3RV1011-1JA15 SIEMENS | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 6
Technical content
Circuit breaker size S00 for motor protection, CLASS 10 A-release 7...10 A N release 130 A Screw terminal Standard switching capacity with transverse auxiliary switch 1 NO+1 NC product brand name SIRIUS product designation Circuit breaker design of the product For motor protection product type designation 3RV1 General technical data size of the circuit-breaker S00 size of contactor can be combined company-specific S00 product extension auxiliary switch Yes power loss [W] for rated value of the current
- at AC in hot operating state 9.25 W
- at AC in hot operating state per pole 3.1 W insulation voltage with degree of pollution 3 at AC rated value 690 V surge voltage resistance rated value 6 kV mechanical service life (switching cycles)
- of the main contacts typical 100 000
- of auxiliary contacts typical 100 000 electrical endurance (switching cycles) typical 100 000 reference code according to IEC 81346-2 Q Substance Prohibitance (Date) 01/01/2013 Ambient conditions installation altitude at height above sea level maximum 2 000 m ambient temperature
- during operation -20 ... +60 °C
- during storage -50 ... +80 °C
- during transport -50 ... +80 °C relative humidity during operation 10 ... 95 % Main circuit number of poles for main current circuit 3 adjustable current response value current of the current-dependent overload release 7 ... 10 A operating voltage
- rated value 20 ... 690 V
- at AC-3 rated value maximum 690 V
- at AC-3e rated value maximum 690 V operating frequency rated value 50 ... 60 Hz operational current rated value 10 A operational current
- at AC-3 at 400 V rated value 10 A
- at AC-3e at 400 V rated value 10 A operating power
- at AC-3 3RV10111JA15 Page 1/6 10/24/2022 Subject to change without notice © Copyright Siemens
— at 230 V rated value 2.2 kW — at 400 V rated value 4 kW — at 500 V rated value 5.5 kW — at 690 V rated value 7.5 kW
- at AC-3e — at 230 V rated value 2.2 kW — at 400 V rated value 4 kW — at 500 V rated value 5.5 kW — at 690 V rated value 7.5 kW operating frequency
- at AC-3 maximum 15 1/h
- at AC-3e maximum 15 1/h Auxiliary circuit design of the auxiliary switch transverse number of NC contacts for auxiliary contacts 1
- note 1 number of NO contacts for auxiliary contacts 1
- note 1 number of CO contacts for auxiliary contacts 0 operational current of auxiliary contacts at AC-15
- at 24 V 2 A
- at 110 V 2 A
- at 120 V 2 A
- at 125 V 2 A
- at 230 V 0.5 A operational current of auxiliary contacts at DC-13
- at 24 V 1 A
- at 60 V 0.15 A Protective and monitoring functions product function
- ground fault detection No
- phase failure detection Yes trip class CLASS 10 design of the overload release thermal breaking capacity maximum short-circuit current (Icu)
- at AC at 240 V rated value 100 kA
- at AC at 400 V rated value 50 kA
- at AC at 500 V rated value 3 kA
- at AC at 690 V rated value 2 kA breaking capacity operating short-circuit current (Ics) at AC
- at 240 V rated value 100 kA
- at 400 V rated value 13 kA
- at 500 V rated value 3 kA
- at 690 V rated value 2 kA response value current of instantaneous short-circuit trip unit 130 A UL/CSA ratings full-load current (FLA) for 3-phase AC motor
- at 480 V rated value 10 A
- at 600 V rated value 10 A yielded mechanical performance [hp]
- for single-phase AC motor — at 110/120 V rated value 0.5 hp — at 230 V rated value 1.5 hp
- for 3-phase AC motor — at 200/208 V rated value 2 hp — at 220/230 V rated value 3 hp — at 460/480 V rated value 5 hp — at 575/600 V rated value 7.5 hp contact rating of auxiliary contacts according to UL C300 / R300 Short-circuit protection product function short circuit protection Yes 3RV10111JA15 Page 2/6 10/24/2022 Subject to change without notice © Copyright Siemens
design of the short-circuit trip magnetic design of the fuse link
- for short-circuit protection of the auxiliary switch required fuse gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A) design of the fuse link for IT network for short-circuit protection of the main circuit
- at 240 V gL/gG 80 A
- at 400 V gL/gG 63 A
- at 500 V gL/gG 50 A
- at 690 V gL/gG 50 A Installation/ mounting/ dimensions mounting position any fastening method screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715 height 90 mm width 45 mm depth 75 mm required spacing
- for grounded parts at 400 V — downwards 20 mm — upwards 20 mm — at the side 9 mm
- for live parts at 400 V — downwards 20 mm — upwards 20 mm — at the side 9 mm
- for grounded parts at 500 V — downwards 20 mm — upwards 20 mm — at the side 9 mm
- for live parts at 500 V — downwards 20 mm — upwards 20 mm — at the side 9 mm
- for grounded parts at 690 V — downwards 20 mm — upwards 20 mm — backwards 0 mm — at the side 9 mm — forwards 0 mm
- for live parts at 690 V — downwards 20 mm — upwards 20 mm — backwards 0 mm — at the side 9 mm — forwards 0 mm Connections/ Terminals type of electrical connection
- for main current circuit screw-type terminals
- for auxiliary and control circuit screw-type terminals arrangement of electrical connectors for main current circuit Top and bottom type of connectable conductor cross-sections
- for main contacts type of connectable conductor cross-sections
- for auxiliary contacts tightening torque size of the screwdriver tip Pozidriv size 2 design of the thread of the connection screw 3RV10111JA15 Page 3/6 10/24/2022 Subject to change without notice © Copyright Siemens
- for main contacts M3
- of the auxiliary and control contacts M3 Safety related data B10 value
- with high demand rate according to SN 31920 5 000 proportion of dangerous failures
- with low demand rate according to SN 31920 50 %
- with high demand rate according to SN 31920 50 % failure rate [FIT]
- with low demand rate according to SN 31920 50 FIT protection class IP on the front according to IEC 60529 IP20 touch protection on the front according to IEC 60529 finger-safe, for vertical contact from the front display version for switching status Rocker switch Certificates/ approvals General Product Approval For use in hazard- ous locations Confirmation For use in hazard- ous locations Declaration of Conformity Test Certificates Marine / Shipping Special Test Certific- ate Type Test Certific- ates/Test Report Marine / Shipping other Railway Confirmation Miscellaneous Special Test Certific- ate Further information Information- and Downloadcenter (Catalogs, Brochures,…) https://www.siemens.com/ic10 Industry Mall (Online ordering system) https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV1011-1JA15 Cax online generator http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV1011-1JA15 Service&Support (Manuals, Certificates, Characteristics, FAQs,...) https://support.industry.siemens.com/cs/ww/en/ps/3RV1011-1JA15 Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV1011-1JA15&lang=en Characteristic: Tripping characteristics, I²t, Let-through current https://support.industry.siemens.com/cs/ww/en/ps/3RV1011-1JA15/char Further characteristics (e.g. electrical endurance, switching frequency) http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV1011-1JA15&objecttype=14&gridview=view1 3RV10111JA15 Page 4/6 10/24/2022 Subject to change without notice © Copyright Siemens
I> I>I> 6/T3 4/T2 2/T1 5/L3 3/L2 1/L1 last modified: 6/25/2022 3RV10111JA15 Page 5/6 10/24/2022 Subject to change without notice © Copyright Siemens