Technical content

Visit product website  DATA SHEET Type 8805  Ball valve / Butterfly valve with pneumatic rotary actuator Type 8202  pH or redox potential transmitter, ELEMENT design Type 8045  Magnetic inductive Insertion flowmeter Type 8798  Remote sensor for pneumatically actuated process valves Type 2301  Pneumatically operated 2-way Globe Control Valve Type 2300  Pneumatically operated 2-way angle seat control valve ELEMENT Type 2103  2/2-way diaphragm valve with pneumatic stainless steel actuator (Type ELE- MENT) for decentralised automation Type 8619  multiCELL – Multi- channel and multi-func- tion transmitter/controller Standard | EU | en | 2024 - 03 - 07 | 30 Digital electropneumatic Process Controller SideControl

  • Compact and robust design Start-up via the TUNE function of the positioner and process controller Integrated diagnostic functions for valve monitoring Dynamic actuating system with no air consumption in controlled state EtherNet/IP, PROFINET, Modbus TCP, PROFIBUS DP-V1 or Bürkert system bus (büS) The device Type 8793 digital process controller is designed with standardisation according to IEC 60534 1 or VDI/VDE 3845 (IEC 60534 2) for assembly to linear and rotary actuators. The variant with remote position sensor can also be used to control Bürkert process control valves. The process controller processes all standard current and voltage signals and can also be equipped with the fieldbus interface. The actual process value is supplied directly to the device as 4 mA, PT100 or as a frequency signal. The process controller calculates the position setpoint for the subordinated positioner via variance comparison. The parameteri- sation of process and position controllers can be carried out automatically via the Tune function. Operation is simple via the graphical display with keypad or via Bürkert Communicator. The process controller is equipped with diagnostic func- tions to monitor the valve. The diagnostics can be used to monitor the operating conditions of the control valve which makes maintenance decisions predictable and optimises the availability of the plants as required. The pneumatic actuating system can be used equally for single-acting and double-acting actuators. It is characterised by a defined safety response in the event of the failure of the electri- cal or pneumatic auxiliary power and possesses an enormous air capacity range with pressure supply up to 7 bar. Product variants described in the data sheet may differ from the product presentation and description. Type description Can be combined with Type 8793 © Christian Bürkert GmbH & Co. KG, Subject to alteration

2 | 31Visit product website  Table of contents 1. General technical data 4 1.2. Linear remote position sensor (ELEMENT Type 8798) .... 1.3. Rotative remote position sensor (NAMUR) .... 1.4. Position feedback with proximity switches (accessories for retrofitting) ... 2. Approvals and conformities 8 2.2. Conformity ... 2.3. Standards .... 2.4. Explosion protection ... Positioner SideControl Type 8793 2.5. North America (USA/Canada) ... Positioner SideControl Type 8793 Linear position sensor, remote (ELEMENT Type 8798) Rotative position sensor, remote (NAMUR Type 8798) 2.6. Others China Compulsory Certification (CCC) 3. Dimensions 10 3.2. Remote version 3.3. Mounting specification of NAMUR/Remote Version .... NAMUR version Remote version 3.4. ATEX/IECEx version 3.5. Remote position sensor version ... 3.6. Mounting on control valve according to NAMUR ... 4. Device/Process connections 15 PROFIBUS DP Connection EtherNet/IP, PROFINET, Modbus TCP connection Bürkert system bus (büS) connection 5. Performance specifications 23 Process control loop Position control loop Additional software options of process controller SideControl Type 8793 (extract) 5.2. Interface diagram .... Version without fieldbus communication Version with fieldbus communication 6. Product installation 25 NAMUR version Remote version Position feedback with proximity switches 6.2. Combination possibilities with pneumatic process valves ...

3 | 31Visit product website  7. Ordering information 29 7.2. Bürkert product filter 7.3. Ordering chart Process controller SideControl Type

8793 NAMUR version

Process controller SideControl Type 8793, remote version Remote position sensor for remote version of SideControl Type 8793 7.4. Ordering chart accessories .... Standard accessories Accessories SideControl Remote

