GAPTEC-Electronic GmbH & Co. KG sales@gaptec-electronic.com – www.gaptec-electronic.com Page 1 of 6 360ACDR_SC – Rev. 2017-1.1 Specifications subject to change without notice. 360ACDR_SC Series 360W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated Industrial DIN Rail Power Supply High efficiency up to 93% Universal AC input range (85~264VAC) Support 1+1 or N+1 redundant system Built-in current sharing function Built-in current limiting circuit Over voltage protection (OVP) Over load protection (OLP) Short circuit protection (SCP) Over temperature prot. (OTP) Wide operating ambient temperature (-25°C~70°C) 150% (540W) peak load capacity 100% full load burn-in test AC-DC Converter 360 Watt The 360ACDR_SC series features standard rail mounting, energy efficiency and is highly cost-effective. The series offers stability and high noise immunity especially for industrial control equipment, machinery and other demanding environments for industri al equipment. This converter offers a compact and light weight design with and standard rail installati- on (32mm). Furthermore this series offers Easy Fuse Tripping due and a built-in DC OK relay contact. The converter can be installed on TS-35/7.5 or TS-35/15. Example: 360ACDR_24SC 360= 360 Watts AC= AC/DC DR= Din Rail 24= Vout S= Single Output C= PFC (Power Factor Correction) Input specifications Input voltage range 85~264VAC, 127-375VDC Input frequency 47~63Hz Power factor 110VAC
- 0.99 (typ) 230VAC
- 0.95 (typ) AC current 110VAC
- 5A (max) 230VAC
- 2.5A (max) Inrush current Cold start 110VAC
- 20A (typ) 230VAC
- 40A (typ) Leakage current Input—output: <0.25mA Input—PG: <3.5mA Output specifications Item Test conditions Min Typ Max Units Output voltage accuracy Full load ±3 % Voltage adjustment range
- 24V: 24~28V
- 34V: 34~37.5V
- 48V: 48~56V Line regulation Vin= min. to max. at full load ±0.5 % Load regulation 0% to 100% load ±1 % Ripple + Noise see model specifications table Set-up time @230VAC 3 s Hold-up time @230VAC, full load 20 ms Overshoot and undershoot 5 % Switching frequency 100 KHz Protection specifications Over-load protection 110%~150% of rated current, Constant current limiting for some time (150% of rated current, last 3S) then PS stop working for 7S, after 7S, if the load <=rated current, PS will work normally, auto recovery Over-voltage protection
- 24V: 29~33V, hiccup mode, auto recovery
- 36V: 39~43V, hiccup mode, auto recovery
- 28V: 58~63V, hiccup mode, auto recovery Over-temperature protection 115±5°C, detect on heat sink of power transistor; shut down O/P, auto recovery after temperature goes down. Common specifications Short circut protection: Long-term mode, automatic recovery Temperature rise at full load: 40°C MAX Cooling: Free air convection Operation temperature range: -25°C~+70°C Storage temperature range: -40°C ~+85°C Storage humidity range: < 95% Temperature coefficient: 0.03%/°C MAX MTBF (using MIL-HDBK-217F): +25°C >300,000 hours Safety standards: meet UL508, UL60950, EN60950 Power boost: 150% of rated current Parallel function: support DC-OK: V On: when output voltage is up to 90% of rated output voltage V Off: when output voltage is down to 80% of rated output voltage DC-OK relay contact rating: Max 30V/1A or 60V/0.3A or 30Vac/0.3A resistive load Case material: Heat-resistant Plastic (UL94-V0) and metal Dimensions: 50*124*127mm Weight: 917g Isolation specifications Item Test condition Min Typ Max Units Withstand voltage* • Primary-Sec. ≤10mA
- Primary-PG ≤10mA
- Secondary-PG ≤20mA Output-DC/OK: 0.5KVac/1mA 3000 2500 500 VAC Isolation resistance 10 MΩ * Input-Output, tested for 1 minute, 500VDC and leakage current less than 1mA Note: 1. All parameters NOT specially mentioned are measured at rated input, rated load and 25°C of ambient temperature.
