Transmittersfor Level, Volume, orOpen C hannelFlow Installation and OperatingMan ual Mo del344/345 S oftware version2.3

EchotelModel 344/345UltrasonicNon-contactTransmitter Read thisMan ualBefore Installing T his manu al providesinformation on the Echotel ® Model 344/345 U ltrasonicT ransmitter.Itisimportant that allinstructions arereadcarefully and followed in sequence. Detailedinstructionsare included in the Unit Configuration section ofthism anual. ConventionsUsed in thisMa nual Ce rtainconventions areusedin thism anualto convey specifictypesofinformation.Generaltechnicalmaterial, supportdata,and safetyinformationarepresentedinnar - rativeform. Th e followingstylesare usedfor notes,cau - tions,and warnings. NO TES N otescontaininformationthataugmentsorclarifiesan operatingstep. No tesdo notnormallycontainactions. The y follow the proceduralstepsto wh ichtheyrefer. C autions Ca utionsalertthe techniciantospecialconditionsthat could injurepersonnel,dam age equipment,or reduce a comp onent’sme chanicalintegrity. Cau tions arealso usedtoalertthetechnicianto unsafe practicesor the needforspecialprotective equipmentorspecificm ate - rials. In thismanu al,a cautionbox indicatesa poten - tially hazardous situationw hich,ifnot avoided,m ay resultin minorormoderateinjury. WA RNINGS W arnings identifypotentiallydangerous situations or serioushazards.Inthism anual,a w arningindicatesan imminently hazardoussituationw hich,ifnotavoided, could resultin seriousinjuryordeath. SafetyMe ssages Fo llow allstandardindustryproceduresforservicingelec - trical and com puter equipment wh en w orkingw ithor around highvoltage. Always shut offthe power supply before touchingany compo nents.Although highvoltage isnot present inthis system,itmay be present inother systems. Electrical compo nentsaresensitiveto electrostaticdis - charge. T o prevent equipment dam age,observesafety procedures wh en w orking with electrostatic sensitive compon ents. Low Voltage Directive For use inInstallationsCategoryII,PollutionD egree 2. Ifequipm entisused in a manner not specifiedby the manu facturer,protectionprovidedby equipmentm aybe impaired. WA RNING Explosion hazard. D o not connector disconnectdesigns rated Explosion-proofor N on-incen - dive unlesspowerhasbeenswitched offand/ortheareais known tobe non-hazardous NoticeofC opyrightand Limitations Magn etrol& M agnetrollogotype,and Echotelare regis - tered tradem arksofM agnetrolInternational. C opyright© 201 0 M agnetrolInternational,Incorporated Allrightsreserved. Performa nce specificationsareeffectivewith date ofissue and are subject to change w ithout notice. Magne trol reserves the right to ma ke changes to the product described in thism anual at any time w ithout notice. Ma gnetrolm akesno w arranty w ithrespecttothe accuracy ofthe inform ation inthism anual. Wa rranty AllMagne trolelectronicleveland flow controlsare war - ranted freeofdefectsinm aterialsorw orkman shipforone fullyearfrom the date oforiginalfactoryshipment. Ifreturned withinthe warrantyperiod;and,upon factory inspectionofthe control,the causeofthe claimisdeter - mined to becovered underthe warranty;then,Magne trol willrepairor replace the controlatno cost to thepur - chaser(orowner)otherthan transportation. Magn etrol shallnot be liablefor misapplication,labor claims,directorconsequentialdamage orexpensearising from the installation or use of equipment. T here areno otherw arrantiesexpressed orimplied,exceptspecialw rit - ten w arrantiescoveringsom e Magn etrolproducts. Qu alityAssurance T he quality assurance system in place atMagnetrol guarantees the highestlevelofqualitythroughoutthe compa ny. M agnetroliscommitt ed to providing full custom er satisfaction both in quality productsand qualityservice. Ma gnetrol’squalityassurance system is registered to ISO 9 001 affirmi ng its com mitme nt to know n international qualitystandardsprovidingthe strongest assurance of product/service quality available.

1.0 Installation

1.4.1 Mou nting3⁄4" or2"NPT T ransducer

with Factory-Supplied B racket,

1.4.2 Mou nting3⁄4" or2"NPT T ransducer

with Factory-Supplied B racketand

1.4.3 Mou nting3⁄4",1" or2"NPT T ransducer

with Flange,Wi thorWi thout

2.0 W iring

2.1 ElectrostaticDischarge(ESD) Ha ndlingProcedure .10

3.0 G eneralInformation

4.0 U nitC onfiguration

4.4.1.2 R elay#2-normaloperation

4.4.1.3 R elay#3-normaloperation

4.4.1.4 R elay#4-normaloperation

5.0 Reference Information

Echotel ® Mod el344/345 UltrasonicN on-contactT ransmitters EchotelModel 344/345UltrasonicNon-contactTransmitter

Ca ution: Rea d entiresection priortostartinginstallation.

1.1 Unpacking

Unp ackthe instrum entcarefully. Make sureallcompone nts havebeen rem oved from the packing material.Inspectall comp onentsfordam age. Che ck the contentsofthe packing slip and reportany discrepanciesto the factory.Ch eckthe nam eplatem odelnum berto be sureitagreesw ith thepack - ingslip and purchase order.Chec k and record the serial numbe rforfuture reference w hen ordering parts. M odelN um ber S erialN um ber

1.2 Mounting

1.2.1 TransmitterLocation

The transmitterenclosure shouldbe securelyfastenedtoan appropriate supportingstructure,in a location thatpermits easy accessformaintenance. A void locationsthatare exposed todirectsunlight,flooding,highlevelsofradiated electromagn eticinterference,and excessivevibration or shock.

1.2.2 TransducerLocation

Mo del384/385 transducersm ustbe mou nted directlyover them aterialtobe m easured. B oth floorand w allmou nt transducerbracketsare availableforuseoveropen tanksor channels. F langem ountsareavailableforuse with closed vessels. Ifmo unted ina location w herethere isintense, extrem e,directsunlight,a sunshadeisrecom me nded. Properm ounting and wiring ofthe ultrasonic transduceris oftheutmostimportance. B oth the accuracy and therelia - bility oftheM odel344/345 can be adverselyaffected ifthe transducerismo unted improperly. NOT E: The 344/345 requiresa blockingdistance between the trans - ducer and the m aximum liquid level.The m inimum blocking distance is12 inches (305 m m )for Mode l345 and 18 inches (460mm ) for Mo del 344.At tempe ratures above +140°F (+60° C )m inim um ,it is 18 inches for either mo del.Ma ximum blocking distance should be lim ited to approximately 10 feet (3 m) as this blocking distance is extended at the expense of the usefulspan overw hich theinstrum entoperates.

4 EchotelModel 344/345UltrasonicNon-contactTransmitter

1.3 TransmitterMounting Procedure

The reare two predrilled openingsin the enclosurefor connecting3⁄4" NEMA 4X conduit. Referto F igure 3. 1. Op en thedoorofthe unit. 2. Dr illholesinthe enclosureasrequired foradditional wiring.Be carefulnotto dam agetheprinted circuitboards. Be surethatthe PC boardsare notdam aged orcontam inated when rem oving filingsand/ordebrisfrom the housing. 3. Provide w atertightsealsforallw iring entrancesintheenclo - sure tom aintaintheNEM A 4X rating. 4. Mo unttheenclosureto a wallorflatsurface usingthe appropriate screws orbolts. T he mo unting tabson theback oftheenclosurecan be rotated tothe sides,ortopand bot - tom tofacilitatem ounting. RefertoF igure 4. 5. Installconduitforpowerand controlwiring. Be sure all connectionstothe enclosure maintain a NEMA 4X rating. 6. Close thedooruntilitistime tow irethe transmitter. Secure thedoorby tightening thesixscrew s. Proceed to T ransducerMo unting on thenextpage. N OTE: Do not overtighten the screws that hold the transmitterdoor closed.Do notuse an electric orpneumaticdriveon thescrew. Ove rtightening can cause cracking ofthe housing,resulting in leakage intothehousing. Transducer Air Liquid Blocking Distance* Model 345 25 feet (7.6 m) maximum Model 344 35 feet (10.7 m) maximum Model 345 24 feet (7.3 m) maximum Model 344 33.5 feet (10.2 m) maximum Range Span *Minimum Blocking Distance: 18 inches (460 mm) for the Model 344 12 inches (305 mm) for the Model 345 Figure 2 Transducer Mo unting Location–Level/Volume EchotelModel 344/345UltrasonicNon-contactTransmitter Figure4 TransmitterMo untingTabs Figure 3 Predrilled Co nduitOpen ings

1.4 Transducer Mounting Requirements

  1. Whe neverpossible,locate the transducerto avoid obstruc - tionsbetween thetransducerface and the surface ofthe levelbeing tracked. T he ultrasonicsignalisemitted from thetransducerwitha beam spread ofapproximately 12 degrees. O bjectsthatextend intothe ultrasonic beam canproduce echoesthatm ask the truelevel.T he falsetarget buffering feature allowsforblocking outup tonine obstructionsinside thetank. UltrasonicBeam Angle Distancefrom 12°Beam Minimum Distance Transducer Face Diameter From Wallor infeet infeet Obstructionininches 2' 0.42' 2.52" 4' 0.84' 5.04" 6' 1.25' 7.5" 8' 1.67' 10.02" 10' 2.1' 12.6" 12' 2.5' 15" 14' 2.9' 17.4" 16' 3.3' 19.8" 18' 3.76' 22.56" 20' 4.18' 25.08" 22' 4.6' 27.6" 24' 5.02' 30.12" 26' 5.44' 32.64" 28' 5.86' 35.16" 30' 6.28' 37.68" 32' 6.80' 40.8" 35' 7.44' 44.64" 2. Position the transducersothatthe radiating surface or transducerfaceisexactlyparallelto the measurement surface. T hisw illprovide thestrongestreturn signalsand enhance thereliability ofthe Mo del344/345. 3. Inapplicationswhere them ateriallevelmay com e intothe blocking distance orwhere thefulltank heightw illbe used, thetransducerm ustbe m ounted in a shortpipe stub (standpipe).T he diameterofthe standpipe shouldbe at least8 inches(200m m )and itslength shouldbe limitedto 11 inches(280m m) from transducerface.Referto F igure 6. NO TE: W hen m ounting in a standpipe,performance is enhanced by using as shortofa pipe as possible. Figure 6 TransducerMo unting inStandpipe Figure 5 UltrasonicBeam Angle 8" (200) Minimum I.D. NPT Transducer This end welded or flanged to tank Pipe Stub Maximum 11" (280 mm) or less EchotelModel 344/345UltrasonicNon-contactTransmitter 12°beam

7EchotelModel 344/345UltrasonicNon-contactTransmitter 4. Avoidinstalling thetransducerin tank top openingsthat exhaustheated airorvapors.The boundariesbetween the vaporsand the outside airoften representacoustic imped - ance gradientsthatcan causetroublesome sound reflections. Inthose installations,the transducershouldbe mounted wellawayfrom theopening inside thetank,orin a pipe stub. RefertoF igures6 and 7. 5. T o preventelectrom agnetic noisefrom disrupting thenor - m aloperation ofthe Mod el344/345,itisrecommend ed thateachtransducercablebe run in itsown conduit,sepa - rated from otherpow ercablesand wiring. 6. Lo cate them ountingprocedurefrom the chartbelowand proceed tothe appropriate instructions. C aution: Do notinstalltransducers inthecenterofdome d roof tanks.Loc atetransducers 1'to3'offcentertom inim ize false/m ultiple echoes being reflectedoffthe dome d roof.