4 | 31Visit product website  1. General technical data 1.1. Process controller SideControl Type 8793 Product properties Dimensions Further information can be found in chapter “3. Dimensions” on page 10 Material Housing Aluminium, plastic-coated Seal EPDM, NBR, FKM Operation Display Graphic display with backlight and intuitive menu navigation Operating keys Membrane keypad with 4 keys Service interface Connected to PC via USB connection Configuration tool Bürkert Communicator PACTware (only for device versions with PROFIBUS) Commissioning Initialisation positioner/process controller Automatic by P.TUNE function (self-optimization of PID parameters) Status display Optical position indicator (mechanical) Integrated (for NAMUR version) Communication Fieldbus EtherNet/IP, PROFINET, Modbus TCP, PROFIBUS DP-V1 Digital Bürkert system bus (büS) (based on CANopen) Performance data Position sensor Integrated position sensor (NAMUR) Conductive plastic rotary potentiometer External remote position sensor Linear or rotative Measuring range for rotary actuator PROFIBUS Rotation angle: 30°…150° EtherNet/IP, PROFINET, Modbus TCP and büS Rotation angle: 30°…180° Stroke range for linear actuator 3…130 mm, depending on the lever of the attachment kit Electrical data Operating voltage 24 V DC ± Residual ripple Max. 10 Power consumption < W Protection class III according to DIN EN 61140 Input /Output Digital input 1 digital input, 0…5 V = log “0”, 10…30 V = log “1” Digital output 2 digital outputs (optional), galvanically isolated Current limitation 100 mA, output will be synchronised when overloaded Analogue output 1 output (optional) 0/4…20 mA, 0…5/10 V In-/Output data setpoint and actual value Setpoint signal Setpoint setting 0/4…20 mA 0…5/10 V Input resistance 0/4…20 mA: 70 Ω 0…5/10 V: 20 kΩ Actual value signal Setting 4…20 mA 70 Ω input resistance/resolution 12 bit Frequency setting 20 kΩ input resistance, 0…1000 Hz/1 ‰ f reading of input frequency range, input signal > 300 mVss sine, rectangle, triangle Setting Pt 100 Measuring range - 20…+ 220 ºC, resolution < 0.1 ºC Electrical connection Multipole version Screw terminals: M8, M12 according to device version (see connection description) Cable gland version 2x M20 1.5 (cable Ø 6…12 mm) on screw terminals (0.14…1.5 mm²) Remote version 1x M12 1.5 (cable Ø 3…6.5 mm)

5 | 31Visit product website  Pneumatic data Control medium Neutral gases, air, quality class according to ISO 8573 Dust content Class 7 (< µm particle size) Particle density Class 5 (< mg/m3) Pressure dew point Class 3 (<- °C) Oil content Class X (< mg/ m3) Air supply filter Exchangeable Mesh size ~0.1 mm Supply pressure 1.4…7 bar 1.) 2.) Pilot air port Threaded port G ¼ Positioning system Universal air capacity Single and double acting 50 lN/min (at 1.4 bar 2.)) for aeration and ventilation 150 lN/min (at 6 bar 2.)) for aeration and ventilation QNn= 100 lN/min Low air capacity Single acting QNn= 7 lN/min (QNn according to definition at pressure drop from 7 to 6 bar abs) Approvals and conformities Explosion protection Ignition protection class II 3D Ex tc IIIC T135 °C Dc II 3G Ex ec IIC T4 Gc ATEX BVS 16 ATEX E 118 X II 3G Ex ec ic IIC T4 Gc II 3D Ex tc IIIC T135 °C Dc IECEx IECEx BVS 16.0091 X Ex ec ic IIC T4 Gc Ex tc IIIC T135 °C Dc Further information can be found in chapter “2.4. Explosion protection” on page 8 North America (USA/Canada) CSA for Canada and the USA UL 429 (Electrically operated valves) CSA C22.2 No. 139 (Electrically operated valves) Further information can be found in chapter “2.5. North America (USA/Canada)” on page 8 Others China Compulsory Certification (CCC) The products with Ex approval are suitable for import and use for hazardous applications in China. Further information can be found in chapter “2.6. Others” on page 9 Further information can be found in chapter “2. Approvals and conformities” on page 8 Environment and installation Operating conditions Ambient temperature With ATEX/IECEx approval 0…+ Without Ex approval - 10…+ Degree of protection IP65/IP67 according to EN 60529, 4X according to NEMA 250 Standard Operating altitude Up to 2000 m above sea level Installation and mechanical data Mounting variant NAMUR according to IEC 60534 1 resp. VDI/VDE 3845 (IEC 60534 2), remote Installation position As required, display above or laterally Valve actuator (type, size) Rotary and linear actuators according to NAMUR, ELEMENT Type 2301, 2300 (actuator size Ø 70/90/130/225 mm) and CLASSIC (actuator size Ø 175/225 mm) in combination with remote version Adapter kit Further information can be found in chapter “7.4. Ordering chart accessories” on page 31 1.) Supply pressure has to be 0.5…1 bar above the minimum required pilot pressure for the valve actuator . 2.) Pressure data: overpressure to atmospheric pressure

