700-SH ALLEN-BRADLEY | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 7
Technical content
Overview/Product Selection Product Selection ➊ Maximum load current when mounted on a heat sink Bulletin 700-SH 40 A (resistive) Max. Continuous Load (Output) Current with Heat Sink 264V AC or 528V AC Max. Load Voltage Range Options 5…24V DC, 100…120V AC, 200…240V AC Control Input Voltage LED Indicator for Input/Logic ON/OFF Status Monitoring Built-in Varistor to Absorb Most Surges Protective Cover for Added Safety (Meets VDE 106 Finger Safe Standard) Table Of Contents Approximate Basic Application Input-to-Output Isolation Method Zero Cross Function LED Indicator Rated Output (Load) Max. Current and Voltage Range ➊ Rated Input Control Voltage Cat. No. Factory- Stocked Item (Single Pack) Phototriac Yes Ye s 5…24V DC 700-SH05GZ25 ✔ Photocoupler
5 A @ 24…240V AC 100…120V AC 700-SH05GA12 ✔
200…240V AC 700-SH05GA22 ✔ Phototriac 5…24V DC 700-SH10GZ25 ✔ Photocoupler
10 A @ 24…240V AC 100…120V AC 700-SH10GA12 ✔
200…240V AC 700-SH10GA22 ✔
10 A @ 200…480V AC 5…24V DC 700-SH10HZ25 ✔
Phototriac 5…24V DC 700-SH25GZ25 ✔ Photocoupler
25 A @ 24…240V AC 100…120V AC 700-SH25GA12 ✔
200…240V AC 700-SH25GA22 ✔ Photocoupler 25 A @ 200…480V AC 5…24V DC 700-SH25HZ25 ✔ Phototriac
40 A @ 24…240V AC
5…24V DC 700-SH40GZ25 ✔ 100…120V AC 700-SH40GA12 ✔ Photocoupler 200…240V AC 700-SH40GA22 ✔
40 A @ 200…480V AC 5…24V DC 700-SH40HZ25 ✔
➊ For information regarding selection of the proper heat sink for your application, refer to "Heat Sink Size Vs. Load Current" graph on page 54 or "Load Current Vs. Ambient Temperature Characteristics" on page 55. Description Pkg. Qty Cat. No. Factory-Stocked Item Heat Sink— Panel or DIN Rail Mount ➊ 1 700-S10 ✔ Heat Sink— Panel or DIN Rail Mount ➊ 1 700-S20 ✔ Heat Sink— Panel or DIN Rail Mount ➊ 1 700-S30 ✔ DIN Rail Mounting Pack Standard 35 x 7.5 mm DIN Rail, 1 meter long, 10 rails per package. Order must be for 10 rails or multiples of 10. 199-DR1 ✔ Cat No. 700-S10 Cat No. 700-S20 Cat No. 700-S30 Cat No. 199-DR1
➊ The input impedance is measured at the maximum value of the rated supply voltage. ➋ With a constant current input system, SSR impedance varies with a change in input voltage. ➌ Refer to graphs, “Temperature Characteristics…” and “Must Release Voltage” on page 54 for further details. ➍ When specified heat sink is used. Refer to accessories, page 52 for applicable heat sinks. For more details, refer to graphs “Load Current Vs. Ambient Temperature Characteristics” on page 55, and the “Heat Sink vs. Load Current” graph on page 54. ➎ If the SSR operation is continuous ON/OFF , this value should be reduced by 50%. Refer to “Inrush Current Resistivity” graphs on page 54 for more details. Control/Input Ratings Cat. No. Rated Control Voltage Operating Control Voltage Range Impedance ➊ Control Voltage Levels 700-SH_ _G… Pick-up Voltage Drop-out Voltage 4V DC max. 1V DC min. Load/Output Ratings Cat. No. Applicable Load Rated Load Voltage Load Voltage Range Continuous Load Current (Resistive) Max. Inrush Current➎With Heat Sink (A) ➍ Without Heat Sink (A) ➍ — — Min. Max. Min. Max. 700-SH05G… 24…240V AC 19 …264V AC 0.1 A 5 A 0.1 A 3 A 60 A (@50/60 Hz, 1 cycle) 700-SH10G… 0.1 A 10 A 0.1 A 4 A 150 A (@50/60 Hz, 1 cycle)700-SH10H… 200…480V AC 180…528 VAC 0.2 A 10 A 0.2 A 4 A 700-SH25G… 24…240V AC 19…264V AC 0.1 A 25 A 0.1 A 4 A 220 A (@ 50/60 Hz, 1 cycle)700-SH25H… 200…480V AC 180…528V AC 0.2 A 25 A 0.2 A 4 A 700-SH40G… 24…240V AC 19…264V AC 0.1 A 40 A 0.1 A 6 A 440 A (@ 50/60 Hz, 1 cycle)700-SH40H… 200…480V AC 180…528V AC 0.2 A 40 A 0.2 A 6 A
Specifications, Continued ➊ Cat. No. 700-SH_ _ _HZ25 not CE or TÜV approved. Inrush Current Resistivity➋ ➋ Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitiv e inrush current will damage the SSR. ➌ The heat sink size refers to the combined area of the sides of the heat sink that radiate heat. For example, when a current of 18 A is allowed to flow through the SSR at 40°C, the graph shows that the heat sink size is about 450 cm2. Therefore, if the heat sink is square, one side of the heat sink must be 15 cm (152 x 2 = 450) or longer. Characteristics Cat. No. 700-SH05G, -SH10G, SH25G 700-SH40G 700-SH10H, -SH25H, SH40H Load Switching Method/ Device Triac Thyristor Pick-up Time 1/2 of load power source + 1 ms max. (DC input) 3/2 of load power source + 1 ms max. (AC input) Drop-out Time 1/2 of load power source + 1 ms max. (DC input) 3/2 of load power source + 1 ms max. (AC input) Output ON Voltage Drop 1.6 V (RMS) max 1.8 V (RMS) max Output Leakage Current 5 mA max (at 100V AC) 10 mA max. (@ 200V AC) 10 mA