1.4.1 Mount ing3⁄4" N PT or2" N PT TransducerwithFactory-

Sup plied Bracket,W ithoutTransducerH ousing 1. Position the bracketsuch thatthetransducermou nting holeispositioned overthe open tank orchannel. R efertoF igure 8. 2. Secure thebracketto the w all,floor,orvesselasappropriate with four3⁄8" screws. R eferto the mo unting hole pattern as shown inthedimensionaldrawingsin Section 5.5.3. 3. Pulltransducercablethrough mo unting bracketand hand- tighten transducerinto fitting in mo unting bracket. C aution: HA ND -TIGHTEN ON LY .DO NOT use a pipewrench or othertools w hen tightening thetransducer.U se Teflon ® tape on thread for316stainless steeltransducer.Avoid excessive twisting ofthe transducercable. 4. Provide conduitfrom the transducertothe transmitter enclosure. Car efullypullthetransducercablethrough the conduittoward the transmitterenclosure.Thiscablewillbe connected asshown in Section 2.3.1,TransducerW iring W ithoutTransducer Ho using . Figure 7 TransducerMo unting forTanks With Exhaust NP T M ounting Housing Section 3⁄4"or2" bracket without 1.4.1 2" bracket with 1.4.2 3⁄4",1",or2" flange without 1.4.3 3⁄4"or2" flange with 1.4.3

  1. Tighten theconduittothe threadson the top ofthe trans -

(3M ™ #4441Gella ™ R eenterable Encapsulantorequivalent).

  1. Proceed toSection 2.0,W iring .

1.4.2 Mount ing2" N PT TransducerwithFactory-Supplied

  1. Position thebracketsuch thatthe transducermo unting
  2. Secure thebrackettothe wall,floor,orvesselasappropriate

shown inthedimensionaldrawingsin Section 5.5.3.

  1. Mo unttransducerintothe 2"NP T holeinbracketand

excessive twisting ofthetransducercable.

  1. Provide conduitfrom the transducerto thetransmitter

Figure 11. Thiscablewillbe connected asshown in Section 2.3.2,TransducerW iringWi thTransducer H ousing . (3M ™ #4441Gella ™ Re enterable Encapsulantorequivalent).

  1. Tighten theconduitatthe 3⁄4"connection on the transducer
  2. Proceed toSection 2.0,W iring .

1.4.3 Mo unting 3⁄4",1",or2" N PT Transducerwith Flange,

W ith orW ithoutTransducerH ousing 1. Position transduceroverthetank port. Boltthetransducer flangeto thetank portflange.Referto Figure12. 2. Hand -tighten transducerinto flange. Cau tion: H AN D-T IGHTEN ON LY .DO NO T use a pipewrench or othertoolswh en tightening thetransducer.U se Teflon ® tape on thread for316stainless steeltransducer.Avoid excessivetwisting ofthetransducercable. 3. Installconduitfrom the 3⁄4" NP T 316 SS nippleon trans - ducertothetransm itterenclosure. F ortransducersw ith transducerhousing,conduitisconnected to the 3⁄4" NPT housing conduitconnection. 4. Carefullypullthe connecting cablethrough the conduitto thetransmitter. R eferto Figure 13. T hiscablewillbe con - nected asshown inthe TransducerW iring section. N OTE: In high hum idityapplications,itis recommend ed that the transducer w iring be com pletely imme rsed in an insulating com pound w here the conduit connects to the transducer (3M ™ #4441Gella ™ R eenterable Encapsulantorequivalent). 5. Proceed toSection 2.0,W iring . EchotelModel 344/345UltrasonicNon-contactTransmitter Figure 12 Transducer Air Liquid Flange Figure 13 Transducer Transducer Cable Bolts Transducer Flange User Flange Conduit

2.1 ElectrostaticDischarge (ESD)

Magne trol’selectronicinstrumentsarem anufactured tothe highestqualitystandards. T hese instrum entsutilize elec - tronic com ponentswhich m aybe damaged by static elec - tricity presentinmo stw ork environm ents. T he following stepsarerecom m ended to reduce the riskofcom ponent failure due toelectrostaticdischarge:

  • Ship and store circuitboardsin anti-static bags.Ifan anti- staticbagisnotavailable,wrap boardin alum inum foil.Do notplaceboardson foam packing m aterials.
  • Use a grounding wriststrap w hen installing and remo ving circuitboards. A grounded workstation isalsorecom mend ed.
  • Hand leprinted circuitboardsonlyby the edges.Do not touch com ponentsorconnectorpins.
  • Make sure thatallelectricalconnectionsare comp letely mad e and none are partialorfloating. Gr ound allequip - me nttoa good,earthground. EchotelModel 344/345UltrasonicNon-contactTransmitter

11Echotel Model 344/345 Ultrasonic Non-contact Transmitter

2.2 Transmitter Power Wiring

NOTE: Models 344 and 345 have the same motherboard (P/N 030-3564-00X), but have unique daughter boards. The 345 uses a daughter board (P/N 030-3565-001) that drives the 50 kHz Model 385-XXXX-XXX transducer, and the 344 uses a daughter board (P/N 030-3573-001) that drives the 38 kHz Model 384-XXXX-XXX transducer. Caution: DO NOT attempt to operate this unit at voltages other than as specified from the Model Identification as it will damage the unit. Caution: This instrument is grounded through the grounding con- nector of terminal block TB1. The power input must include a ground wire connected to a good earth ground. Failure to ground the instrument may allow a shock hazard to exist! 1. Open the cover of the transmitter enclosure by loosening the six screws. 2. The PC board is marked for 120/240 VAC (L1, L2/N, GND) and 24 VDC (+,–) power connections. Ensure proper con- nections are made on the six position terminal block TB1. Refer to Figure 14. Spade lugs should be used. For opti- mum operator safety, observe the wiring colors listed in the chart at left. 3. T o prevent electromagnetic noise from disrupting the normal operation of the Model 344/345, the ground (GND) should be connected to a good earth ground with as short a length as possible of heavy wire or copper braid. 4. Proceed to the appropriate transducer wiring section. NOTE: Stainless steel transducers are shipped with a protective rub- ber cap over the transducer face. Remove this cap after mounting is complete.

2.3 Transducer Wiring

Caution: Do not run transducer cable in the same conduit with power, signal, or other transducer cables. The transducer cable consists of two twisted pairs of wire wrapped with a shield. Refer to Figure 15 for wire identifi- cation. NOTE: It is imperative that Magnetrol cable part number 037-3176 (Belden Type 8102) be used. If connecting cable was not pro- vided with unit, consult factory for specifications. Maximum total cable length is 500 feet (152 m). AVOID SPLICING CABLE. If a 316 stainless steel transducer is used, connect the green ground wire to an earth ground (i.e. conduit, tank, etc). If a junc- tion box is used, connect earth ground to green terminal screw. TB5 TB1 L1 L2/N GND (+) (-) LOOP 4-20 Totalizer Heater Power Supply (–) (+) Loop 4–20 Figure 14 344/345 Motherboard (shown with daughterboard removed) U.S. Europe U.K. Line 1 (Hot) Black Blue Brown Line 2 (Neutral) White Black Blue Ground Green/Yellow Green/Yellow Green/Yellow Wiring Colors By Country/Continent

Afterrunning the transducerw iring in itsow n conduitfrom thetransducerto thetransmitter,separate thew iresintotwo groups; Gro up 1 - Ultrasonicsignalw iring (orange/whitepair) Gro up 2- T emp eraturecomp ensation w iring (blue/w hitepair)

2.3.1 TransducerWiring W ithout TransducerHo using

The follow inginstructionsare intended forusew hen the transducerisprovided withouta transducerhousing. T here willbe 35 feet(10.7 meters)ofpotted cablecom ing outof thetransducer. T hiscablecan be shortened asdesired to accom mo datetheinstallation. Gro up 1 (U ltrasonic Signal) 1. Con necttheorangew /w hite stripe w ire tothe terminal marked (X1) atT B 6. 2. Con necttheshieldwire to the middleterminalatT B 6. 3. Con nectthewhitew/ orangestripe w ire tothe terminal marked (X2)atT B 6. Gro up 2 (T emp erature Signal) 1. Con nectthewhitew/ blue stripe wireto the terminal labeled positive(+)atT B7. 2. Con necttheblue w /white stripe wireto the terminal labeled negative(-)atTB7. NOT E: Bothgroups ofw ire(U ltrasonicand Tem perature)must be connected. EchotelModel 344/345UltrasonicNon-contactTransmitter Daughterboard TB6 X2 SH X1 TB7 – + Ultrasonic Transducer TB6 TB7 NOT E: Overallcable jacket and individual wire jackets should be cutas shortas possible.This illustration is intended forw iring termination clarityonly. Figure 15 Wiring without TransducerHousing

2.3.2 TransducerW iring witha TransducerH ousing

The follow ing instructionsareintended foruse when a transducerhousing hasbeen provided.Thishousing is threaded onto thetopofthe transducervia a 3⁄4" NP T 316 SS nipple. A boardinside thehousing isused to terminatethe transducercabling. NO TE: Ifcable w as notprovided by Ma gnetrol,Beldon 8102orequiv - alentm ustbe used. Gr ou p 1 (U ltrasonic Signal) 1. Co nnectthe orangew /w hitestripe w irefrom thetransducer housing terminalmarked (X1) to the term inalinside the transm itterm arked (X1) atTB 6 on the daughterboard. 2. Co nnectthe shieldfrom thetransducerhousingterminal marked (SHL D) to the m iddleterminalatT B6 on the daughterboard. 3. Co nnectthe white w/ orangestripe w irefrom thetransducer housing terminalmarked X 2(GND )tothe terminal marked (X2)atTB 6 on thedaughterboard. Gr ou p 2 (T emp erature Signal) 1. Co nnectthe white w/ bluestripe w ire ofthe tw istedpair from thetransducerhousing terminalm arked (+)tothe terminallabeled positive(+)atTB 7 on the daughterboard. 2. Co nnectthe blue w /w hite stripe w ire ofthe tw istedpair from thetransducerhousing terminalm arked (-)tothe terminallabeled negative(-)atT B 7 on the daughterboard.

13 EchotelModel 344/345UltrasonicNon-contactTransmitter

TRANSDUCER TEMPERATURE□ SENSORX1 X2 + - SHLD SHLD SH Figure 16 W iring withTransducerHousing TB6 Bluewithwhitestripe Orange withwhitestripe White w/orange stripe White withbluestripe TB7 SHLD

2.4 Relay O utputWiring

The 344/345 unitissupplied w ith 4 relaysthatcanoperate asnormal independentcontactclosuresorcan be usedas dedicated relaysasfollows: R elay1 No rm al R elay 2 N ormalorLead/La g Pum p Alternation (withRelay 1 ) R elay3 No rm alorDed icated Fault R elay4 No rm alorSam plerCo ntact Relayconnectionsare supplied on the mo therboard as shown in F igure 17. 1. T wo -wireleadsareconnected to the desired relayterminal block. Co nnectone wireto the com mo n terminal(labeled CO ),and theotherto theterminalforthedesired contactfunction—(NC) fornormallyclosed or(NO )for normallyopen. Repeatthisstep foreach relay. 2. R eferto RelaySettingsintheI/O Con figuration section forinformation on configuring the relays. NO TE: Ifthe device tobe operatedby therelayhas an inductive load, a separatepow ersupply should be used forthe electronics.