6 | 31Visit product website  1.2. Linear remote position sensor (ELEMENT Type 8798) Note: When mounting the remote positioner away from the actuator, the length of the pneumatic control lines influences the dynamics and accuracy of the position control loop. The length of the control air lines should therefore be as short as possible. Product properties Actual position signal Digital (RS485) Detection range of the sensor 3…45 mm (stroke range of valve spindle) Electrical data Operating voltage 24 V DC ± Protection class III according to DIN EN 61140 Power consumption < 0.3 W Electrical connection Cable gland (cable length) 1x M16 1.5 (cable Ø 5…10 mm) on screw terminals (0.14…1.5 mm²) Connection cable 10 m Approvals and conformities Protection class IP65 and IP67 according to EN 60529, 4X according to NEMA 250 standard Explosion protection Ignition protection class II 3G Ex ec IIC T4 Gc II 3D Ex tc IIIC T135 °C Dc Further information can be found in chapter “2.4. Explosion protection” on page 8 North America (USA/Canada) UL Recognized for the USA and Canada cULus certificate: 238179 Further information can be found in chapter “2.5. North America (USA/Canada)” on page 8 Others China Compulsory Certification (CCC) The products with Ex approval are suitable for import and use for hazardous applications in China. Further information can be found in chapter “2.6. Others” on page 9 Further information can be found in chapter “2. Approvals and conformities” on page 8 Environment and installation Ambient temperature - 25…+ 1.3. Rotative remote position sensor (NAMUR) Note: When mounting the remote positioner away from the actuator, the length of the pneumatic control lines influences the dynamics and accuracy of the position control loop. The length of the control air lines should therefore be as short as possible. Product properties Stroke range when mounted to linear actuator 3…130 mm, depending on the lever of the attachment kit Actual position signal Digital (RS485) Measuring range Rotation angle 30°…180° Electrical data Operating voltage 10…30 V DC Protection class III according to DIN EN 61140 Power consumption < 0.8 W Electrical connection 2 m round cable (shielded) Approvals and conformities Protection class IP65 according to EN 60529 North America (USA/Canada) UL Recognized for the USA and Canada cULus certificate: E226909 Further information can be found in chapter “2.5. North America (USA/Canada)” on page 8 Further information can be found in chapter “2. Approvals and conformities” on page 8 Environment and installation Ambient temperature - 25…+

7 | 31Visit product website  1.4. Position feedback with proximity switches (accessories for retrofitting) Note: The feedback unit possesses 2 proximity switches that can be adjusted independently of each other via switch flags. Product properties Output function 3-wire, normally open contact, PNP Electrical data Electrical connection M12, 4-pin Operating voltage 10…30 V DC Protection class III according to DIN EN 61140 DC-rated current ≤ 100 mA Residual ripple ≤ % Uss Approvals and conformities Degree of protection IP65 and IP67 Further information can be found in chapter “2. Approvals and conformities” on page 8

8 | 31Visit product website  2. Approvals and conformities 2.1. General notes

  • The approvals and conformities listed below must be stated when making enquiries. This is the only way to ensure that the pro duct complies with all required specifications. Not all available versions can be supplied with the below menti oned approvals or conformities. 2.2. Conformity In accordance with the Declaration of Conformity, the product is compliant with the EU Directives. 2.3. Standards The applied standards which are used to demonstrate compliance with the EU Directives are listed in the EU-Type Examination Certificate and/or the EU Declaration of Conformity. 2.4. Explosion protection Positioner SideControl Type 8793 Approval Description Optional: Explosion protection ATEX: BVS 16 ATEX E 118 X II 3G Ex ec ic IIC T4 Gc II 3D Ex tc IIIC T135 °C Dc IECEx: IECEx BVS 16.0091 X Ex ec ic IIC T4 Gc Ex tc IIIC T135 °C Dc 2.5. North America (USA/Canada) Positioner SideControl Type 8793 Approval Description Optional: CSA for Canada and the USA The products are CSA approved for Canada and the USA according to: UL 429 (Electrically operated valves) CSA C22.2 No. 139 (Electrically operated valves) Linear position sensor, remote (ELEMENT Type 8798) Approval Description Optional: UL Listed for the USA and Canada The products are UL Listed for the USA and Canada according to: UL 61010 1 (ELECTRICAL EQUIPMENT FOR MEASUREMENT, CONTROL, AND LABORATORY USE – Part 1: General Requirements) CAN/CSA-C22.2 No. 61010 Rotative position sensor, remote (NAMUR Type 8798) Approval Description Optional: UL Listed for the USA and Canada The products are UL Listed for the USA and Canada according to: Certificate no.: E226909

