 6* 18 16 in. lbs 1 to 8* 1 to 8* 1 to 8* *If using two or more conductors, they must be the same size
- Wire strip length – 9/16”
www.marathonsp.com REV-C 07/13/2020 Drawing Lines DIM “A”±.02 [.38] DIM “B”±.02 [.38]