2.5 O utputSignalWiring

The 4 –20mA DC outputconnectionscan be mad e atter - minal blockTB 1, located inside thetransmitterhousing. Referto Figure 18. The loop isopticallyisolated,hasnon- grounded outputs,and can drivea 1000 -ohm load. 1. Co nnectthe positive(+)shielded twisted pairwire from the load toterminalLO O P (+). 2. Co nnectthe negative(-)shielded tw isted pairwirefrom the load toterminalLO O P (-). NO TE: The shield should be connected toan earthground atonly one location. Figure17 344/345 Mo therboard NC CO NO NC CO NO RELAY #1 RELAY #2 TB3 RS485 RS232NC CO NO NC CO NO RELAY #3 RELAY #4 TB4 TB2 T Figure18 344/345 Mo therboard TB5 TOT. (TOTALIZER) HEAT (HEATER) L1 (+) L2/N (-) GND (+) (-) LOOP 4-20 TB1 NC RE EchotelModel 344/345UltrasonicNon-contactTransmitter

2.6 RS-232 Output

N O TE: The RS-232 output is only used for downloading inform ation from theoptional31-day datalogger. RS -232outputconnection islocated atT B 2and labeled T X and RX. R efertoF igure19. This connection forthe RS-232isutilized forthehook-up ofa laptop com puter. Inthelaptop m ode,one candown - load stored dataifunitisequipped with the datalogging option. The cabletoconnectthelaptop com puterto the Mod el 344/345 m ustbe supplied by the user.Con figurethiscable asshow n in F igure 19. D ow nloading instructionsare in the Laptop Section on page39.

2.7 Transducer Synchronization

T ransducersynchronization isonlyavailablew iththeMod el 344 unit.Itallowsyou to run the cabling from mu ltiple Mo del384 transducersin the same conduit.Th isprevents thepossibilityforcrosstalkto occurfrom one Mode l344 to another. The synchronization scheme involvesthe useof one 344 unitoperating asa master,and one ormore other unitsoperating asslaves. MultipleM odel344 unitsshouldbe w ired togetherutilizing TB 8 (Figure20)on the daughterboardasshown inFigure 21 below. T he masterunitsynchronizesthe ultrasonicsignals such thatallunitstransmittheirultrasonicsignalsatthe same time. T hiseliminatesthe possibility ofcrosstalk occurring. No calibration orconfiguration isnecessaryother thanthe wiringshown below.

15 EchotelModel 344/345UltrasonicNon-contactTransmitter

(344Daughterboard) SynchronizationTerminalBlock – TB8 SYNC. IN SYNC. OUT GR. REF. SYNC. OUT GR. REF. SYNC. IN GR. REF. SYNC. IN GR. REF. SLAVE UNITMASTER UNIT SLAVE UNIT Figure 21 Synchronization WiringDiagram TB2 (344/345Transmitter) DB 25F Connector (Laptop) RX TX 3 Figure 19

3.0 GeneralInformation

3.1 Menus

The M odel344/345 transmittercontainsa microprocessor- based operatorinterfacew hich allows foreasyconfiguration oflevel,volum e,oropen channelflow applications.A llcon - figuration dataisentered viaa keypad located on thefront oftheunit. Userinterface and configuration instructionsare broken down into six m aingroupsofme nus: M EA SURE D VAL UE S To view measured values SYS TE M CON FIG Basicprogramm ing informationrequiredforsystem operation. I/O C ONFIG Configureinput/outputfunctions A DVA NCE D CONFIG Additionalvaluesthataffecttheperformanceand functionalityofthe transmitter DIAGNOST ICS Testfunctionsand system diagnosticinformation LA PTOP Download dataloggingtolaptop computer (with optionalD ata Log geronly)

3.2 Passw ords

Ca ution: The Mod el344/345 is shipped from thefactorywiththe passwo rdsetat0341.Ifthepassw ordismisplaced or forgotten,consultthe factory forassistance. The M odel344/345 hastw o typesofpasswo rdsthatcanbe used toprotectconfiguration parameters. The y are asfollows:

3.2.1 G eneralPassw ord

The Ge neralPasswo rd ( PASSWO RD )isused forthe System Con fig and the I/O Conf igportion ofthe Men u Structure. Whe n a changeismad e to parametersinthese m enus(i.e., range,span,4 –20m A, relays,etc.),the M odel344/345 will prom pttheoperatortoentera passwo rd.Thispasswordcan be any one- tosix-digitnumeric combination.

3.2.2 SupervisoryPasswo rd

The SupervisoryPasswo rd( SUP PSWD )isused forthe Ad vanced Co nfigportion oftheM enu Structure. This password isused to protectvaluesthatcan affectthe performanceand/oraccuracy ofthedevice. NOT E: Although the Sup ervisory Pa ssword is normallyused in the Advanced Co nfig m enu,this passw ordcan alsobe used in any portion of the m enu.The Sup ervisoryPa ssword overrides the GeneralPa ssw ord.

16 EchotelModel 344/345UltrasonicNon-contactTransmitter

The Passwords can be changed at any time via the Advanced Config mode. If an invalid password is entered, the display will read Password Invalid. By pressing twice, the unit will continue to operate with the previously-programmed parameters.

3.3 Operator Keypad

All Unit Configuration instructions in this manual will show the local transmitter display exactly as it will appear to the operator. The operator interface to the 344/345 is via a keypad consisting of the following keys: 17Echotel Model 344/345 Ultrasonic Non-contact Transmitter Password Sup Pass For numeric entry of parameters. For decimal-point entries. To exit any programming area and return to a measurement mode. For entering new parameter values into memory. Also used to exit the parameter entry mode, if pressed prior to entering numeric parameter values. To sequentially access other parameters. Parameters may also be skipped over without affecting their stored values. The DOWN arrow also acts as a backspace for correcting data entry errors. Helpful when entering a new tag in the Enter Tag section of the Advanced Configuration menu.

18 EchotelModel 344/345UltrasonicNon-contactTransmitter

  1. 0 UnitConfiguration

4.1 Comple te Menu Structure

V olum e (Vo lume mo de only) F low (Flow m ode only) Totalizer(Flow mo de only) L evel D istance L oop C alculation Tem perature V iew D ataLog P revious M enu TestR elays Test4–20m A Lo op S ignalS trength V iew Version# Extended Errors P revious M enu R elay Se ttings 4–20mA S ettings Totalizer(Flow mo de only) C om m P ortS etup P revious M enu Tem perature C alibrate Gain Lim it F alse Targets EnterTag C alculation C hange Su p P assword D am pening S etC lock D efaultDisp lay C hange Passwo rd P revious M enu L evelU nits M ode S etup S TR T ____ EN D ____ Level Only Volum e & L evel Flow & Level R ange S etting S pan S etting P reviousMenu Vessel Type Volume Units R ange S etting M aximum Volum e S pan S etting P reviousMenu Flow Element Flow Units R eferenceD istance M aximum Flow M aximum H ead Low Flow Cutoff P reviousMenu

4.2 Mea suredValues

The M easured ValuesM enu containsread-onlydatathatis presentlybeing measuredby the Model 344/345 transmitter . Press from thedefaultdisplayto accesstheMeasured Valuesm enu. “Me asured Values”along w ith the Up/D own arrows willbe displayed. T oview the Me asured Values,press atthe Me asured Valuesdisplay.“Level”w illbe displayed iflevelmod e has been selected. “Volume” willbe displayed ifvolume mod e hasbeen selected. “F low ” w illbe displayed ifflow mod e has been selected. T oview the PresentMea surement:Press . A fterreviewing, press to return toL evel,Volume (Volume Mod e Only) orFlow (Flow M ode On ly).T o scrolldow n to thenext Me asured Value: Press . Pressing the scrollsup the me nu. Press atany me asured valuethatyou w ishto review. Ifyou do notwish to view them easuredvaluesatthistime, press once ifina m ain men u mo de ortwiceifina value read m ode from anywherein the displayand theunitwill return tothe defaultdisplay,orpress atPrevious Menu display,and theunitw illreturn to Measured Values .

4.2.1 View Data Log

Ifthe344/345 transmitterw asordered w ith theData Lo ggeroption,theView Dat a L og screen allows forstorage ofup to 31 daysofthefollow ing measurem entdata. Level Min imum and maximum leveland time ofoccurrence each day. Volume and Level Min imum and maximum volume and time ofoccurrence each day. Flow and Level Min imum and maximum flow and time ofoccurrenceeach dayand totalflow forthatday. EchotelModel 344/345UltrasonicNon-contactTransmitter

  1. 3 System Configuration This m enu isused to configurethe main controlparame - tersofthe Mo del344/345. T hisisalso used forfirst-time configuration oftheunit. On ceintheSystem Con figuration M enu,you m ayscroll through theselectionsby using or arrow. Once the desired selection isdisplayed,press . T he unitiscapable ofbeingconfigured inthreedifferentm odesofoperation.
  • Le velOn ly
  • Volume & Le vel
  • Flow & Le vel

4.3.1 LevelMe asureme nt

NO TE: The 344/345 has a defaultrange settingof 144 inches programm ed into the software.Ifthe transducer isinstalled inthe application and the distance from the transducer face is further away than 144 inches,the display w illread Los s of Echo .The range setting w illhave tobe adjustedatthis pointin ordertoclearthe loss ofecho error. 1. Press todisplayMeasured Values . 2. Press todisplaySystemConfig . 3. Press todisplayLevel Units . 4. Press then or tom akeyourunitsofm easure selection. 5. Press todisplayMode Setup . NO TE: Ifyour selection is differentfrom the previous selection,the display willask for a passw ord.At any pointPASS WORD? is displayed,key in 0341 ,and press . 6. Press todisplayLevel Only . WA RNING Changing theM ode Setup W ILL eraseA L L settings ifthe344/345 hasbeen previouslyconfigured! Con firm changeby pressing . K eyin yourpass - wo rdifPassword? isdisplayed. 7. Press todisplayRange Setting . NO TE: Ran ge setting is the m easured distance from the transducer face to the low est point of me asurement or the zero level pointin thevessel. EchotelModel 344/345UltrasonicNon-contactTransmitter

  1. Press . or togglesbetw een manual set orauto set . N OTE: Man ualSe tis thepreferredmo de. Man ualSet Mo de allows directentry oftheRa nge value.Enter the distance from the transduer face to the zerolevelpointor bottom ofthe vessel.Auto Se tMo de isonlyused ifthevessel dimensions areunknow n.L iquidlevelmust be broughtdown to zeropointin thevesselpriortopressing toautom aticallyset theR ange value. 9. Press ,key inRng value. 10. Press todisplaySpan Setting . N OTE: The Sp an Se tting is thedistance from thelowe stpointor zero to the m aximum anticipated distance that the levelwillrise in the tank,w ithout entering the blockingdistance of the trans - ducer.Typically,Spa n is thedifference between theR ange and theblocking distance. 11. Press todisplay Manual Set . N OTE: The user can toggle between Manual Set and Auto Set likethe range setting schem e.Inthe auto mo de,be certainthat the levelisat itsabsolute m axim um in the tank otherwise loss of echo ma y occur. 12. Press ,key inSpn value. Cau tion: Ifthe actuallevelfalls below them aximum range oftheunit, thefail-safeselection mu stbe setup so thatthedesired outputis transmitted.When thelevelfallsbelow thepro - gram m ed range,thedisplay w illshow Lo ss ofEcho.Ifthis condition occurs,thefail-safeactions willtake place. WA RNING : Iflevelexceeds the programme d span,falsedisplay or output/controlerrors w illoccur.Transducershould be installed and unitprogramm ed toassurethatthis level cannotoccur. 13. Press to displayPrevious Menu 14. Press todisplaySystemConfig . 15. Press onceto displayI/O Config . System Co nfiguration isnow com plete. ProceedtoI/O Con figuration,Section 4.4 . EchotelModel 344/345UltrasonicNon-contactTransmitter Transducer Air Liquid Blocking Distance* Model 345 25 feet (7.6 m) maximum Model 344 35 feet (10.7 m) maximum Model 345 24 feet (7.3 m) maximum Model 344 33.5 feet (10.2 m) maximum Range Span *Minimum Blocking Distance: 18 inches (460 mm) for the Model 344 12 inches (305 mm) for the Model 345 Figure 22

4.3.2 Volume and LevelMe asureme nt

This m enu isused to configurethe parametersofthe Mod el 344/345 forVolum e and Le velMeasureme nt. On ce in the System Config men u, you m ayscrollthrough theselectionsby using or . On ce thedesired selection isdisplayed,press . The unitiscapableofbeing config - ured in threedifferentm odesofoperation.