9 | 31Visit product website  2.6. Others China Compulsory Certification (CCC) Positioner SideControl Type 8793 and linear position sensor, remote (ELEMENT Type 8798) Conformity Description Optional: China Compulsory Certification (CCC) The products with Ex approval are suitable for import and use for hazardous applications in China.

10 | 31Visit product website  3. Dimensions 3.1. NAMUR version Note: Dimensions in mm 7.5 A 109.8 7.5 81.8 A A A 49.9 97.4 144.6 L 98.9 81.9 R A1 P A2 Cable gland (standard) PROFIBUS DP multipole Multipole with binary output Multipole Description L A A1 A2 A3 Standard 171.1 31 30 – – PROFIBUS DP 157.8 36 31 13.5 36.1 Multipole digital outputs 157.6 36 31 13.5 – Multipole 157.6 36 31 – –

11 | 31Visit product website  3.2. Remote version Note: Dimensions in mm A Cable gland 49.9 144.6 L 81.9 R A1 P A2 A Multipole/Bus 452x M4 Description L A A1 A2 A3 A4 A5 Remote cable gland 171.1 31 30 11.5 – – – Remote multipole/bus 157.8 36 31 13.5 36 20 11

12 | 31Visit product website  3.3. Mounting specification of NAMUR/Remote Version Note: Dimensions in mm The rotation angle of the sensor must be within a range of 180°. 1.)

  • When opened up to approx. 50 %, the sensor indicator should be in this position. NAMUR version 180° 1) Ø50 7.5 45° 4x90° 4 x M6 4 x M8 1.) Max. 180° are possible for the EtherNet/IP, PROFINET, Modbus TCP and büS variants, max. 150° for the other variants. Remote version 2x M4

13 | 31Visit product website  3.4. ATEX/IECEx version Note: Dimensions in mm 94.6 111.85 3.5. Remote position sensor version Note: Dimensions in mm Linear position sensor Type 8798 for valve position detection of Bürkert ELEMENT valves and hygienic process valves for the remote SideControl positioner . 99.5 Ø 91 114 17.1 119

14 | 31Visit product website  3.6. Mounting on control valve according to NAMUR Note: Dimensions in mm Rotative position sensor to detect rotary motion of rotary actuators according to NAMUR/IEC 60534 1 and VDI/VDE 3845 (IEC 60534 2) for the remote SideControl positioner. 36.1 46 20 SW 17 40 23.5 5

15 | 31Visit product website  4. Device/Process connections 4.1. Electrical connections Multipole connection Functional earth FE M12 circular connector, 8-pin Operating voltages and diverse signals M8 circular connector, 4-pin Digital outputs M8 socket, 4-pin Actual process value 3 1 1 3 M12 circular plug, 8-pin (setpoint) Pin Pin assignment Outer circuitry/Signal level

1 Setpoint + (0/4…20

mA or 0…5/10 Completely galvanically isolated

2 Setpoint GND 2 GND

3 GND 3 24 V DC ± 10 %

Maximum residual ripple 10 %4 + V 4

5 Digital input + 5 +

0…5 V (log. “0”) 10…30 V (log. “1”)

6 Digital input GND 6 GND

8 Analogue feedback + 8 + (0/4…20 mA or 0…5/10 V)

Completely galvanically isolated

7 Analogue feedback GND 7 GND

M8 socket, 4-pin (only for digital outputs options) Pin Pin assignment Outer circuitry/Signal level

1 Digital outputs 1 1 24 V/0 V, NC/NO Relative to operating voltage GND

(terminal GND)

2 Digital outputs 2 2 24 V/0 V, NC/NO Relative to operating voltage GND

(terminal GND)

3 Digital outputs GND 3 GND

16 | 31Visit product website  Round plug M8, 4-pin (actual process value) Symbols for switch position Location of switches Switch on left Switch on right Input type 1.) Pin Pin assignment DIP switch Outer circuitry 4…20 mA internally supplied 1 + V transmitter supply Switch on the left Transmitter GND I

