Technical content

Overview/Product Selection Product Selection Bulletin 700-SC  3 A (resistive) Max. Continuous Load (Output) Current  264V AC, 48V DC or 125V DC Max. Load Voltage Range Options  5…24V DC or 110/220V AC Control (Input) Voltage Options  LED Indicator (Optional) For Input/Logic ON/OFF Status Monitoring  700-HN103, 700-HN104, or 700-HN128 Socket Compatible  Compatible with 700-AT1 or 700-AT2 Timer Module Table Of Contents Approximate Input-to-Output Isolation Method Zero Cross Function LED Indicator Rated Output (Load) Max. Current and Voltage Range Rated Input Control Voltage Cat. No. Factory- stocked Item (Single Pack) Photocoupler Y es Ye s

3 A @100…240V AC 5…24V DC 700-SCZY3Z25 ✔

2 A @ 100…240V AC 100/110V AC 700-SCZY2A1 ✔

200/220V AC 700-SCZY2A2 ✔ Phototriac No 3 A @100…240V AC 24V DC 700-SCTY3Z24 ✔ Photocoupler No 3 A @ 4…48V DC 5…24V DC 700-SCNY3Z25 ✔ Ye s No

3 A @ 100…240V AC 4…24V DC 700-SCZN3Z26 ✔

Phototriac No 24V DC 700-SCTN3Z24 ✔ Photocoupler N/A

3 A @ 4…48V DC 4…24V DC 700-SCNN3Z26 ✔

2 A @ 5…110V DC 5…24V DC 700-SCNN2Z25 ✔

➊ Series B retainer clip must be used with Bulletin 700-SC Description Pkg. Quantity Cat. No. Factory-stocked Item Screw Terminal Socket — Panel or DIN Rail Mounting; Guarded Terminal Construction Order must be in ten or multiples of ten 1 700-HN103 ✔ Screw Terminal Socket – Panel or DIN Rail Mounting. Guarded Terminal Construction 14-blade miniature socket for use with Bulletin 700-SC relays. This socket has coil and contact separation as well as the ability to plug in optional plug in modules (700-A** accessories: LED, Surge Suppression, Timing Modules) 700-HN104 ✔ Screw Terminal Base Socket — Panel or DIN Rail Mounting; Open Style Construction Order must be in multiples of ten 10 700-HN128 ✔ DIN Rail Mounting Pack Standard 35 x 7.5 mm DIN Rail, 1 meter long, 10 rails per package. Order must be for 10 rails or multiples of 10. 10 199-DR1 ✔ Pre-printed identification tags — contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F , R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays. 700-N40 Blank identification tags — contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays. 700-N41 Retainer Clip Secures relay in socket. Order must be for 10 clips or multiples of 10. 10 700-HN114(B)➊✔ ON-Delay Time Module Voltage Range: 12…24V AC/DC used with 700-HN153 socket 1 700-AT1 One Shot Timing Module Voltage Range: 12…24V AC/DC used with 700-HN153 socket 1 700-AT2 Cat. No. 700-HN103 Cat. No. 700-HN104 Cat. No. 700-HN128 Cat No. 199-DR1 Sample Retainer Clips

➊ With constant current input circuit system. SSR impedance varies with a change in input voltage. ➋ Input impedance attains its maximum at the operating voltage. ➌ If the SSR operation is continuous ON/OFF , this value should be reduced by 50%. Refer to “Inrush Current Resistivity” graphs on page 40 for details. ➍ Refer to the following "Load Current Versus Ambient Temperature Characteristics" graphs on page 40 for additional load current details. Control/Input Ratings Cat. No. Rated Control Voltage Operating Control Voltage Range Impedance Control Voltage Levels Pick-up Voltage Drop-out Voltage 700-SCZY3Z25 5…24V DC 4…28V DC 15 mA max. ➊ 4V DC max. 1V DC min. 700-SCZY2A1 100/110V AC 75…125V AC 41 K Ω± 20% 75V AC max. 20V AC min. 700-SCZY2A2 200/220V AC 150…250V AC 72 K Ω ± 20% 150V AC max. 40V AC min. 700-SCTY3Z24 24V DC 19.2…28.8V DC 2 K Ω ± 20% 19.2V DC max. 1V DC min. 700-SCNY3Z25 5…24V DC 4…28V DC 1.5 K Ω + 20%/–10% ➋ 4V DC max. 700-SCZN3Z26 4…24V DC 3…28V DC 15 mA max. ➊ 3V DC max. 700-SCTN3Z24 24V DC 19.2…28.8V DC 2 k Ω ± 20% 19.2V DC max. 700-SCNN3Z26 4…24V DC 3…28V DC 1.5 K Ω + 20%/–10% ➋ 3V DC max.700-SCNN2Z25 5…24V DC Load/Output Ratings Cat. No. Rated Load Voltage Applicable Load Load Voltage Range Continuous Load Current (Resistive) Max. Inrush Current ➌ — — — Min. Max. ➍ — 700-SCZY3Z25 100…240V AC 75…264V AC