  • Le velOn ly
  • Volume & Le vel
  • Flow & Le vel 1. Press todisplayMeasured Values . 2. Press todisplaySystemConfig . 3. Press todisplayLev elUnits . 4. Press then or tom akeyourunitsofm easure selection. 5. Press todisplayMode Setup . NOT E: Ifyour selection is differentfrom the previous selection,the display willask for a passw ord.At any pointifPASS WORD? is displayed,key in0341 ,and press the key. 6. Press then or untilVolume & Lev el isdisplayed. WAR NING Changing theM ode Setup W ILL eraseA L L settings ifthe344/345 hasbeen previouslyconfigured! Con firm changeby pressing . K eyin yourpass - wo rdifPassword? isdisplayed. 7. Press todisplayVesselT ype . 8. Press then or toscrollthrough vesseltype selections. Hor iz/Flat Hor iz/Elipp. Hor iz/Sphere Verti/Flat Verti/Conical Spherical Custom T able (refertoSec tion 4.3.2.1) EchotelModel 344/345UltrasonicNon-contactTransmitter
  1. Press toselectyourvesseltype. 10. Press then keyin promp ted values. Rad__ . R adius End_ _. End R adius (entervalue ofone end ofvessel) Len __ . Length Ht_ _ . He ight Con_ _. Con e 11. Press todisplayPassword?.Ke y inpassword. Volume Units . 13. Press then or toscrollthrough volume units selections. Cubic Feet Gallons Million Gallons Cubic Meters Liters Million Liters Petroleum B arrel 14. Press toselectunits. 15. Press todisplayRange Setting . N OTE: R ange setting is the m easured distance from the transducer face to the low estpointofm easurement orzero. 16. Press then or totogglebetween manual set or auto set . N OTE: Man ualSe tis thepreferredmo de. Man ualSet Mo de allows directentry oftheRa nge value.Enter the distance from the transduer face to the zerolevelpointor bottom ofthe vessel.Auto Se tMo de isonlyused ifthevessel dimensions areunknow n.L iquidlevelmust be broughtdown to zeropointin thevesselpriortopressing toautom aticallyset theR ange value. 17. Press ,key inRng value. 18. Press todisplayMaximum Volume . 19. Press key inMax value . 20. Press todisplaySpan Setting N OTE: The Sp an Se tting is thedistance from thelowe stpointor zero to the m aximum anticipated distance that the levelwillrise in the tank,w ithout entering the blockingdistance of the trans - ducer.Typically,Spa n is thedifference between theR ange and theblocking distance. EchotelModel 344/345UltrasonicNon-contactTransmitter Horizontal/Flat side view Horizontal/Elliptical side view Rad Rad End Length Length Length Horizontal/Spherical side view Vertical/Flat top view Vertical/Conical top view Spherical Rad Height Height Cone Rad Rad Rad Figure23 VesselTypes
  1. Press todisplayManual Set . NOT E: The user can toggle between Manual Set and Auto Set .Inthe AutoSet m ode,be certain thatthelevelisatitsabsolutem ax - imum in the tank otherw ise loss ofecho may occur. 22. Press ,key inSpn value. Ca ution: Ifthe actuallevelfalls below thema ximum range ofthe unit,the fail-safeselection m ustbe setup so thatthe desiredoutputis transm itted.When thelevelfallsbelow theprogramm ed range,the display willshow Lo ss of Echo.Ifthis condition occurs,thefail-safeactions will takeplace. WAR NING : Iflevelexceeds theprogrammed span,falsedisplay or output/controlerrors w illoccur.Transducershould be installed and unitprogram me d toassurethatthis level cannotoccur. 23. Press to displayPrevious Menu 24. Press todisplaySystemConfig . 25. Press onceto displayI/O Config . System Co nfiguration isnow com plete. Proceedto I/O Con figuration,Section 4.4 . EchotelModel 344/345UltrasonicNon-contactTransmitter

4.3.2.1 Cust om TableEntry

  1. IfCustom T able isselected atstep 8,Press to display T ableName . 2. Press todesignatea TableNam e. Press to startthe firstcharacterscrolling. Ifa fasterscrolling speed isdesired, press again.Press to stop ata character.Use or tosingle-step to a desired character. 3. Press onceagain to proceed tothe nextcharacter.F or thebalance ofthe TableNam e,perform thesame stepsas stated above. A m aximu m of13 characterscanbe used. 4. Whe n com pleted,press to displayMax T able Span . 5. Press and key in Max value in the chosen levelunits. 6. Press todisplayMax T able Value . K ey in the maximu m valuein the chosen volume units.(Forexample: ifthevalue for100% ofvolume in the tablew as5,500gallons,enter 5500.) 7. Press todisplayT able Units . T heseare thetablevolume units. Press to startthe firstcharacterscrolling.Ifa faster scrollingspeed isdesired,press again. Press tostopat a character.Use or to singlestep toa desiredcharacter. 8. Press onceagain to proceed tothe nextcharacter.F or thebalance ofthe tableunits,perform thesame stepsas stated above. A m aximu m of3 characterscanbe used. 9. Whe n com pleted,press to displayEnterT ablePts . 10. Press todisplay00%; 0. 11. Enterpercentofvolume foreachpercentofleveldisplayed in2% steps. Tableiscom plete afterall51 pointsare entered. SeeF igure 24atleftforan examp le. 12. Press todisplayPrevious Menu. 13. Press todisplayVolume Units.Press and Operation Denied willdisplaybecausevolum e unitshavealready been entered. 14. Press or to displayRange Setting. 15. Proceed with step 16, Section 4.3.2 on page23. EchotelModel 344/345UltrasonicNon-contactTransmitter Points Level% % of Volum e 0 0 0.00 1 2 3.60 2 4 5.58 3 6 7.55 4 8 9.51 5 10 11.48 6 12 13.44 7 14 15.41 8 16 17.37 9 18 19.34 10 20 21.31 11 22 23.28 12 24 25.25 13 26 27.21 14 28 29.18 15 30 31.15 16 32 33.11 17 34 35.08 18 36 37.05 19 38 39.02 20 40 40.98 21 42 42.95 22 44 44.92 23 46 46.89 24 48 48.85 25 50 50.82 26 52 52.79 27 54 54.75 28 56 56.72 29 58 58.69 30 60 60.66 31 62 62.62 32 64 64.58 33 66 66.56 34 68 68.51 35 70 70.49 36 72 72.44 37 74 74.42 38 76 76.39 39 78 78.36 40 80 80.33 41 82 82.30 42 84 84.26 43 86 86.23 44 88 88.20 45 90 90.16 46 92 92.13 47 94 94.10 48 96 96.06 49 98 98.03 50 100 100.00 Figure24 Custom TableExam ple

4.3.3 Flow and LevelMe asureme nt

This m enu isused to configurethe main controlparameters ofthe Model 344/345 forthe F low and L evelMea surement. On ceintheSystemConfig m enu,you m ayscrollthrough theselectionsby using or . On ce thedesired selection isdisplayed,press . The unitiscapableofbeing config - ured in threedifferentm odesofoperation.

  • Le velOn ly
  • Volume & Le vel
  • Flow & Le vel 1. Press todisplayMeasured Values . 2. Press todisplaySystemConfig . 3. Press todisplayLev elUnits . 4. Press then or tom akeyourunitsofm easure selection. 5. Press todisplayMode Setup . NOT E: Ifyourselection is differentfrom theprevious selection,thedis - play willask fora passw ord.Ifatany pointPASSWORD ? is dis - played,key in 0341 and pressthe key. 6. Press then or untilFlow & L evel isdisplayed. WAR NING Changing theM ode Setup W ILL eraseA L L settings ifthe344/345 hasbeen previouslyconfigured! Con firm changeby pressing . K eyin yourpass - wo rdifPassword? isdisplayed. 7. Press todisplayFlow Element . 8. Press then or toscrollthrough flow elementselec - tionsshow n atleft. 9. Press toselectyourflow elemen t. 10. Press todisplayPassword?.Ke y inpassword. Flow Units . EchotelModel 344/345UltrasonicNon-contactTransmitter Flow Eleme ntM enu Vnotch 22.5° Vnotch 30° Vnotch 45° Vnotch 6 0° Vnotch 9 0° Vnotch 120° Parshall 1" Parshall 2" Parshall 3" Parshall 6 " Parshall 9 " Parshall 12" Parshall 18" Parshall 24" Parshall 36" Parshall 48" Parshall 6 0" Parshall 72" Parshall 9 6" Parshall 120" Parshall 144" Rct/Cntr (Re ctangularw /End Cont ractions) Rectangular (W ithoutEnd Con tractions) Cipolletti Palmer-B 4" (Palmer-Bowlus) Palmer-B 6" Palmer-B 8" Palmer-B 10" Palmer-B 12" Palmer-B 15" Palmer-B 18" Palmer-B 21" Palmer-B 24" Palmer-B 27" Palmer-B 30" H -Flume 6" H -Flume 9" H -Flume 12" H -Flume 18" H -Flume 24" H -Flume 30" H -Flume 36 " H -Flume 54" I12 Z (I-Flume ) I30Z I40 Z I50 Z I6 0Z I80Z I10H I13 H I16 H Custom T able
  1. Pres s the no r toscrollthrough flowunitsselections. Cubic Feet/Sec Cubic Feet/Min Cubic Feet/Hr Gallons Per Min Gallons Per H our Million Gals/D ay Cubic Meters/Sec Cubic Meters/Min Cubic Meters/Hr Liters/M in Liters/H our MegaL iters/Da y 13. Press toselectunits. 14. Press todisplayReferenceDist . N OTE: R eference distance is the me asured distance from the trans - ducerface tothe low estpointofm easuremen torzeroflow. 15. Press then or totogglebetween Manual or Auto set . N OTE: Man ualSe tis thepreferredmo de. Ma nual Set Mo de allows direct entry of the Reference Di stance.Enter the distance from the transduer face to the point ofzeroflow inthe flum e or weir.Auto Se t Mo de is only used iftheflum e orw eirdim ensions areunknown.LiquidH ead m ust be brought dow n exactly to the zero flow point prior to pressing toautom aticallysetthe Reference Distance value. 16. Press ,key inReferenceDistance value. 17. Press todisplayMaximum Flow . 18. Press key inMax value . 19. Press todisplayMaximum Head 20. Press then or totogglebetween Manual or Auto set . 21. Press key inH ead value . 22. Press todisplayLo w Flow Cutoff . 23. Press ,key inCut value. 24. Press todisplayPrevious Menu . 24. Press todisplaySystemConfig . 25. Press onceto displayI/O Config . System Co nfiguration isnow com plete. ProceedtoI/O Con figuration,Section 4.4 . EchotelModel 344/345UltrasonicNon-contactTransmitter