2 Output from transmitter

3 GND identical with GND operating voltage

4 Bridge according to GND

(GND via 3-wire transmitter) 4…20 mA externally supplied

1 Not assigned

2 Process actual value + 2 4…20 mA

3 Not assigned –

4 Process actual value – 4 GND

2 Clock input + 2 Clock +

3 Clock input – (GND identical with GND

operating voltage) 3 Clock –

4 Not assigned –

3 Clock input – 3 Clock –

Pt 1002 Process actual value 1 (power supply)

3 Process actual value 3 (GND)

4 Process actual value 2 (compensation)

1.) Adjustable via Software

17 | 31Visit product website  Position feedback with proximity switches Note: Accessories for upgrading Proximity switch 1 Proximity switch 2 No. Pin assignment External circuitry/signal level

1 Supply 10…30

10…30 V 10…30 V

2 Switching output (NO)

10…30 V Open/10…30 V

3 GND GND GND

4 Switching output (NO)

10…30 V Open/10…30 V Screw terminal connection +24 V GND 83 + 85 + 31 + 32 – 11 + 12 – 81 + S + S – A B Terminal assignment A Terminal Pin assignment Outer circuitry/Signal level 11 + Setpoint + 11 + + (0/4…20 mA or 0…5/10 Completely galvanically isolated 12 – Setpoint GND 12 – GND 81 + Digital input + 81 + 0…5 V (log. “0”) 10…30 V (log. “1”) Relative to operating voltage GND (terminal GND) V GND Operating voltage + Operating voltage GND V GND

24 V DC ± 10 %

Maximum residual ripple 10

18 | 31Visit product website  Analogue feedback option/digital outputs Terminal Pin assignment Outer circuitry/Signal level 83 + Digital outputs 1 83 +

24 V/0 V, NC/NO

Relative to operating voltage GND (terminal GND) 85 + Digital outputs 2 85 + Relative to operating voltage GND (terminal GND) 31 + Analogue feedback + 31 + + (0/4…20 mA or 0…5/10 V) Completely galvanically isolated 32 – Analogue feedback GND 32 – GND analogue feedback Remote version option in conjunction with remote position sensor Type 8798 Note: For variants without remote version: Terminals A, B, S + and S - not connected Terminal Pin assignment Outer circuitry/Signal level Remote position sensor A Serial interface, A-line A A-line Remote sensor Type 8798 B Serial interface, B-line B B-line S + Sensor supply + S + + S – Sensor supply – S – – Terminal assignments of the process actual value – input Input type 1.) Terminal Pin assignment Outer circuitry 4…20 mA internally supplied Process actual value 1 + V Input Transmitter 1 GND Transmitter GND

3 Bridge according to GND

(GND from 3-conductor transmitter

4 Not assigned

GND GND of operating voltage 4…20 mA externally supplied Process actual value

2 Process actual value + 2 + (4…20 mA)

3 Process actual value – 3 GND

4 Clock input – 4 –

GND GND of operating voltage GND Clock – (GND) Frequency externally supplied Process actual value

3 Not assigned

4 Clock input – 4 Clock –

1 Not assigned 2

Pt 1002 Process actual value 1 (power supply) 1.) Adjustable via software

19 | 31Visit product website  PROFIBUS DP Connection Actual process value 3 1 M12 circular connector, 5-pin (inverse coded, PROFIBUS DP) M12 socket, 5-pin (inverse coded, PROFIBUS DP) Functional earth FE M12 circular connector, 8-pin M8 circular connector, 4-pin Operating voltage, M12 circular plug, 8-pin Pin Pin assignment Outer circuitry/Signal level

2 Not assigned

V Maximum residual ripple 10

5 Digital input +

6 Digital input –

7 Digital outputs 1 (relative to pin 3)

8 Digital outputs 2 (relative to pin 3)

Fieldbus connection, socket/ M12 circular plug, 5-pin Pin Pin assignment Outer circuitry/Signal level

1 VP+

5 Load resistance supply

2 RxD/TxD-N Receive/transmit data -N, A-line

3 DGND Data transfer potential (Ground to 5

4 RxD/TxD-P Receive/transmit data -P, B-line

5 Shielding Shielding/functional earth

20 | 31Visit product website  EtherNet/IP, PROFINET, Modbus TCP connection M12 fieldbus connection (2 Port Ethernet switches) M8 circular connection 4 pin 3 1 1 3 M8 Socket, 4 pin, optional (only by remote version) M12 Circular connection, 8 pin M12 fieldbus connection, D-coded Connection for EtherNet/IP takes place via M12 circular connector , 4-pin, D-coded Pin Description

