60D MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
MODEL: 60D 60D SPECIFICATIONS ES-6604 Rev.15 Page 1/4 https://www.m-system.co.jp/ Field Network Modules 60-UNIT Series ANALOG I/O MODULE (DeviceNet) Functions & Features
- Interfacing analog I/O signals from/to 10-RACK or 18-RACK modules with DeviceNet
- Saving power and I/O wiring inside an instrumentation panel (2.83) (3.15) mm (inch) 153 (6.02) MODEL: 60D-[1][2]-[3][4]
ORDERING INFORMATION
- Code number: 60D-[1][2]-[3][4] Specify a code from below for each of [1] through [4]. (e.g. 60D-161-K/Q)
- Specify the specification for option code /Q (e.g. /C01/S01) [1] NO. OF CHANNELS 04: 4 points 08: 8 points 16: 16 points [2] I/O TYPE 1: Input 2: Output [3] POWER INPUT AC Power K: 85 – 132 V AC (Operational voltage range 85 – 132 V, 47 – 66 Hz) (CE not available) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [4] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel
RELATED PRODUCTS
- Special cable (model: MCN34)
- Programming Unit (model: PU-2x) GENERAL SPECIFICATIONS Construction: Plug-in Connection DeviceNet: Euro type connector terminal (applicable wire size: 0.2 to 2.5 mm2, stripped length 7 mm) I/O: 34-pin connector (OMRON XG4A-3434) Power input: M3.5 screw terminal Screw terminal: Chromated steel (standard) or stainless steel Housing material: Flame-resistant resin (black) Isolation: I/O to DeviceNet to power to FG1 Power indicator: Green LED turns on with power supplied. DeviceNet COMMUNICATION Transmission cable: Approved for DeviceNet Node address setting: DIP switch; 00 – 63 Baud rate setting: DIP switch MS (Module Status) indicator: Bi-color (green/red) LED indicates device status. NS (Network Status) indicator: Bi-color (green/red) LED indicates status of the communication link. INPUT SPECIFICATIONS ■ Analog Input Input range: 1 – 5 V DC Input resistance: ≥ 1 MΩ 10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable. A/D conversion output: 16-bit binary Signal range 0 – 100 % is converted into hexadecimal 0000 – 1770 (0 – 6000). -15 to 0 % is represented by 2’s complements. Overall range is represented by hexadecimal FC7C – 1AF4
MODEL: 60D 60D SPECIFICATIONS ES-6604 Rev.15 Page 2/4 https://www.m-system.co.jp/ Note: In the firmware version 3.00 or later, analog input range 0 – 100% can be converted into hexadecimal 0000 – 2710 (0 – 10000). In addition, negative values of analog input range -15 to 0% can be converted into signed absolute values. Refer to the instruction manual for details.
- Input Connector Pin Assignment PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT
1 Input 1 2 COM
3 Input 2 4 COM
5 Input 3 6 COM
7 Input 4 8 COM
9 Input 5 10 COM
11 Input 6 12 COM
13 Input 7 14 COM
15 Input 8 16 COM
17 Input 9 18 COM
19 Input 10 20 COM
21 Input 11 22 COM
23 Input 12 24 COM
25 Input 13 26 COM
27 Input 14 28 COM
29 Input 15 30 COM
31 Input 16 32 COM
33 No connection 34 No connection
Input 1 – 4 for 4 points, 1 – 8 for 8 points. OUTPUT SPECIFICATIONS ■ Analog Output Output must be isolated with signal conditioners. When the transmission line is open, the last value sampled before failure is held. Output range: 1 – 5 V DC Load resistance: 20 kΩ minimum 10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable. D/A conversion output: 16-bit binary Signal range 0 – 100 % is converted into hexadecimal 0000 – 1770 (0 – 6000). -15 to 0 % is represented by 2’s complements. Overall range is represented by hexadecimal FC7C – 1AF4 Note: In the firmware version 3.00 or later, analog output range 0 – 100% can be converted into hexadecimal 0000 – 2710 (0 – 10000). In addition, negative values of analog output range -15 to 0% can be converted into signed absolute values. Refer to the instruction manual for details. w Output Connector Pin Assignment PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT
1 Output 1 2 COM
3 Output 2 4 COM
5 Output 3 6 COM
7 Output 4 8 COM
9 Output 5 10 COM
11 Output 6 12 COM
13 Output 7 14 COM
15 Output 8 16 COM
17 Output 9 18 COM
19 Output 10 20 COM
21 Output 11 22 COM
23 Output 12 24 COM
25 Output 13 26 COM
27 Output 14 28 COM
29 Output 15 30 COM
31 Output 16 32 COM
Output 1 – 4 for 4 points, 1 – 8 for 8 points. INSTALLATION Power consumption
- AC: Approx. 4 VA
- DC: Approx. 4 W (160 mA) Supply voltage to network: 11 – 25 V DC supplied through the network terminal block Supply current to network: 60 mA max. @ 24 V Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Surface or DIN rail Weight: 450 g (0.99 lb) PERFORMANCE in percentage of span A/D conversion: ±0.1 % D/A conversion: ±0.1 % Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Permissible power failure duration: ≤ 10 msec. Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (input or output to DeviceNet to power)
2000 V AC @ 1 minute (input or output or DeviceNet or
power to FG1) STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive
MODEL: 60D 60D SPECIFICATIONS ES-6604 Rev.15 Page 3/4 https://www.m-system.co.jp/ EXTERNAL VIEW MS NS CN1 PWR I/O Connector Euro Type Connector Terminal for DeviceNet NA1 NA0 NA2 NA3 NA4 NA5 DR0 DR1 ON Node Address Setting Baud Rate Setting NS Indicator LED MS Indicator LED Power LED PU-2x Modular Jack EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) (.55) 38 (1.50) 80 (3.15) (.79) CLAMP (top & bottom) DIN RAIL 35mm wide
- When mounting, no extra space is needed between units. 80 (3.15) 60 (2.36) 72 (2.83) 7.8 (.31) 2–4.5 (.18) dia. MTG HOLE 25 (.98) deep 14–M3.5 SCREW 12 5614 11 110 15
MODEL: 60D 60D SPECIFICATIONS ES-6604 Rev.15 Page 4/4 https://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Note: In order to improve EMC performance, bond the FG1 terminal to ground. Caution: FG1 terminal is NOT a protective conductor terminal. A / D or D / A Conv. I / O CPU DeviceNet Comm. CPU SERIAL TRANSMISSION LINE PU-2x MODULAR JACK U(+) V(–) POWER FG1 8 COMMUNICATION MODULE I/O CONNECTOR DIP SW INDICATOR LEDV+ CAN_H Drain CAN_L To Other DeviceNet Devices To 10-RACK, 18-RACK etc. ■ CABLE IDENTIFICATION The following table defines wire insulation colors and designations. The terminal block is labeled also in the same colors so that the correct assignment can be confirmed. COLOR DESIG. DESCRIPTION black V – Power (–) blue CAN_L Signal Low bare Drain Shield white CAN_H Signal High red V + Power (+) Specifications are subject to change without notice.