28 EchotelModel 344/345UltrasonicNon-contactTransmitter

4.3.3.1 C ustom Table Entry

  1. IfCustom T able isselected atstep 8,Press to display T ableName . 2. Press todesignatea TableNam e. Press to startthe firstcharacterscrolling.Ifa fasterscrolling speed isdesired, press again.Press to stop ata character.Use or tosinglestep toa desiredcharacter. 3. Press onceagain to proceed tothe nextcharacter.For thebalance ofthe TableNam e,perform thesame stepsas stated above. A m aximum of13 characterscanbe used. 4. Whe n com pleted,press to displayMax T able Span . 5. Press and key in Max value in the chosen levelunits. 6. Press todisplayMax T able Value . K ey in the maximu m valuein the chosen flowunits.(Forexamp le:ifthe value for 100% offlowinthetablewas 5,500GP M, enter5500.) 7. Press todisplayT ableUnits . T heseare thetableflow units. Press to startthe firstcharacterscrolling. Ifa faster scrollingspeed isdesired,press again. Press tostopat a character.Use or to singlestep toa desired character. 8. Press onceagain to proceed tothe nextcharacter.For thebalance ofthe tableunits,perform thesame stepsas stated above. A m aximum of3 characterscanbe used. 9. Press todisplayTim ebase. U se or to choose Seconds,Mi nutes,Ho urs,orDay s.T hisselection enables thetotalizerto function properly. 10. Whe n com pleted,press to displayEnterT able Pts . 11. Press todisplay00%; 0. 12. Enterpercentofflow foreach percentofheaddisplayed in 2% steps. Tableiscom pleteafterall51 pointsareentered. See F igure25atleftforan examp le. 13. Press todisplayPrevious Menu. 14. Press todisplayFlow Units.Press and Op eration Den ied willdisplaybecauseflow unitshavealready been entered. 15. Press or to displayReferenceDistance. 16. Proceed with step 14, Section 4.3.3 on page27. Points H ead % % of Flow 0 0 0.00 1 2 3.60 2 4 5.58 3 6 7.55 4 8 9.51 5 10 11.48 6 12 13.44 7 14 15.41 8 16 17.37 9 18 19.34 10 20 21.31 11 22 23.28 12 24 25.25 13 26 27.21 14 28 29.18 15 30 31.15 16 32 33.11 17 34 35.08 18 36 37.05 19 38 39.02 20 40 40.98 21 42 42.95 22 44 44.92 23 46 46.89 24 48 48.85 25 50 50.82 26 52 52.79 27 54 54.75 28 56 56.72 29 58 58.69 30 60 60.66 31 62 62.62 32 64 64.58 33 66 66.56 34 68 68.51 35 70 70.49 36 72 72.44 37 74 74.42 38 76 76.39 39 78 78.36 40 80 80.33 41 82 82.30 42 84 84.26 43 86 86.23 44 88 88.20 45 90 90.16 46 92 92.13 47 94 94.10 48 96 96.06 49 98 98.03 50 100 100.00 Figure 25 Custom TableExam ple

4.4 I/O Configuration

This m enu isused to configurerelaysettings,output,total - ization,and comm unicationsparametersofthe Mod el 344/345. On ceintheI/O Co nfiguration men u,scrollthrough the selectionsby using or arrow. O nce the desired selection isdisplayed,press .

4.4.1 R elay Settings

Allrelayscan be configured fornormal m ode ofaction (i.e., pump control,highorlow alarm) orfordedicated relaysas follows: Relay1- No rmal Relay2-Normal orL ead/Lag Pump A lternation(withR elay 1) Relay3- No rmalorDed icated Fault Relay4- No rmalorSamp lerCon tact

4.4.1.1 R elay #1– normaloperation

  1. Press todisplayMeasured Values . 2. Press todisplaySystemConfig . 3. Press todisplayI/O Config . 4. Press todisplayRelay Settings . 5. Press todisplayRelay # . 6. Ke y in ,press . T he operating statusofthe relaywill be displayed. N OTE: Ifrelay num berisentered in error,press toreturnto R elay Settings. 7. Press or totogglebetween Disabled and Enabled . Wi th Enabled displayed,press to display Setpoint . N OTE: Ifin Flow or Vo lum e m ode,the unitwillprompt tosetrelays in Le veloreitherF low orVo lum e mo de. 8. Press ,key inOn value. 9. Press ,key inOff value. N OTE: Ifkeyed in On and Offvalues areidentical,On >= Setpoint willbe displayed.Press or totoggle between < and >= . 10. Press ,key inOn Delay value. 11. Press ,key inOffDelay value. N OTE: De layis the num berofseconds beforeactivatingordeactivat - ing therelay contactclosure.This valueisadjustable from 1 to 120seconds. EchotelModel 344/345UltrasonicNon-contactTransmitter
  1. Press todisplayFailsafe . Press or to toggle between On ,Off ,orHo ld . N OT E: With loss ofpow er,allrelays,regardless offail-safesetting,will de-energize. NOT E: F ail-safeisthestatethe relay willassume ifa faultisdetected or echo loss occurs.Off me ans the relay isde-energized.On mean s the relay is energized and Ho ld me ans therelay isleftin the statetherelay w as in w hen thefaultoccurred. 13. Press todisplayRelay Settings . NOT E: Ifallrelays are set,press to proceed to Se ction 4.4.2, 4–20 mA Settings.

4.4.1.2 Re lay#2 – norm aloperation orlead/lag pump control

NOT E: L ead/lag pum p controlprovides foran exchange oftheroleor function oftwo pump s in ordertoprovideforeven pum p we ar. The relay action is identicalto the Auto Empty Mod e or the Auto FillM ode;how ever,follow ing each pump shutdown,the lead/lagrole ofeach pum p isexchanged. 1. Press todisplayRelay # . 2. Ke y in ,press todisplayMode:Normal . NOT E: Ifrelay numb eris entered in error,press toreturnto Relay Settings. 3. Press or totogglebetween Normal and Lea dLag 1/2 , press . Th e operating statusofthe relay w illbe displayed. NOT E: Iflead/lag isselected,relays 1 and 2 willalternate.Whe n using lead/lag pum p control,set points cannot be identical; they must operatein thesam e direction.Re fertoFigure26. EchotelModel 344/345UltrasonicNon-contactTransmitter Pump II On Pump I On PumpII Off PumpI Off Pump I On Pump II On Pump I Off Pump II Off Pump II On Pump I On Pump II Off Pump I Off Cycle I CycleII CycleIII Figure27 Air Liquid Relay1, Energized Relay2, Energized Relays1 & 2, De-energized Figure26

4.4.1.3 R elay #3 – normaloperation orfaultdetection

  1. Press todisplayRelay#. 2. Ke y in ,press todisplayMode:Faul t . N OTE: Ifrelay num berisentered in error,press toreturnto R elay Settings. 3. Press or totogglebetw eenFaul t and Normal . 4. IfNo rmal,press and proceed to Step 7 in Section4.4.1.1 Relay#1 . 5. IfF ault,press to displayT'ducer . N OTE: Each ofthe follow ing m enu items ma y be selected to operate w ithR elay 3.U sing or ,toggle between Enabled and Disabled .Press tocontinue tonextitem. T’ducer The unitw as notable todetecta transducer connectedorw as notable todeterm inethe transducer’sfrequency. No Echo The unitis notable todetecta return signal from the transducer. Ringdown The transduceris ringing long enough toring beyond the blocking distance and intothespan. Lo op fl t The calculatedvalue fortheloop outputis less than 4 mA orgreaterthan20m A.The loop out - putw illbe in itsfail-safemo de. Temp. The signalfrom thetemperaturesensorin the transduceris outofrange.Eithera shortor open lead is detected. System This erroris generated w hen thereis an error writing configured values tonon-volatilememory. Faul tAction Energized De-Energized 6. With Faul t Action displayed,press . U sing or , togglebetween Energize orDe-Energize . 7. Press todisplayPrevious Menu ,press to display Relay Settings . N OTE: Ifall relays are set,press to proceed to Se ction 4.4.2, 4–20 mA Settings. EchotelModel 344/345UltrasonicNon-contactTransmitter

4.4.1.4 R elay #4– norma loperation orsam pler

  1. Press todisplayR elay#. 2. Ke y in ,press todisplayMode:Normal . NOT E: Ifrelay numb eris entered in error,press toreturnto Relay Settings. 3. Press or totogglebetw eenNormal and Sampler . 4. IfNo rmal,press and proceed to Step 7 in Section 4.4.1.1 Relay#1 . 5. IfSam pler,press . NOT E: The pulseduration is 90m illiseconds forthe contactclosure. 6. Press or totogglebetween Sample B y T ime or Sample By Flow ,press . IfSamp leBy F low ischosen, proceed tostep 10. NOT E: Sa mp leBy Time is only allowed withunitsordered with data logging option. 7. Interval 0000 isdisplayed. K eyin contactclosure timein minutes,press . 8. Press todisplayPassword?.Ke y inpassword. Relay Settings . NOT E: Ifallrelays are set,press to proceed to Se ction 4.4.2, 4–20 mA Settings. 10. FL W _ _ _. isdisplayed. K ey incontactclosurerate, press . NOT E: Sa mp leBy F low is a m om entary(90millisecond) contactclo - sure.Exam ple:If1000gallons is entered,relay 4 willenergize once forevery 1000gallons. 11. Press todisplayRelay Settings . NOT E: Ifallrelaysareset,press toproceed with 4–20 mA Se ttings. EchotelModel 344/345UltrasonicNon-contactTransmitter

4.4.2 4–20 mA Settings N OTE: 4–20m A settings isdependenton the choiceofMod e Setup designated inSe ction 4.3,System Co nfiguration . 1. Press to display 4: __. ,SetpointLe vel ,SetpointFlow or Setpoint Volume ,depending on the m ode thatthe unitisin. 2. Press or totogglebetw eenLev el ,Flow and Volume . 3. Press to display 4: __. K ey in value. 4. Press to display 20: _ _. K eyin value. 5. Press todisplayFailsafe . Press or to toggle between 4ma ,20mA ,22mA and H old . 6. Press todisplayPassword?.Ke y inpassword. 4– 20 Relay Settings . N OTE: Ifall4 –20m A Se ttings arecomplete,press toproceed with Section 4.4.3,Totalizer(Flow M od e only).

4.4.3 Totalizer(Flow Mo de only)

N OTE: The selected display units willdetermine the totalizer units. Exam ple:ifunitsaregallons and m ultiplieris100,forevery100 gallons the totalizer w illadvance once.Thisisthe we ight of each countofflow increm entshow n on themultipliertotalizer. 1. Press then or to togglebetween H ardware and Software . 2. Press . Ke y in multipliervalue. 3. Press todisplayPassword?.Ke y inpassword. 4. Press todisplayTotalizer . N OTE: R epeatthis procedureforthe rema iningoption (hardware or software). N OTE: The hardw are/software totalizingmultipliershould be chosen so thatatm axim um value,theadvance rateshouldnotexceed once perm inute.Minimum m ultiplieris0.01. N OTE: Ifpow erto theunitis rem oved,So ftwareTotalizerwillresetto zero,unless dataloggeroption w as ordered. EchotelModel 344/345UltrasonicNon-contactTransmitter

  1. 5 Advanced Configuration This m enu isused to calibratenon-controlparametersof theM odel344/345. Each men u item willprom ptfor Sup Pswd ? asa protection againstunauthorized changes. WAR NING : These values arefactorysetand shouldnotbe changed w ithoutconsulting thefactory. 1. Press todisplayMeasured Values . 2. Press todisplaySystemConfig . 3. Press todisplayI/O Config . 4. Press todisplayAdvanced Config . 5. Pres s then or to scrollthrough A dvanced Co nfigurationselections. Temperature Calibrate Gain Limit Dampening False T argets Set Clock EnterT ag Defaul t Display Calculation Change Password Change Sup Password Previous Menu Temperature 1. Press todisplaythe temp eraturesensed inside the trans - ducerin degrees°F (°C ifmetric levelunitsare chosen). 2. Ifthetransducerischanged orthe value seemstobe in error,enterthe correctvalueand press . 3. Di splaywillread Sup Password? ,yourchosen password mu stbe entered atthistime. Press . Calibrate 1. Press todisplaythe measured distance in the present unitsoflevel. 2. Iftheprocessisotherthanairand/ora know n distanceis available,enterthecorrectvalueand press . NOT E: This feature allow s the instrumentto be used with inert gas blankets w here the speed of sound differs significantlyfrom atmosp heric pressure. EchotelModel 344/345UltrasonicNon-contactTransmitter