1 Transmit +

2 Receive +

3 Transmit –

4 Receive –

Operating voltage, M12 circular plug, 8-pin Pin Pin assignment Device side Outer circuitry/Signal level Maximum residual ripple 10 %4 + V 4 Input signal of the control centre (e. g. SPS) 0…5 V (log “0”) 10…30 V (log “1”)

6 Digital input GND 6 GND (identical to pin 3)

Output signal of the control centre (e. g. SPS) (only used with digital outputs option)

7 Digital outputs 1 (relative to pin 3) 7 0…24 V

8 Digital outputs 2 (relative to pin 3) 8 0…24 V

Connection of digital remote position sensor Type 8798, M8 socket, 4-pin (optional) Pin Pin assignment Outer circuitry/Signal level

1 Sensor supply + S + +

2 Sensor supply – S – –

3 Serial interface, A-line A A-line

4 Serial interface, B-line B B-line

21 | 31Visit product website  Bürkert system bus (büS) connection M8 circular connector, 4-pin 3 1 M12 circular connector, 5-pin Earthing function42 1 3 M8 socket, 4-pin, optional (only with remote version) M12 circular connector, 8-pin 1 2 Fieldbus connection M12 x 1 circular plug, 5-pin Pin Cable colour Description

1 CAN Shielding CAN Shielding

3 Black GND/CAN_GND

4 White CAN_H

5 Blue CAN_L

Operating voltage M12 circular plug, 8-pin Pin Pin assignment Device side Outer circuitry/Signal level

3 GND 3

Maximum residual ripple 10 %4 + V Input signal of the control centre (e. g. SPS) 0…5 V (log “0”) 10…30 V (log “1”) Output signal of the control centre (e. g. SPS) (only used with digital outputs option) Connection of digital remote position sensor Type 8798, M8 socket, 4-pin (optional) Pin Pin assignment Outer circuitry/Signal level

22 | 31Visit product website  Connection of analogue remote position sensor, M8 socket, 4-pin (optional) Pin Pin assignment On device side Outer circuitry

1 Potentiometer 1 1

2 Wiper 2

3 Potentiometer 3

M8 circular plug, 4-pin, process actual value (for Type 8793) Input type 1.) Pin Pin assignment DIP switch Outer circuitry 4…20 mA internally supplied 1 + V Transmitter supply Switch on left Transmitter GND I (GND via 3-wire Transmitter) 4…20 mA externally supplied operating voltage) 3 Clock – Pt 1002 Process actual value 1 (power supply) 1.) Adjustable via software

23 | 31Visit product website  5. Performance specifications 5.1. Signal flow diagram Process control loop Process setpoint SP PV Process controller Position control loop Transmitter Process value Process Xd2 CMD Valve opening Position control loop Set-point position value CMD POS Position controller Control system Position measuring systemPosition control loop Valve opening Proportional valve Xd1 B1 PK Additional software options of process controller SideControl Type 8793 (extract) Automatic commissioning of control system Automatic parameterisation of process control loop Automatic or manual characteristics curves selection Setting of seal and maximum stroke threshold respectively Parameterisation of positioner Manual parameterisation of process controller Limitation of stroke range Limitation of manipulating speed Setting of moving direction Configuration of digital input Signal range splitting on several controllers Configuration of analogue or 2 digital outputs Signal fault detection Safety position Code protection Contrast inversion of display Parameterizable diagnostic functions 1.)/digital outputs (option)

24 | 31Visit product website  – Operating-hours counter Path accumulator Position monitoring Process actual value monitoring Graphical display of dwell time density and movement range Monitoring of mechanical end positions in armature 1.) Further diagnostic functions with detailed description can be found in the operating instructions Type 8793 . 5.2. Interface diagram Version without fieldbus communication Input for positon or process setpoint, 4…20mA, 0…20 mA 0…10 V, 0…5 V Digital input Operation Process Controller Input Output Supply Input for process value 4…20 mA, frequency, Pt 100 24 V DC 1.)

