61C MSYSTEM | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

MODEL: 61C 61C SPECIFICATIONS ES-6627 Rev.8 Page 1/4 http://www.m-system.co.jp/ Field Network Modules 61-UNIT Series ANALOG I/O MODULE (CC-Link) Functions & Features

  • Interfacing analog I/O signals from/to Mini-M, Pico-M and other signal conditioner modules with CC-Link
  • Saving power and I/O wiring inside an instrumentation panel 123 4567890 123 4567890 123 4567890 (1.97) 115 (4.53) 100 (3.94) mm (inch) MODEL: 61C-[1][2]-[3][4]

ORDERING INFORMATION

  • Code number: 61C-[1][2]-[3][4] Specify a code from below for each [1] through [4]. (e.g. 61C-161-K/Q)
  • Specify the specification for option code /Q (e.g. /C01) [1] NO. OF CHANNELS 04: 4 points 08: 8 points 16: 16 points [2] I/O TYPE 1: Input 2: Output 3: Input/output (Select 16 for no. of channels) (8 points for input, 8 points for output) (Use Installation Base model: M8BS2-164) [3] POWER INPUT AC Power K: 85 – 132 V AC (Operational voltage range 85 – 132 V, 47 – 66 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) (Specify power suffix code R (24 V DC) when the 61C is to be combined with the M8BS2.) [4] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating

RELATED PRODUCTS

  • Installation Base (model: M2BS2)
  • Installation Base (model: M8BS2) PACKAGE INCLUDES...
  • Terminating resistor (110 Ω, 0.5 W) GENERAL SPECIFICATIONS Construction: Plug-in Connection CC-Link: Euro type connector terminal (applicable wire size: 0.2 to 2.5 mm2, stripped length 7 mm) I/O: Via Installation Base (model: MxBS2) Power input: Via Installation Base (model: MxBS2) Housing material: Flame-resistant resin (black) Isolation: I/O to CC-Link to power Power indicator: Green LED turns on with power supplied. CC-Link COMMUNICATION CC-Link: Conforms to Version 1.10 Station type: Remote device station Station No. setting: Rotary switch; 1 – 64 Number of occupied stations: 61C-04x: 1 station 61C-08x: 2 stations 61C-161: 4 stations 61C-162: 4 stations 61C-163: 2 stations Remote I/O (RX, RY) is fixed to 32 points. Baud rate setting: Rotary switch (156kbps(factory setting), 625kbps, 2.5Mbps, 5Mbps, 10Mbps) Transmission cable: Approved for CC-Link L RUN indicator: Red LED turns on in an normal condition. L ERR. indicator: Red LED turns on or flashes in an abnormality; off with wire breakdown.

MODEL: 61C 61C SPECIFICATIONS ES-6627 Rev.8 Page 2/4 http://www.m-system.co.jp/ SD indicator: Red LED turns on when transmitting. RD indicator: Red LED turns on when receiving. INPUT SPECIFICATIONS ■ Analog Input Input range: 1 – 5 V DC Input resistance: ≥ 1 MΩ (Each input must be isolated by signal conditioners. Non- isolated modules such as M2BW and M8BW are not usable.) A/D conversion Moving averaging: 4 samples Sampling rate: 160 ms A/D conversion output: Signed binary Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements. Overall range is represented by hexadecimal FA24 – 2CEC 0 1 2 3 4 5 6 7 8 9101112131415 RWr n+0 SIGN BIT INPUT 1 A/D CONVERSION DATA RWr n+1 SIGN BIT INPUT 2 A/D CONVERSION DATA RWr n+2 SIGN BIT INPUT 3 A/D CONVERSION DATA RWr n+3 SIGN BIT INPUT 4 A/D CONVERSION DATA RWr n+7 SIGN BIT INPUT 8 A/D CONVERSION DATA RWr n+11 SIGN BIT INPUT 12 A/D CONVERSION DATA RWr n+15 SIGN BIT INPUT 16 A/D CONVERSION DATA RWr n+0 through RWr n+3 for 4 inputs. RWr n+0 through RWr n+7 for 8 inputs or inputs of 16-input/output. RWr n+0 through RWr n+15 for 16 inputs. ■ A/D CONVERSION DATA OUTPUT SPECIFICATIONS ■ Analog Output Output range: 1 – 5 V DC Load resistance: 20 kΩ minimum (Output must be isolated with signal conditioners. When the transmission line is open, the last value sampled before failure is held. Non-isolated modules such as M2BW and M8BW are not usable. ) D/A conversion input: Signed binary Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements. Overall range is represented by hexadecimal FA24 – 2CEC 0 1 2 3 4 5 6 7 8 9101112131415 RWw n+0 SIGN BIT OUTPUT 1 D/A CONVERSION DATA RWw n+1 SIGN BIT OUTPUT 2 D/A CONVERSION DATA RWw n+2 SIGN BIT OUTPUT 3 D/A CONVERSION DATA RWw n+3 SIGN BIT OUTPUT 4 D/A CONVERSION DATA RWw n+7 SIGN BIT OUTPUT 8 D/A CONVERSION DATA RWw n+11 SIGN BIT OUTPUT 12 D/A CONVERSION DATA RWw n+15 SIGN BIT OUTPUT 16 D/A CONVERSION DATA RWw n+0 through RWw n+3 for 4 outputs. RWw n+0 through RWw n+7 for 8 outputs or outputs of 16-input/output. RWw n+0 through RWw n+15 for 16 outputs. ■ D/A CONVERSION DATA INSTALLATION Power consumption

  • AC: Approx. 4 VA
  • DC: Approx. 4 W (160 mA) Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Installation Base (model: MxBS2) Weight: 250 g (0.55 lb) PERFORMANCE in percentage of span A/D conversion: ±0.1 % D/A conversion: ±0.1 % Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Permissible power failure duration: ≤ 10 msec. Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (I/O to CC-Link to power)

MODEL: 61C 61C SPECIFICATIONS ES-6627 Rev.8 Page 3/4 http://www.m-system.co.jp/ EXTERNAL VIEW L RUN PU-2 B RATE STATION NO. L ERR. SD RD PWR 4321 9 8 76 5 4321 9 8 76 5 4321 9 8 76 X10 E F D C B A A: Modular jack for factory calibration B: Power LED C: Station No. Setting D: Baud rate Setting E: Status indicator LED F: Euro type connector terminal for CC-Link COMMUNICATION CABLE CONNECTIONS DA DB DG SLD FG MASTER UNIT DA DB DG SLD FG 61C DA DB DG SLD FG I/O UNIT TERMINATOR blue white yellow EXTERNAL DIMENSIONS unit: mm (inch) (1.50) (.47) 80 (3.15) 100 (3.94) 2–M3 SCREWS

MODEL: 61C 61C SPECIFICATIONS ES-6627 Rev.8 Page 4/4 http://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM I / O CPU CC-Link INTERFACE SERIAL TRANSMISSION LINE Modular Jack for Factory Calibration MODULAR JACK ROTARY SW INDICATOR LEDDA DB DG SLD FG A / D or D / A Conv. I/O & POWER CONNECTOR To Installation Base To Other CC-Link Devices Terminator *Attach the terminating resistor when the module is at the termination of a transmission line. Specifications are subject to change without notice.