N OTE: Ifcalibrate m ode is not properlyused,this m ay cause false levelreadings.C onsultfactory forresetprocedures. 3. Di splaywillread Sup Password? ;yourchosen password mu stbe entered atthistime. Press . Gain Limit 1. Press todisplaythe valueofMax imum gain thatthe unitwilluse. T hisvalue isfrom 1 –32and theunitstepsup insinglegainincrementsuntila suitablesignalisreceived. Lim itingtheMax Gai n to a lowervaluemay helplimit noise problems. 2. Enterany value betw een 1 and 32.Press . 3. Di splaywillread Sup Password? ,yourchosen password mu stbe entered atthistime. Press . N OTE: The Mo del344/345adaptsitsgaintosuittheconditions ofthe application.There are 32 gain steps.The higher the numb er, thehighergain/drive required todetectan acceptable signal. Dampening 1. Press todisplaythe valuedam pening. T hisfactorisa smoothingoraveraging factorforthe M odel344/345 out - put.The higherthenum ber,the more smoothingto improveperformance during rapid changes.T he value may be between 1 and 16. 2. Enterany value betw een 1 and 16. Press . 3. Di splaywillread Sup Password? ;yourchosen password mu stbe entered atthistime. Press . N OTE: The dam pening factor is a smo othing or averaging term . The 344/345averages echo values overa num berofprevious m easurementcycles.The damp ening factorinstructsthenum - berofcycles overw hich theunitshouldperform this average. Thus,thehigherthe dam pening factor,themore averaging and theslow eritreactstoa stepchange inlevel. EchotelModel 344/345UltrasonicNon-contactTransmitter

NOT E: C ontactthe factorypriortousing the F alseTargetsfeature. The false targetrejection feature allow sforsemi-automatic programm ing asfollows.The tank m ustbe emp ty orthe levelbelow any false targetsthatw illbe rejected. T he 344/345 willproceed tofind the firsttargetwhich provides a detectableecho. T he displaywillprom pttheusertoiden - tify each echo aseithera falsetargetorthe true distanceto theprocessm aterial. 1. Iftheecho resultsfrom a falsetarget,press . T he 344/345 willstore gainand distanceparametersabouteach targetthatwillallowittodiscern true levelsfrom falsetar - getechoes. The 344/345 willsuppressthistargetand increasegain untilthenexttargetisobtained. T hisprocedurecan be repeated untilallfalsetargetshavebeen acknow ledged. 2. Afterthetruedistanceisdisplayed,press . 3. The 344/345 w illpromp t“Press ” to saveallnew false targets. 4. Press tocontinue. 5. Di splaywillread Sup Password? ,yourchosen password mu stbe entered atthistime. Press . NOT E: Entering this m enu again w illrestartthe falsetarget selection and cleartheoldtargets. WAR NING : Make surethatallfalse targetsarecleared ordeleted from thesoftware.Press wh en T ar 0:___in is dis - played.Press and inputSup ervisoryPa sswo rd code. Set Clock This allows forsettingorchanging ofthe date and time. This isonlyavailablewiththe Data L ogging option. Unit prom ptsfor: Month? Date? Year? Hou r? (24 -hourform at) Minute? Afterentering these values,the unitprom pts to setand then requestspasswo rd. EchotelModel 344/345UltrasonicNon-contactTransmitter

This m enu shows the presentTag - M agnetrol. 1. Ifdesired,thistagcanbe changedby using or to scan through characters. 2. Press touse thecharacteratthatlocation in theTag. Pressingthe key w illstartscrolling oftheavailablechar - acters. Whe n closeto thedesired character,press and use arrows to reachdesiredcharacter. Defaul t Display This m enu allow stheoperatortoselectthe items tobe dis - played during normaloperation.T he following itemsmay be toggledEnabled/Di sabledusing or : Lev el Vol/Flow (Onlyw hen Volum e orFlow m ode ischosen) Lo op T ag Clock Calculation Totalizer The lastm enu item isPreviousMe nu. Ifany changew as mad e inthedefaultdisplay,pressing atthispointwill cause the unittopromp tfortheSup Pswd. Calculation 1. Press todisplayExisting Text Is . 2. Press againtodisplayText: . 3. EnterT extby using or and press ateachentry. D isplaywillthen read Mul t: . T hisisthe multiplierused to show up incalculation. T hisvalue ism ultiplied by your level,flow orvolume reading. N OTE: The calculation isintended for display purposes only.Itdoes notaffectthecontrolrelays orloop currentoutput. Change Password Allowsfora changeofpassword. R equirestheSup Pswd. Change Sup Password Allowsfora changeofSup Pswd . R equirestheSup Pswd. Previous Menu 1. Press toreturn tothe previousm enu,Advanced Config . 2. Press arrow toproceed to Di agnostics. EchotelModel 344/345UltrasonicNon-contactTransmitter

  1. 6 Diagnostics M enu This m enu isused to provide the userw ith testing the functionality and providing usefulinformation for troubleshootingoftheunit. 1. Press todisplayMeasured Values . 2. Press todisplaySystemConfig . 3. Press todisplayI/O Config . 4. Press todisplayAdvanced Config . 5. Press todisplayDiagnostics . 6. Pres s then or to scrollthrough Di agnostic selections. Test Relays Test 4– 20 L oop Signal Strength View Version# Extended Errors Previous Menu Test Relays This m enu allow stheoperatortocycleindividualcontrol relayson oroff. Test 4– 20 mA Lo op By entering differentvaluesintothe system, the actualloop currentoutputcanbe adjusted to testdependentdevices and/orcontrolloops. The entered mA value w illremain untilthe keyispressed. Signal Strength This m enu providesthe userw ith a gain value from 1 to32 (1=low gain/sensitivity,32=high gain/sensitivity)and a per - centreceived signalstrength from 0 to100% . T he 344/345 processorcontrolsthe signalstrength at60 –70% . T hisisa variable gain circuitw hich self-adjustsforan optim um signal return. View Version This isthesoftware version numbe rin the 344/345. Extended Errors This information m aybe requested during troubleshooting oftheunit. EchotelModel 344/345UltrasonicNon-contactTransmitter

4.7 Laptop Menu

This m enu isused to enterthe startand end day rangefor downloadingofstoreddata logforthe Mo del344/345 with optionaldata loggingfeature. 1. Press todisplayMeasured Values . 2. Press todisplaySystemConfig . 3. Press todisplayI/O Config . 4. Press todisplayAdvanced Config . 5. Press todisplayDiagnostics . 6. Press todisplayLa ptop . 7. Press todisplayStrt . Enterthe number oftheday(the mo strecentday)to begin dow nloading. The presentdayis alwaysday1. Data up to31 dayspriorto the currentday canbe downloaded. 8. Press and End willappear.K eyin the ending day. 9. Press ,Processing… w illbe displayed. Ifthelaptopis connected forRS-232and the baud rate iscomp atibleasset inthe I/O Con fig,theunitw illbegin to dow nloadthe start/end dayrange. SeeFigure 28atleft. N OTE: Thisisan updating 31 -day format.Itwilldownload the mini - m um ,m aximum (attimes ofoccurrence),and totalflow datafor selected days.Whe n thetransm ission ofdataiscom plete,the displayw illreturntoLa ptop. Any PC com mu nication program may be used tocapture thisdata.Startthecomm unicationsprogram. Setup as 8 bit,9600 Baud,1 stop bit. Selectdown loadfile(usually pageDO WN key),selectA SCII filetype. Refertoyour comm unicationsprogram docume ntation ifneeded.

5.1 Description

Mo del344/345 transmittersperform level,volume,oropen channelflowm easurementsofliquidsand slurries.

5.2 Theory ofO peration

Pulsesgenerated by the electronicsaretransm itted tothe ultrasonictransducer.T he transducerdirectsan ultrasonic pulseto theliquidsurface.The returning echo/signalis detected by the transducer. T he electronicsconvertthesig - nalintoa digitalrepresentation ofthe level,flow orvolume me asureme nt. EchotelModel 344/345UltrasonicNon-contactTransmitter TB2 (344/345Transmitter) DB 25F Connector (Laptop) RX TX 3 Figure28

40 EchotelModel 344/345UltrasonicNon-contactTransmitter

Ch eck forthe following applicationsensitivitiesbeforeproceedingtothe nextsection: VAP OR S INVISIBLE (may alterspeed ofsound) VISIBLE (may cause falsereflections or attenuation) FOAM SURF ACE AGITAT ION A NGLE OF RE POSE TEMP ERA TURE PRE SS URE OB STR UCTIO NS Ifany ofthe above sensitivitiesarepresent,consultthefactoryforrecom mendat ions.

5.3 Troubleshooting

  1. _____ Wa s Belden 8102used? Ifnot,improperopera - tion ma y occur. 2. _____ Istransducerwiringrunina dedicated conduit? 3. _____ Isshieldconnectedatbothends? TR AN SDUC ER 1. _____ Chec k transduceralignment(vertical) 2. _____ Istransducerm ounted hand tight? O vertight - ening m ay cause ringing,some installations ma y requireuse ofa “shock”absorber. 3. _____ Minimum nozzlediameter8 inches. 4. _____ Ma ximum nozzleheight11inches. 5. _____ Chec k beam path forobstructions,including tank w all.R efertoS ection1.4forS onicBeam D ispersion chart. 6. _____ Chec k transducerhousing form oisture. 7. _____ W hatisthe distancefrom thetransducerface to currentlevel? PRO C ES S 1. Wh atisthe temperature? PRO CES S cont. 3. _____ D oes thetank have a mixingblade?Could it be providingfalselevelreadingsorcreatinga vortexresultinginecho loss. 4. _____ Istherean angleofrepose? (Solids) NOTE : R efertoS ection5.7,Measu rement Range Calculations ,ifany ofthepoints intheP ROCESS sectionhave been checked. TRA N SMITTER Enterthe specifiedm enu and obtainthefollowinginforma - tionbeforeconsultingthefactory. M EA SUR ED VA LUES M ENU S Y ST EM CONFIGURATION AD VA NCED CONFIGURATION D IAGNOS TICS M ENU 1. Transmitteris II indoors II outdoors? 2. W hat is the transmitter serial num ber? INST AL LA TION CHECKL IST F ollowing these five steps will assist in troubleshooting application difficulties with Model 344/345: Step 1: Application Checklist – review fundamental application parameters Step 2: Installation Checklist – review typical installation problems Step 3: Troubleshooting Table – explains diagnostic error conditions shown on the LCD display and some typical electronic problems. Step 4: Troubleshooting Flowchart – step-by-step procedure Step 5: Contact factory.

