60ACMEB GAPTEC | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

GAPTEC-Electronic GmbH & Co. KG sales@gaptec-electronic.com – www.gaptec-electronic.com Page 1 of 4 60ACMEB – Rev. 2017-1.0 Specifications subject to change without notice. Approval Model* Power [W] Output voltage [V] Output current [mA, max] Capacitive Load [µF, max] Efficiency [@230VAC, %, typ] UL/CE 60ACMEB_05S4 60 5.1 10000 10000 86 UL/CE 60ACMEB_09S4 60 9 6666 5000 87 UL/CE 60ACMEB_12S4 60 12 5000 5000 88 UL/CE 60ACMEB_15S4 60 15 4000 4000 86 UL/CE 60ACMEB_24S4 60 24 2500 2000 87 * Add suffix CM for Chassis mounting with screw terminals (f.ex. 60ACMEB_05S4CM), see different package measurements. Add suffix DR for Din-Rail mounting (f.ex. 60ACMEB_05S4DR). 60ACMEB Series 60W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated Universal input: 90~264VAC Regulated output, low ripple and noise High efficiency up to 88% Plastic case, meets UL94V-0 Short circuit protection (SCP) Output power protection (OPP) Over voltage protection (OVP) Meet EN60950, UL60950 Mounting: PCB Mounting & Chassis Mounting with Screw Terminals Meets EN60601-1, ANSI/ AAMI ES60601-1 standards (2xMOOP) UL 60950-1 (pending) AC-DC Converter 60 Watt The 60ACMEB series is a compact size power converter offered by Gaptec. It features universal input voltage, taking both DC and AC input voltage, low power consumption, high efficiency, high reliability, safer isolation. It offers good EMC performance, meets IEC/EN61000-4, CISPR22/EN55022, UL60950 and EN60950 standards, and is widely used in medical instrumentation and critical applications in commercial and industrial electronic equipment. Input specifications Input voltage range 90-264 VAC; 120-370 VDC Input frequency 47~440Hz Input current 115VAC

  • 1.5A (max) 230VAC
  • 1A (max) Inrush current (<2ms, cold start) 115VAC
  • 55A (typ) 230VAC
  • 95A (typ) Leakage current < 0.1mA/264VAC (touch current) Recommended external fuse
  • 3.15A • slow-blow (pending) Example: 60ACMEB_05S4 60= 60Watt; AC= AC-DC; MEB= series; 5Vout; S= Single Output; 4= 4kVAC Note: 1. This product is not designed for use in critical life support systems, equipment used in hazardous environment, nuclear control systems or other such applications which necessitate specific safety and regulatory standards other the ones listed in this datasheet. 2. Safety approvals cover frequency 47-63 Hz. 3. That “natural convection” is about 20LFM but is not equal to still air (0 LFM). 4. It‘s recommended to add Varistor 14S471K at L / N input side in parallel. 5. All specifications valid at normal input voltage, full load and +25°C after warm- up time unless otherwise stated. Output specifications Item Test conditions Min Typ Max Units Output wattage • 60ACMEB_05S4
  • Others W W Output voltage accuracy Full load ±2 % Line regulation 0.5 % Load regulation 1% to 100% load
  • 60ACMEB_05S4/ 60ACMEB_09S4
  • Others 1.5 Ripple & noise* • 60ACMEB_05S4/ 60ACMEB_09S4
  • Others 100 mV 1% of Vout Hold-up time full load 10 ms * Measured at 20MHz of bandwidth with 0.1uF & 47uF parallel capacitor. Protection specifications Short circuit protection Protection type: Automatic recovery Over-voltage protection Protection type: Zener diode clamp Over-power protection Protection type: Hiccup model, auto recovery

GAPTEC-Electronic GmbH & Co. KG sales@gaptec-electronic.com – www.gaptec-electronic.com Page 2 of 4 60ACMEB – Rev. 2017-1.0 Specifications subject to change without notice. 60ACMEB Series 60W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated Common specifications Operating temperature range -40°C ~ +80°C (with derating) Power derating temperature range 55°C ~ 70°C: 3.75%/°C Storage temperature range -40°C ~ +90°C Case temperature range Under 115VAC 73°C, others 80°C Humidity (non-condensing) 95% MAX Cooling Free air convection Temperature coefficient ±0.05%/°C I/O-isolation voltage 4000VAC Altitude during operation 5000m Atmospheric pressure 70kPa to 106kPa EMC / EMI / Conducted and radiated EMI EN55011 class B (Radiation Class A for 60ACMEB_S4CM series) EMC / EMS / ESD IEC/EN 61000-4-2 Contact ±4KV / Air ±8KV perf. Criteria B EMC / EMS / Radiated Immunity IEC/EN 61000-4-3 10V/m perf. Criteria A EMC / EMS / Fast Transient IEC/EN 61000-4-4 ±2kV perf. Criteria B EMC / EMS / Surge IEC/EN 61000-4-5 ±1KV perf. Criteria B EMC / EMS / Conducted immunity IEC/EN 61000-4-6 10Vr.m.s perf. Criteria A EMC / EMS / PFMF IEC/EN 61000-4-8 30A/m perf. Criteria A EMC / EMS / Dips IEC/EN 61000-4-11 30% / 10ms perf. Criteria B EMC / EMS / Interruption EN61000-4-11 >95% 5000ms Safety standards IEC60950, EN60950, UL60950 Safety approvals cUL / UL Standard: UL 60950-1, CAN/CSA C22.2 No. 60950-1-07 ANSI/AAMI ES60601-1 (2005 + C1:09 + A2:10), CAN/CSA-C22.2 No. 60601-1 (2008), 2 x MOPP CB Standard: IEC 60950-1:2005 (2nd Edition) + Am 1:2009 + Am 2:2013 IEC 60601-1:2005 (3rd Edition) + CORR. 1 (2006) + CORR. 2 (2007) + AM1 (2012) or IEC 60601-1 (2012 reprint), 2 x MOPP Case material UL94V-0 MTBF 200,000 h~400,000 h @25°C Package 89.0 x 63.5 x 27.0 mm Weight 260g Typical characteristics Derating graphs Power derating

GAPTEC-Electronic GmbH & Co. KG sales@gaptec-electronic.com – www.gaptec-electronic.com Page 3 of 4 60ACMEB – Rev. 2017-1.0 Specifications subject to change without notice. 60ACMEB Series 60W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated Block diagram Mechanical dimensions Note: Unit: mm[inch] General tolerances: ±0.50mm [±0.020inch] PIN Single

1 AC IN (L)

2 AC IN (N)

4 NO PIN

6 NO PIN

7 NO PIN

GAPTEC-Electronic GmbH & Co. KG sales@gaptec-electronic.com – www.gaptec-electronic.com Page 4 of 4 60ACMEB – Rev. 2017-1.0 Specifications subject to change without notice. 60ACMEB Series 60W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated Chassis mounting with screw terminals PIN Single

1 NO CONNECT

2 AC IN (L)

3 AC IN (N)

5 NO CONNECT

7 NO CONNECT

8 NO CONNECT