max (at 200V AC) 20 mA max. (@ 400V AC) Output VDRM, VCEO (V) 600 600 1200 Output di/dt (A/uS) -SHO5G = 100, -SHO10G, -SH25G= 50 50 100 Output dv/dt (V/uS) -SHO5G = 200, -SHO10G, -SH25G= 100 100 300 Output I2t (A2S) -SHO5G = 24.5, -SHO10G=112.5 -SH25G= 260 1260 260, SH40 = 1800 Output Tj °C Max. 125 Insulation Resistance 100 MΩ min (at 500 VDC) Dielectric Strength 2,500V AC, 50/60 Hz for 1 minute Vibration Resistance (max.) 10…55 Hz, 1.5 mm double amplitude (10 G) Shock Resistance (max.) 1,000 m/s2 (100 G) Ambient Temperature Operating: -30°C…80°C (-22°F…176°F) with no icing or condensation Storage: -30°C…100°C (-22°F…212°F) with no icing or condensation Ambient Humidity Operating: 45%…85% (no condensation) Standards ➊ UL508, CSA C22.2, CE, TÜV Weight Approx. 60g Approx. 70g Approx. 80g
Specifications, Continued Load Current vs. Ambient Temperature Characteristics➊➋ ➊ For the above 5 graphs, the line “with iron plate measuring 100 x 100 x 0.8” means the SSR is mounted directly to an iron plate of at least this size. ➋ All graphs assume conductive grease is being used. Refer to page 56 for details of using conductive grease.
Mounting Considerations➊➋➌➍➎ All units are in millimeters unless otherwise indicated. Dimensions are not intended for manufacturing purposes. ➊ The proper mounting orientation of the heat sink is so the heat fins run perpendicular to the floor (vertical) to maximize vent ilation flow. ➋ If the fins do not run perpendicular to the floor, a 30% current derating is required. ➌ When attaching a heat sink to Bulletin 700-SH, apply heat conductive grease on the heat sink to maximize heat transfer between the SSR and the heat sink. Recommended types: Silicon based, Toshiba YG6240; Non-silicon based, AOS company type 53300. Heat Sinks➏ ➐ ➐ Heat sink weight: cat. nos. 700-S10 = 200 g, 700-S20 = 400 g, 700-S30 = 560 g 13.8 47.6±0.2 Two, 4.3-dia. or M4 holes Load Input (-) (+) Load power supply Load 25 max. 27 max. 4.5 dia. Four, M4 x 8 screws 4.5 43 max. 58 max. 47.5 44 Operating indicator Mounting Holes Terminal Arrangement/ Internal Connections (Top View) Cat. No. 700-SH05… 47.6±0.2 Two, 4.3-dia. or M4 holes 13.8 25 max. 27 max. 58 min.47.5 44 4.5 dia. Two, M5 x 12 screws Two, M 4 x 8 4.5 43 max. Operating indicator Mounting Holes Cat. No. 700-SH40 4.6 dia. Two, M3 holes Two, M4 holes 5.647.6 77 max. 90±0.3 100 max. 35 30.5 0.3 44 max. 30 5 4.56 47 max. Two, 3.2-dia. holes 35±0.2 90±0.4 Two, 4.4-dia. or M4 holes 51 max. Cat. No. 700-S10 Mounting Holes 4.6 dia. Two, M3 holes Two, M4 holes 35 30.5±0.3 47.6 77 max. 90±0.3 100 max. 5.6 3071 max. 100 max. 4.5 75 max. Two, 3.2-dia. holes 35±0.2 90±0.4 Two, 4.4-dia. or M4 holes 28 13 Mounting Holes Cat. No. 700-S20 4.6 dia. 47.6 77 max. 5.6 100 max. 100 max. 5 4.5 30100 max. 90±0.3 Two, 3.2-dia. holes 104 max. 35±0.2 90±0.4 Two, 4.4-dia. or M4 holes 56±0.3 1328 Three, holes Mounting Holes Cat. No. 700-S30
Basic Application Considerations Load Connection For an AC load, use a power supply rated at 50 or 60 Hz. The maximum operating frequency is 10 Hz. The Bulletin 700-SH has a built-in varistor for surge/inrush protection of AC loads. If additional suppression is required, con nect an external varistor across the load device terminals. Select a varistor which meets the load voltage condition outlined in the table below . Zero Cross Function A SSR with a zero cross function operates when an AC load voltage reaches the zero point or its vicinity. This reduces clicking noises when the load is switched, and minimizes the influence of an inductive load, such as a lamp, heater, or motor, on the power supply because the i nrush current of the load is reduced. This can also minimize the scale of the inrush current protection circuit. At a low applied voltage, such as 24V AC, the load current is not fully supplied. When the unit is switched ON, the voltage required to power the unit deprives the output signal of the necessary voltage level and thus creates loss time. The lower the load voltage is, the greater the loss time is. This condition, however, will not create any serious problems. For a DC inductive load, a diode should be connected parallel to the load to absorb the counter electromotive force (OFF) of the load. Note: For additional details when using Solid-State Relays, refer to pub. 700-AT001A--EN-E, “Solid-State Relay Application Guide" available at www.theautomationbookstore.com. Load Voltage Varistor Voltage Varistor Surge Resistance 100…120V AC 240…270 V 1000 A min.200…240V AC 440…470V 380…480V AC 820…1000V Output (load voltage) Input ON OFF Loss time SSRInput Load Load power supply