C OMM PARAM FAIL The configuration parameters for Press ENT to continue. This loads default values for the the com mu nications port are commu nication parameters. The configuration parameters corrupt. should be checked to make sure that they match your application. M AIN PARAM FAIL The ma in parameters which Press ENT to continue. This will load default values for the main store range/reference and parameters. All of the items in the System Config menu need to be span/headroom are corrupt. verified. S TRA P TABLE FAIL There is an error in the custom Press ENT to continue; the table is cleared. If a custom table is not strapping table entry. being used, then this error can be ignored. If you are using a custom table, the table has to be re-entered. RL Y 1 PAR AM F AIL The parameters for Relay 1 are Press ENT to continue. The relay is disabled and the settings are set corrupt. to default values. Reconfigure the relay from the I/O Config menu. RL Y 2 PAR AM F AIL The parameters for Relay 2 are Press ENT to continue. The relay is disabled and the settings are set corrupt. to default values. Reconfigure the relay from the I/O Config menu. RL Y 3 PAR AM F AIL The parameters for Relay 3 are Press ENT to continue. The relay is disabled and the settings are set corrupt. to default values. Reconfigure the relay from the I/O Config menu. RL Y 4 PAR AM F AIL The parameters for Relay 4 are Press ENT to continue. The relay is disabled and the settings are set corrupt. to default values. Reconfigure the relay from the I/O Config menu. L OO P PAR AM F AIL The 4 –20 mA loop parameters Press ENT to continue. The loop is disabled and the settings are set are corrupt. to default values. Reconfigure the relay from the I/O Config menu. C AL C PA R AM FAIL The calculation parameters are Press ENT to continue. New values need to be entered for the corrupt. calculation. This is done from the Calibration menu. PASS WOR D LOS T The passwords are corrupt. Press ENT to continue. Enter new passwords from the Calibration menu . D ATA LOG LOST The data log is corrupt. Press ENT to continue. The data log is cleared. Microprocessor internal register able to set the register to the proper value and will function properly. w as not set correctly on power up. The softwa re will attempt to set the register to the proper value TRAN S DUCER FAIL The unit was not able to detect Ensure that the transducer is connected properly to the unit. a transducer connected or was If the transducer wiring is properly connected, contact factory for not able to determine the replacement transducer. transducer's frequency. L OS S OF ECHO The unit is not able to detect a Ensure that the level to be detected is within the range and span of return signal from the transducer. the unit. Check the application for foam, obstructions, or heavy vapors. Display Problem Solution

5.3.1 Troubleshooting System P roblem s

41 Echotel Model 344/345 Ultrasonic Non-contact Transmitter

42 Echotel Model 344/345 Ultrasonic Non-contact Transmitter

RIN GD OW N ER RO R The transducer is ringing long Decrease the span to increase the blocking distance (range enough to ring into the span of minus span) of the unit. the unit. R eplace the transducer (the current transducer may have a problem that causes it to ring too long. TEM PERAT URE FAULT The signal from the temperature Check to see that the sensor wires are connected properly. sensor in the transducer is out of Ensure that the sensor wires are not shorted or open. range. Either a short or open lead detected. O PE RATION D ENIE D The current operation is not Retry the proper passwo rd. allow ed because the proper passw ord was not entered. “OUT OF R ANGE” The value that was entered was Re-enter a value within the proper limits. not in an acceptable range. C ANN OT BE EQUA L The value for the 4 mA point Choose the values that are not the same and re-enter. and the 20 m A point cannot be equal. INV AL ID LEAD/L AG Setting relay 1 and 2 for Check that both relays are enabled and that the set points are lead/lag is not allowed. proper for lead/lag operation. PAS SWOR D INVAL ID The password entered is Retry the previous operation and enter the proper password. not valid. N O C LOCK PRES ENT The real time clock was not If you need the real time functions, contact the factory to see if found on the board. your unit was ordered with the data logging option. N o data logging or time samp ling is allowed. L OO P > 20 mA The calculated value for the If the level is within a normal operating range, adjust the loop loop output is greater than parameters to allow proper tracking of the level. If the level is out 20 mA . The loop output will be of the normal 4 –20 m A range then correct the problem with the in its fail-safe mod e. level. L OO P < 4 mA The calculated value for the If the level is within a normal operating range, adjust the loop loop output is less than 4 m A. parameters to allow proper tracking of the level. If the level is out The loop output will be in its of the normal 4 –20 mA range then correct the problem with the fail-safe mode. level. F aint display Disp lay is too dim or Turn the CONTR AS T adjustment potentiometer clockwise to too light darken the display or counterclockwise to lighten the display, until the desired contrast is obtained. The CONTRAST pot is located on the top left of the motherboard above the ribbon cable connection. 1/2 display lit Only half of display is lit If a new PC b oard was recently purchased, it may be incompati - ble with the other boards. In this case, the JP9 jumper on the m otherboard (underneath daughterboard) should be moved to the other position. Display Problem Solution

43 Echotel Model 344/345 Ultrasonic Non-contact Transmitter

IS LED D10 LIT ON M OTHER BO ARD ? • CHE CK P OWE R SUP PLY

  • CHE CK FUS E IS LC D DIS PLA Y ON? • CHECK RIBBON CABLE
  • AD JUST CONTRAST POT (SEE SECTION 5.3.1)
  • CHECK BOA R D CONNECTION AC CE SS DENIED TO PROGRA MM ING • VER IFY PAS S WORD IS DISPLAY S HO W ING LOS S OF ECHO RIN GD OW N E R ROR TEM P . FAULT TR AN SD UCE R FAIL ?
  • CHECK TRANSDUCER WIRING
  • CHECK RANGE AND SPAN SETTINGS
  • M AK E S UR E TARGET IS NOT BEYOND R ANGE OR ABOVE SPAN
  • IF S.S. S ENS OR, MAKE SURE PLASTIC P R OTECTIVE COVE R HAS BEEN REMOVED IS LEVE L R EADING C O RRECT ? • CHECK RANGE AND SPAN SETTINGS
  • CHECK TEM P ERATURE READING ARE REL AYS OPE R ATING PROPE RLY? • CHECK RELAY PROGRAM MING
  • M AK E S UR E UNIT IS READING COR R ECT LEVEL IS 4 –20 M A OUTP UT CORRECT? • CHECK 4 –20 MA PROGRAM SETTINGS
  • M AK E S UR E UNIT IS READING COR R ECT LEVEL
  • LOOP POW ER IS SUPPLIED BY 344/345 M AK E S URE LOAD IS IN PASSIVE MODE
  • LOOP RES ISTANCE M UST BE <1000 OHMS UN IT IS OP ER ATING CORRE CTLY CO NTA CT FACTO RY If it becomes necessary to contact the factory for technical assistance, please have all of the information gathered in S teps 1-4 readily available. This will help us in resolving the problem. YES YES N O N O YES YES YES NO NO NO N O NO YES YES

5.3.2 Troubleshooting Flow C hart

5.4 Agency Approvals

FM 34X-X442-10X Non-h azardous NE MA 4X, IP65 Non-incendive Class I, II, III, Div. 2; Groups A, B, C, D, F , & G, T4A 384-XKXX-0XX Non-h azardous NEMA 4X , IP65 Explosion proof Class I, II, III, Div. 1; Groups B, C, D, E, F , & G, T6 385-XXXX -XXX Non-h azardous NEMA 4X , IP65 385-XEXX -006 Explosion proof Class I, II, III, Div. 1; 385-XEXX -010 Groups B, C, D, E, F , & G, T6 385-XEXX -003 Explosion proof Class I, II, III, Div. 1; Groups A, B, C, D, E, F , & G, T6 CSA 34X-X442-10X Non-h azardous Type 4X enclosure 344-X442-10X Non-incendive Class I, II, III, Div. 2; Groups A, B, C, D, E, F , & G, T4A 384-XKXX-0XX Non-h azardous Type 4X enclosure 384-XK0X-0XX Explosion proof Class I, II, III, Div. 1; Groups B, C, D, E, F , & G 384-XK1X-0XX Explosion proof Class I, II, III, Div. 1; 384-XKYX -0XX Groups C, D, E, F , & G 385-XXXX -XXX Non-h azardous Type 4X enclosure 385-XE1X-0XX Explosion proof Class I, II, III, Div. 1; 385-XEY X-0XX Groups C, D, E, F , & G 385-XE0X-0XX Explosion proof Class I, II, III, Div. 1; Groups A, B, C, D, E, F , & G A GE NC Y M ODEL APP RO VE D APPROVAL CATEGORY APPROVAL CLAS SES These units have been tested to EN 50081-2□ and EN 50082-2 and are in compliance with□ the EMC Directive 89/336/EEC.

44 Echotel Model 344/345 Ultrasonic Non-contact Transmitter

S upply voltage 120 VAC +10%/-15%, 50–60 Hz

24 VD C , ±20%

Po w er consumption 12 w atts (without heater) F use size 1⁄4 amp replaceable, 250 VAC Slo-Blo ® for AC units 2 amp replaceable, 250 VDC Slo-Blo for DC units Ou tput signal 4–20 mA isolated (1,000 Ω load), RS-232 R elays F our 10 am p resistive, SPDT F ail-safe User selectable for analog and relay outputs Disp lay Sixteen (16) character alphanume ric LCD Keypad Sixteen (16) button integral to front panel Enclosure material High-impact polycarbonate Weig ht 8 pounds (3.6 kg) R esponse time 2 seconds typical Accuracy ± 0.25% of calibrated span Hu midity 95% Non -condensing Am bient tempe rature without heater & thermostat* -4° to +160° F (-20° to +70° C ) with heater & thermo stat -40° to +160° F (-40° to +70° C) *The 31-day data logger has a +32° F (0° C) minimum w hen used without the heater and thermostat. 5 .5.2 Transducer Mo del 384 Model 385 Transducer frequency 38 kHz 50 kHz Max imum range 35 feet (10.7 meters) 25 feet (7.6 meters) Max imum span 33.5 feet (10.2 meters) 24 feet (7.3 meters) Minimum dead band 18 inches (460 mm) from 12 inches (305 mm ) from 18 inches (460 mm) from Op erating tem perature -40° to +163° F (-40° to +73° C) -40° to +200° F (-40° to +93° C) Op erating pressure -10 to +50 psig (-0.69 to +3.45 bar) Tempe rature compen sation Automatic, over the operating temperature range of the transducer Beam angle 12° conical Cab le length 500 feet (152 meters) ma ximum between transducer and transmitter

45 Echotel Model 344/345 Ultrasonic Non-contact Transmitter

5.5 Specifications

5.5.1 Transmitter

46 Echotel Model 344/345 Ultrasonic Non-contact Transmitter

5 .5.3 Physical Inches (mm ) M odel 344/345 Transmitter Mod el 385 Transducers 9.50□ (241) 9.50□ (241) 13.00□ (330) 6.00□ (152) 6.75□ (171) Optional□ Mounting□ Flange 3.00□ (76) 4.63 (118)□ Dia. 2.75□ (70) 4.00□ (102) 3.00 (76),□ 6.00 (152) or□ 10.00 (254)□ depending□ upon model 3/4" NPT2" NPT 2"□ NPT 3.00 (76),□ 6.00 (152) or□ 10.00 (254)□ depending□ upon model 3/4"□ NPT 3/4"□ NPT 6.00 (152) or□ 10.00 (254)□ depending□ upon model 3/4"□ NPT 3.00□ (76) Figure 31 2" NPT Transducer with Ho using Figure 30 Side View Figure 32 3⁄4" and 2" NPT Transducer without Housing Figure 29 Front View

48 Echotel Model 344/345 Ultrasonic Non-contact Transmitter

5.6 Replacement Parts

Item Description Part Number

1 NEMA 4 X enclosure, LCD display, keypad with hardware Consult Factory

2 Enclosure gasket 012-1606-001

3 Main P.C. board

120 VAC Z30-3564-001

120 VAC w ith data logger Z30-3564-007

240 VAC Z30-3564-002

240 VAC w ith data logger Z30-3564-008

24 VD C Z30-3564-003

24 VD C with data logger Z30-3564-009

4 Daughter P.C. board Mod el 344 Z30-3573-001 Mod el 345 Z30-3565-001 5 Display P.C. board Z30-3539-002

6 Transducer housing base

NE MA 4X, aluminum 004-9104-001 NE MA 4X, stainless steel 004-9140-001

7 Transducer housing cover

NE MA 4X, aluminum 004-9105-001 NE MA 4X, stainless steel 004-9142-001

8 O-ring 012-2101-345

9 Transducer P.C. board 030-3515-001

10 Bracket 005-6634-001

11 Transducer Refer to Section 5.8, Model Num bers Transducer mount bracket Wal l mount, 3⁄4" male N PT 036-3812-002 Wal l mount, 2" female NPT 036-3812-001 Floor mount, 3⁄4" m ale NP T 036-3813-002 Floor mount, 2" female NP T 036-3813-001

Mo del 384 Transducer without housing Figure 41 Mod el 384 Transducer with Hous ing Figure 38 Transm itter Optional□ Mounting□ Flange Optional□ Mounting□ Flange Optional□ Mounting□ Flange Figure 42 Mo del 385 Transducer with Housing Figure 40 M odel 385 Transducer without housing Echotel Model 344/345 Ultrasonic Non-contact Transmitter