2 Digital outputs

24 V PNP 2.) Analogue feedback 2) 4…20mA, 0…20 mA 0…10 V, 0…5 V Initiator 1/Initiator 2 24 V PNP NO 2.) Version with fieldbus communication PROFIBUS DP, EtherNet/IP, PROFINET, Modbus TCP and Bürkert system bus (büS) Bus Operation Process controller PROFIBUS DP EtherNet/IP PROFINET Modbus TCP büS Input Output Suuply Bus 24 V PNP 2.) Input for process- value 4…20mA, frequency, Pt 100 24 V DC 1.) Initiator 1 / Initiator 2 24 V PNP NO 2.) 1.) Operating voltage is supplied with a 3-wire unit independent from the setpoint signal 2.) Alternative options

25 | 31Visit product website  6. Product installation 6.1. Mounting options NAMUR version Note: Positioner with integrated position sensor, installation according to NAMUR/IEC 60534 1 and VDI/VDE 3845 (IEC 60534 The NAMUR version of the SideControl positioner is equipped with an integrated position sensor (linear or rotary). It has a standardised interface for direct attachment to linear actuators according to NAMUR/IEC 60534 1 and VDI/VDE 3845 (IEC 605334 2). Linear actuators Rotary actuators See operating manual Type 8793  See operating manual Type 8793 Description Article no. Mounting kit 787215 Description Article no. Adapter kit 787338 Mounting bracket 770294 Adapter kit for rotary actuators (Article no. 787338) Mounting bracket for rotary actuator (Article no. 770294 4.9 -0.1 8 +0.1 A 107.6 B R34 19.5 R7 C Actuator shaft height A B C [mm] [mm] [mm] [mm] 20 46.5 80 – 30 56.5 80 130 50 76.5 – 130

26 | 31Visit product website  Remote version Note: Dimensions in mm 2 mounting options The SideControl positioner remote version is used to control process control valves in combination with a remote position sensor. The remote position sensor is mounted directly on the valve to detect the valve position. The remote positioner can be mounted on the wall or on a standard rail in a control cabinet. Wall mounting with accessory bracket 120 131.5 196.1 Ø4.7 174 36 8.5 10.5 8.5 Description Article no. Bracket for wall mounting 675715 Mounting on Standard rail Note: Dimensions in mm Adapter can be turned by 90º the standard rail. 36.3 10.3 Description Article no. Holder for standard rail mounting 675702

27 | 31Visit product website  Position feedback with proximity switches Note: Upgrade feature for SideControl NAMUR External position indicator Cover for standard display element Housing cover Connecting external position indicator Description Article no. Position feedback 677218

28 | 31Visit product website  6.2. Combination possibilities with pneumatic process valves Note: Further ordering information can be found in chapter “7.3. Ordering chart” on page 29 Process controller SideControl 8793

8793 NAMUR 8793 Remote 8793 Remote

(IEC 60534 Linear actuators IEC 60534 Rotary actuators VDI/VDE 3845 (IEC 60534 Control valve system Typ 8805 Ball valve/Butterfly valve with pneumatic rotary actuator Typ 8798 Remote sensor for pneumatically actuated process valves Typ 2300 Pneumatically actuated 2-way angle seat control valve ELEMENT Typ 8798 Remote sensor for pneumatically actuated process valves

29 | 31Visit product website  7. Ordering information 7.1. Bürkert eShop Bürkert eShop – Easy ordering and quick delivery You want to find your desired Bürkert product or spare part quickly and order directly? Our online shop is available for you 24/7. Sign up and enjoy all the benefits. Order online now 7.2. Bürkert product filter Bürkert product filter – Get quickly to the right product You want to select products comfortably based on your technical requirements? Use the Bürkert product filter and find suitable articles for your application quickly and easily. Try out our product filter 7.3. Ordering chart Process controller SideControl Type 8793 NAMUR version Note: Mounting according to NAMUR IEC 60534 1 resp. VDI/VDE 3845 (IEC 60534 Further versions are available on request. Communication Electrical connection Analogue feedback

2 Digital

1.) cCSAus ATEX II 3 GD/ IECEx CCC 2.) Article no. Single and double-acting with universal air capacity Without fieldbus communication Cable gland – – – Yes – 317976 – Yes Yes Yes – 317978 Yes Yes Yes Yes – 317977 Yes Yes Yes – Yes 318040 – Yes Yes – Yes 318041 Multipole – – – Yes – 317979 – Yes Yes Yes – 317981 Yes Yes Yes Yes – 317980 PROFIBUS DP-V1 Multipole Via bus – – Yes – 206600 Via bus Yes Yes Yes – 206601 EtherNet/IP Multipole Via bus – Yes Yes – 317930 Via bus Yes Yes Yes – 317931 PROFINET Multipole Via bus – Yes Yes – 317940 Via bus Yes Yes Yes – 317941 Modbus TCP Multipole Via bus – Yes Yes – 317950 Via bus Yes Yes Yes – 317951 Bürkert system bus (büS) Multipole Via bus – Yes Yes – 317960 Via bus Yes Yes Yes – 317961 1.) See “Additional software options of process controller SideControl Type 8793 (extract)” on page 23 2.) CCC (China Compulsory Certificate) for device versions with Ex approval