0.1 A 3 A

45 A (@50/60 Hz, 1 cycle)

700-SCZY2A1 100…240V AC 0.1 A 2 A700-SCZY2A2 700-SCNN3Z25 4…48V DC 3…52.8V DC 0.1 A 3 A 18 A (10 ms)700-SCNY3Z26 700-SCNN2Z25 5…110V DC 3…125V DC 0.1 A 2 A 10 A (10 ms) Characteristics Cat. No. 700-SCZ…. 700-SCT 700-SCNN3… 700-SCNN2… Load Switching Method/Device Triac Transistor Pick-up Time 1/2 of load power source + 1 ms max. (DC input) 1 ms max 0.5 ms max 0.5 ms max 3/2 of load power source + 1 ms max. (AC input) Drop-out Time 1/2 of load power source + 1 ms max. (DC input) 1/2 of load power source + 1 ms max 2 ms max 2.5 ms max 3/2 of load power source + 1 ms max. (AC input) Output Leakage Current 5 mA max (@ 100 V AC) 10 mA max (@ 200 V AC) 2.5 mA max (@ 100 V AC) 5 mA max (at 200 V AC) 5 mA max (@ 50 V DC) 0.1 mA max (@ 100 V DC) Output VDRM, VCEO (V) 600 600 80 80 Output di/dt (A/uS) 50 50 — — Output dv/dt (V/uS) 250 250 — — Output I2t (A2S) 18 18 — — Output Tj °C Max. 125 125 150 150 Insulation Resistance 100 MΩ min (@ 500V DC) Dielectric Strength 1,500 V AC, 50/60 Hz for 1 minute Vibration Resistance (max.) 10…55 Hz, 1.5 mm double amplitude (10 G) Shock Resistance (max.) 1,000 m/s2 (100 G) Ambient Temperature Operating: -30°C…80°C (-22...176°F) with no icing or condensation Storage: -30°C…100°C (-22...212°F) with no icing or condensation

Specifications, Continued Load Current Versus Ambient Temperature Characteristics Inrush Current Resistivity➊ ➊ Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitiv e inrush current will damage the SSR. Characteristics Standards UL508, CSA C 22.2, CE, VDE Ambient Humidity Operating: 45%…85% (no condensation) Weight Approx. 50 g Ambient temperature (°C) Ambient temperature (°C) Load current (A) Load current (A) Inrush current (A. Peak) Energizing time (ms) Inrush current (A. Peak) Energizing time (ms) Inrush current (A. Peak) Energizing time (ms) 2010 700-SCNN3... 700-SCNY3

Note: Bulletin 700-SC is compatible with the 700-HN103, 700-HN104, and 700-HN128 sockets. All units in millimeters unless otherwise indicated. Dimensions are not intended for manufacturing purposes. ➊ Bulletin 700-SC is compatible with cat. nos. 700-HN103, -HN104, and -HN128 socket. Basic Application Considerations For Bulletin 700-SC Connection For DC Load Switching, Bulletin 700-SC will operate properly if the load is connected to either the positive or negative SSR l oad terminal. High-density Mounting of Multiple SSRs If multiple relays are mounted side by side, be aware that the outer wall of each SSR works as a radiator. The SSR casing serves to dissipate heat. Install the relays so that they are adequately ventilated. If poor ventilation is unavoidable, reduce the load current by half. Protective Component When controlling AC inductive loads, connect an inrush/surge absorbing device (varistor) across the SSR load terminals. If the SSR has built-in surge suppression (Bulletins 700-SE and 700-SH) and additional surge suppression is required, connect the varistor across the terminals of the load device . Select a varistor that meets the conditions of the load voltage outlined in the table below. Note: For additional details applying solid-state relays, refer to pub. number 700-AT001A-EN-E, "Solid-State Relay Application Guide." Document available at www.theautomationbookstore.com. Load Voltage Varistor Voltage Varistor Surge Resistance 100…120V AC 240…270 V 1000 A min.200…240V AC 440…470 V 380…480V AC 820…1000 V Terminal Arrangement/ Internal Connections (Bottom V iew) 8(+) 12(–) – + – + Load (+) (–) Input Load Input voltage Load power supply Note: The plus and minus symbols shown in parentheses are for DC loads. 28 max. 21.5 max. 36.5 max. 42.5 max. Cat, No 700-SC… ➊