50 Echotel Model 344/345 Ultrasonic Non-contact Transmitter

5.7 Meas urement Range Calculations

U ltrasonic non-contact devices are typically rated for a ma ximum rang e in ideal conditions. Exp erience has shown that ma ximum range must be red uced for certain factors. Although the max imum rang e rating is somewh at conserv - ative, each application must be evaluated for specific con - ditions in the tank. H O W T O C A L C U L A T E To evaluate the performa nce of a 344 or 345 in a particular application, use the chart on the next page and follow the steps below: 1. Select one condi tion from each of the o perating param eters that best describes your app lication. 2. Enter the corresponding perform ance mu ltiplier value in the application co lumn. 3. M ultiply all of the selected values together. 4. Mu ltiply step 3 by the m aximum po tential range of the unit. This yields a value that is the m aximum allowa ble meas uremen t range for the ap plication. E X A M P L E The vessel is a closed-top tank, 26-feet tall and is filled from the top. Surface agitation Expect slight agitation from fill line. Performan ce multiplier 0.9. Vapo r and steam The process temperature is +130° F , slight vapor is expected. Pe rforma nce multiplier 0.9. Beam interference No interference exists. Performa nce multiplier 1.0. Transducer alignment The transducer will be perpendicular to the liquid surface. Pe rforma nce multiplier 1.0. Fo am None . Performance mu ltiplier 1.0. Dust No ne. Performan ce multiplier 1.0. Air mo vem ent No ne. Performan ce multiplier 1.0. Amb ient temperature 0 to +120° F . Performan ce multiplier 1.0. Pressure Atmosphe ric pressure. Performance multiplier 1.0. Wi ll the Model 344 wor k for this app lication? C A L C U L A T I O N Mu ltiply all values in the app lication colum n: The calculation yields 28.35 feet as the new maximum range. Since the tank is 26 feet tall, this application wi ll give satisfactory results with the Mo del 344. NOT E: The performance multipliers provided are conservative estimates. Since these factors are subjective, the values have been designed to provide very high confidence of system success. Contact the factory if there are any questions concerning the interpretation of any of these performance multipliers. Sensor alignment Temperature□ Pressure Beam spread□ interference Beam spread□ interference Air movement Dust Vapors Foam Surface□ agitation

Operating Parameter Condition Performance Application Multiplier SURFACE AGITATION: Surface agitation or waves can degrade the Smooth, glasslike surface 1.0 performance. Moderate agitation results in only slight degradation Slight agitation, choppiness 0.9 of performance. The worst case is when the surface is a good Heavy agitation 0.8 reflector, but in the wrong direction. (See also transducer alignment.) Slight vortex (6°) 0.7 VAPORS AND STEAM: Vapors in the air space, above the process, become apparent, and cause problems when the liquid process No condensation 1.0 temperature is well above the temperature of the airspace. The greater the difference, the more expected vapor problems. The problems result from condensation or layering in the sound path, both of which attenuate the sound signal, degrading performance Little condensation 0.9 To avoid these problems, ensure that the vessel is insulated so that vapors are less likely to condense. If a vent is used, be sure that the Much condensation/ 0.8 vent, which is where condensation will form, is well away from the foggy appearance transducer. BEAM SPREAD INTERFERENCE: It is strongly recommended that No interference 1.0 nothing be allowed within the transducer’s beam, except the liquid which is being monitored. Often, the signal from the liquid will be Agitator at speed less than 60 RPM 1.0 strong, compared to the signal from other sources, such as ladder rungs, filling process material, support struts, etc. For that reason, Agitator at speed greater than 60 RPM Consult some applications may provide satisfactory results, even with Factory interference. Interference from agitator blades is only an intermittent interference that usually has little effect on performance. Interference outside 4°, far from 0.8 It is recommended there be no interference within the 6° half angle of transducer (in bottom third of range) the transducer beam. If interference is unavoidable, make the inter- ference as far as possible from the transducer so that the real signal Interference outside 4°, near to 0.5 at the longest distance is stronger than the interference signal. transducer (in top third of range) TRANSDUCER ALIGNMENT: Optimum performance is obtained when Beam perpendicular to liquid surface 1.0 the transducer is perfectly aligned. If the process is not perpendicular to the sound beam, the sound will not reflect properly back to the transducer. The effect is significant. Beam 4° off from perpendicular 0.5 FOAM: Even small thicknesses of foam can attenuate the ultra- No foam 1.0 sound and render the system inoperative. If possible, moving the Light froth, less than 0.25" thick 0.8 transducer to an area in the tank where there is less foam will improve the performance. Thick, heavy-density foams can sometimes produce Light foam, less than 0.5" thick 0.5 a reflection from the top of the foam. The multipliers shown at right Light foam, more than 1" thick 0.1 are general guidelines. For further assistance consult the factory. DUST: Dust attenuates the sound and results in poor performance. No dust 1.0 Even barely perceptible haze in the air can cause significant Haze, barely perceptible 0.7 attenuation. Slight dust 0.4 Heavy dust 0.1 AIR MOVEMENT: The movement of air, as possible in an open top No air movement 1.0 vessel, can create a layer from which the sound will reflect. This will Open vessel, but transducer below rim 0.8 be most noticeable in applications where vapors or steam tend to form. Open air movement in sound path 0.7 AMBIENT TEMPERATURE: The ambient temperature can have a -20° to +140° F (-29° to +50° C) 1.0 significant effect on the sound and on the transducer’s capability to -40° to -20° F (-40° to -29° C) 0.9 transmit and receive sound. The most noticeable effect on the transducer is at the temperature extremes. +140° to +160° F (+50 to +70° C) 0.9 PRESSURE: Sound requires air molecules to be able to travel. Sound -10 to +50 PSIG (0.689 to +3.45 Bar) 1.0 will not travel in a vacuum. Likewise, higher pressures will allow the sound to continue without decay, which can cause problems with Pressures outside above rating Consult multiple echoes. Factory Multiply all values together in the application column Multiply by maximum potential range (35 feet for Model 344 or 25 feet for Model 345 ) X Maximum allowable measurement range for this application = Echotel Model 344/345 Ultrasonic Non-contact Transmitter

5.8 Mod el Number s

5 .8.1 Transmitter

52 Echotel Model 344/345 Ultrasonic Non-contact Transmitter

5.8.2 M odel 384 38 kHz Transducer

0 N one

1 Mec hanical totalizer

3 Mec hanical totalizer & 31-day data logger

0 120 VAC , 50/60 Hz 1 240 VAC , 50/60 Hz 2 24 VDC 3 120 VAC with heater and thermo stat 4 240 VAC with heater and thermo stat

344 Ultrasonic non-contact transmitter, used with Model 384 transducer

345 Ultrasonic non-contact transmitter, used with Model 385 transducer

2 1" NPT , not available with transducer housing code 1 or Y 5 2" NPT K Kynar ® PR O C ESS CON NEC TION TR ANS DUCER MOU NTING BR A CKET 384 K

0 No mounting bracket

3 Wal l mount bracket for 2" NPT process connection only

4 Floor mount bracket for 2" NPT process connection only

TR AN SDUCER INSER TIO N LENGTH 003 3" (76 mm ) length 010 10" (254 mm ) length TR AN SDUCER MATER IAL 0 No housing, 35' (10.7 m) of cable potted into transducer

1 Ca st alum inum , NEMA 4X/ 7/9 housing with 3⁄4" NPT single conduit,

connecting cable ordered separately Y 316 stainless steel, NEMA 4X/7/9 housing with 3⁄4" NPT single conduit connecting cable ordered separately

5.8.3 M odel 385 50 kHz Transducer

10 feet (3 m ) minimum , 500 feet (152 m) maximum length. Example: 12 foot cable length = Code 012

5.8.4 Co nnecting Ca ble

TR AN SDUC ER MO UNTI NG BR A CKET 385 TR A NSDUC ER INSER TIO N LEN GTH TRA NS DUCER MATERI AL TR AN SDUC ER HO USING 003 3" (76 m m ) length 006 6" (152 mm ) length 010 10" (254 mm ) length

0 No m ounting bracket

1 W all m ount bracket for 3⁄4" NP T process connection only

2 Floor mount bracket for 3⁄4" NP T process connection only

3 W all m ount bracket for 2" NPT process connection only

E 316 stainless steel (for use in hazardous environments, refer to agency approvals) ⁄4"N P T, not available with transducer housing code 1 or Y 5 2" NP T 0 N o housing, 35' (10.7 m) of cable potted into transducer

1 C ast aluminum, NEMA 4X/7/9 housing with 3⁄4" NP T single conduit,

connecting cable ordered separately Y 316 stainless steel, NEMA 4X/7/9 housing with 3⁄4" NP T single conduit connecting cable ordered separately Echotel Model 344/345 Ultrasonic Non-contact Transmitter

Echotel Model 344/345 Ultrasonic Non-contact Transmitter Notes

Echotel Model 344/345 Ultrasonic Non-contact Transmitter Notes

BULLETIN: 51-629.5 EF FECTIV E: July 2010 SU PERSEDE S: January 2000 5300 Belmon t Road • Downers Grove, Illinois 605 15-4499 • 630-969-400 0 • Fax 630-969-9489 • www.magnetrol.com

145 Jardin Drive, Units 1 & 2 • Concord, Ontario Canada L4K 1X7 • 905-738-9600 • Fax 905-738-1306

Heikensstraat 6 • B 9240 Z ele, Belgium • 052 45.11.11 • Fax 052 45.09.9 3 Regent Bu siness Ctr., Jubilee Rd. • Burgess Hill, Sussex RH15 9TL U.K. • 01444-871313 • Fax 01444-871317 Copyright © 2010 Magnetrol International, I ncorporated . All rights reserved. Printed i n the USA. Service Policy Owners of Mag netrol controls may request the return of a control or any part of a control for complete rebuilding or replaceme nt. T hey will be rebuilt or replaced prompt - ly. C ontrols returned under our service policy mus t be returned by Prepaid transportation. Magnetrol w ill repair or replace the control at no cost to the purchaser (or owner) other than transportation if: 1. R eturned within the w arranty period; and 2. T he factory inspection finds the cause of the claim to be covered under the warranty. If the trouble is the result of conditions beyond our con - trol; or, is N OT covered by the w arranty, there will be charges for labor and the parts required to rebuild or replace the equipme nt. In som e cases it may be expedient to ship replacement parts; or, in extreme c ases a comp lete new control, to replace the original equipmen t before it is returned. If this is desired, notify the factory of both the model and serial numbers of the control to be replaced. In such cases, cred - it for the materials returned will be determined on the basis of the applicability of our warranty. No claims for misapplication, labor, direct or consequen - tial damage will be allowed. Return Material Procedure So that we m ay efficiently process any materials that are returned, it is essential that a “R eturn Ma terial Authorization” (RMA ) num ber be obtained from the fac - tory, prior to the m aterial’s return. T his is available through M agnetrol’s local representative or by contacting the factory. Please supply the following information: 1. Co mpan y Name 2. D escription of M aterial 3. S erial Num ber 4. R eason for R eturn 5. A pplication An y unit that w as used in a process m ust be properly cleaned in accordance w ith O SHA standards, before it is returned to the factory. A M aterial Safety D ata Sheet (M SD S) m ust accompany material that was used in any m edia. All shipments returned to the factory must be by prepaid transportation. All replacem ents will be shipped F .O .B. factory. ASS UR ED QU AL ITY & SER VICE COST LESS Mag netrol, Magnetrol logotype, and Echotel are registered trademarks of Magnetrol International. Teflon is a registered tradem ark of DuP ont. Kynar is a registered tradem ark of Arkema, Inc. Slo-Blo is a registered tradem ark of Littelfuse, Inc.