GAPTEC-Electronic GmbH & Co. KG sales@gaptec-electronic.com – www.gaptec-electronic.com Page 2 of 6 360ACDR_SC – Rev. 2017-1.1 Specifications subject to change without notice. 360W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated Industrial DIN Rail Power Supply 360ACDR_SC Series Mechanical dimensions AC terminal blocks installation information Terminal No. Function Specs 1 PG 6.35mm, 3pin screw terminal blocks2 N 3 L DC terminal blocks installation information Terminal No. Function Specs 1 DC 6.35mm, 3pin screw terminal blocks 2 OK 3&4 +V 5&6 -V AC/DC terminal Type Screw terminal blocks Solid wire 0.5-6mm2 Strand wire 0.5-4mm2 Wire Spec AWG20-10 (PG wire >18AWG) Max wire diameter 2.8mm Recommended stripping length 7mm Screwdriver 3.5mm Straight or Cross Screwdriver Recommended torque 1NM EMC specifications EMC / Emission Compliance to EN55022, EN55024, FCC PART 15 Class B EMC / Harmonic current Compliance to EN61000-3-2, CLASS A EMC / Immunity Compliance to EN61000-4-2, -3, -4, -5, -6, -8, -11; heavy industry level The power supply is considered as a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. Approval Model Power [W] Output [Vo, VDC] Rated Current [A] Current Range [A] Ripple&Noise* [mV, max] 0~70°C -25°C Efficiency [%, typ] UL (pending) 360ACDR_24SC 360 24 15 0~15 240 480 93 UL (pending) 360ACDR_36SC 360 36 10 0~10 240 480 92.5 UL (pending) 360ACDR_48SC 360 48 7.5 0~7.5 480 720 92.5 * Measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1 uF & 10uF parallel capacitor. 360ACDR_SC
GAPTEC-Electronic GmbH & Co. KG sales@gaptec-electronic.com – www.gaptec-electronic.com Page 3 of 6 360ACDR_SC – Rev. 2017-1.1 Specifications subject to change without notice. 360W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated Industrial DIN Rail Power Supply 360ACDR_SC Series Typical characteristics Functional block diagram short time working, 3s. continuous working Output current vs. ambient temperature – 360ACDR_24SC Output current vs. ambient temperature – 360ACDR_36SC Output current vs. ambient temperature – 360ACDR_48SC Ambient temperature (°C) Ambient temperature (°C) Ambient temperature (°C) Load (A) Load (A) Load (A) Functional diagram
GAPTEC-Electronic GmbH & Co. KG sales@gaptec-electronic.com – www.gaptec-electronic.com Page 4 of 6 360ACDR_SC – Rev. 2017-1.1 Specifications subject to change without notice. 360W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated Industrial DIN Rail Power Supply 360ACDR_SC Series Mounting method instruction A1 is recommended output current. A2 is the allowed max output current (PSU lifetime is around half of A1). Below curves are tested under 230Vac (179~264Vac), when 110Vac input (85~175Vac), all derating points drop 10°C. 360ACDR_24SC Mounting A Mounting B Mounting C Mounting D Mounting E
GAPTEC-Electronic GmbH & Co. KG sales@gaptec-electronic.com – www.gaptec-electronic.com Page 5 of 6 360ACDR_SC – Rev. 2017-1.1 Specifications subject to change without notice. 360W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated Industrial DIN Rail Power Supply 360ACDR_SC Series Mounting method instruction 360ACDR_36SC Mounting A Mounting B Mounting C Mounting D Mounting E
GAPTEC-Electronic GmbH & Co. KG sales@gaptec-electronic.com – www.gaptec-electronic.com Page 6 of 6 360ACDR_SC – Rev. 2017-1.1 Specifications subject to change without notice. 360W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated Industrial DIN Rail Power Supply 360ACDR_SC Series Mounting method instruction 360ACDR_48SC Mounting A Mounting B Mounting C Mounting D Mounting E