30 | 31Visit product website  Process controller SideControl Type 8793, remote version Note: Further versions are available on request. Communication Electrical connection Analogue feedback Diagnostics 1.) cCSAus ATEX II 3 GD/ IECEx CCC 2.) Article no. Single-acting with low air capacity for actuator series Type 23xx (Ø70/90 mm) Without fieldbus communication Cable gland – – – Yes – 318015 – Yes Yes Yes – 318013 Yes Yes Yes Yes – 318012 EtherNet/IP Multipole Via bus Yes Yes Yes – 317937 PROFINET Via bus Yes Yes Yes – 317947 Modbus TCP Via bus Yes Yes Yes – 317957 Bürkert system bus (büS) Via bus Yes Yes Yes – 317967 Single and double-acting with universal air capacity for actuator series Type 23xx (Ø130/225 mm) and 27xx (Ø175/225 mm) Without Fieldbus communication Cable gland – – – Yes – 317982 Yes Yes Yes Yes – 317983 – Yes Yes Yes – 317984 Yes Yes Yes – Yes 318042 EtherNet/IP Multipole Via bus Yes Yes Yes – 317934 PROFINET Via bus Yes Yes Yes – 317944 Modbus TCP Via bus Yes Yes Yes – 317954 Bürkert system bus (büS) Via bus Yes Yes Yes – 317964 1.) See “Additional software options of process controller SideControl Type 8793 (extract)” on page 23 2.) CCC (China Compulsory Certificate) for device versions with Ex approval Remote position sensor for remote version of SideControl Type 8793 Product Mounting version Electrical connection cULus ATEX II 3 GD/IECEx CCC 1.) Article no. Mounting on control valves Type 8798 Control valve Type 23xx Cable gland - 10 m round cable Yes – 300730  Cable gland - m round cable – Yes 20003944 Multipole - m round cable Yes – 307956 Control valve Type 27xx Cable gland - m round cable Yes – 211535 Cable gland - m round cable – Yes 226859 Multipole - m round cable Yes – 329888 NAMUR mounting NAMUR (rotative) Cable gland m round cable (extend able to m maximum) Yes – 211536  1.) CCC (China Compulsory Certificate) for device versions with Ex approval

31 | 31Visit product website  7.4. Ordering chart accessories Standard accessories Note: The associated communication software can be downloaded under Type 8793 Description Article no. M12 circular socket with cable, 8-pin, cable length: 5 m, for input and output signals 919267 M8 plug, 4-pin for digital outputs, with solder joints 917131 USB büS interface set 2 (Type 8923) for connection to the Bürkert Communicator software: including büS stick, connection cable to M12 plug, M12 connection cable on micro USB for the büS service interface and Y distributor, cable length: 0.7 m 772551 büS cable extension, M12, cable length: 1 m 772404 büS cable extension, M12, cable length: 3 m 772405 büS cable extension, M12, cable length: 5 m 772406 büS cable extension, M12, cable length: 10 m 772407 Silencer G ¼ 780780 USB interface for serial communication 227093 Software Bürkert Communicator Type 8920 AS-Interface flat cable clamp, M12 outlet, stainless steel outlet 799646 Accessories SideControl NAMUR Note: Further information can be found in chapter “6. Product installation” on page 25 Description Article no. VDI/VDE 3845 stainless steel universal assembly bridge (IEC60534 2) 770294 Attachment kit for stainless steel rotary actuators according to VDI/VDE 3845 (IEC 60534 2) 787338 Attachment kit for linear actuators according to IEC 60534 1 787215 Position feedback with proximity switches (optional upgrade feature) 1.) 677218  1.) External end position feedback for upgrading SideControl NAMUR Accessories SideControl Remote Description Article no. Mounting bracket for stainless steel wall mount (spare part), see “6. Product installation” on page 25 675715 Standard rail assembly kit aluminium/stainless steel, see “6. Product installation” on page 25 675702 Attachment kit for Type 21xx/23xx actuator series, actuator size Ø 70/90/130 mm 679917 Attachment kit for Type 21xx/23xx actuator series, actuator size Ø 225 mm 60025906 Adapter kit remote sensor, control valves Type 27xx, actuator size Ø 175/225 mm 679945 Sensor puck (replacement part) 682240