Visit product website DATA SHEET Type 8006 Mass Flow Meter (MFM) Type 8008 Flowmeter for gases Type 8746 Mass flow controller (MFC) / Mass flow meter (MFM) for gases Type 8611 eCONTROL - Universal controller Standard | EU | en | 2023-11-06 | 23 Electromotive 2-way globe proportional valve
- Actuator isolated from flow path Excellent range and fast response times Low power consumption Connection orifice DN 15...25 Variants: standard, positioner, process controller The direct-acting Type 3285 motor valve is suitable for dosing liquids and gases in closed or open control loops. The valve is driven by a stepper motor. The integrated electronics assembly simplifies the process integration; additional actuation mod- ules are not necessary. The engine does not need any energy to maintain a certain valve opening. This feature can reduce the energy consumption of a plant dramat- ically and therefore make it more efficient. Type 3285 is available as an ON/OFF valve or proportional valve by default, as a variant with integrated positioner, and as a variant with integrated process controller. Product variants described in the data sheet may differ from the product presentation and description. Type description Can be combined with Type 3285 © Christian Bürkert GmbH & Co. KG, Subject to alteration
2 | 15Visit product website Table of contents 1. General technical data 3 1.2. Electrical control and interfaces .... 2. Approvals and conformities 5 2.2. Conformity ... 2.3. Standards .... 2.4. North America (USA/Canada) ... 2.5. Drinking water .... 2.6. Others Oxygen 3. Materials 6 3.2. Material specifications ... 4. Dimensions 7 4.2. Capacitive buffer module 5. Device/Process connections 9 5.2. Digital (fieldbus) 6. Performance specifications 10 6.2. Pressure range .... 6.3. Flow characteristic Exemplary characteristic curve of the motor valve 7. Product operation 12 Product accessories 8.2. Bürkert Communicator Software ... Connection Type 3285 with Bürkert Communicator software 9. Ordering information 14 9.2. Recommendation regarding product selection.... 9.3. Bürkert product filter 9.4. Bürkert Product Enquiry Form ... 9.5. Ordering chart accessories .... Standard accessories Accessories cable Bürkert accessories
3 | 15Visit product website 1. General technical data 1.1. General Product properties Dimensions Further information can be found in chapter “4. Dimensions” on page 7 Material Further information can be found in chapter “3.2. Material specifications” on page Valve body Brass or stainless steel Seal • NBR for liquids EPDM for liquids and special gases (e. g. ammonia, acetylene) FKM for neutral gases Seat sealing Technical ceramics Design • Disc On/Off valve Disc control valve Connection nominal diameter DN 15… DN 25, NPS ½…1 Safety setting in case of power failure With capacitive buffer module as accessory, see chapter “4.2. Capacitive buffer module” on page Flow direction Above seat Controller variant Standard On/Off, standard control valve, position controller or process controller Weight ~ 0.8 kg (DN 8)…1.5 kg (DN 25) Status display LED (Refer to the instruction manual for more information.) Performance data Typical values of positioning behaviour1.) Dead band of the position control ± 0.5 % (corresponds to setting range 1:100) Closing time 4 s Operating pressure 0…6 bar(g) (see chapter “6.2. Pressure range” on page 10 Vacuum version (up to - 0.9 bar(g)) (optional) KVS value 1.8…9.6 m³/h (see chapter “6.2. Pressure range” on page 10 ) Electrical data Operating voltage 24 V DC ± % (max. residual ripple 10 Duty cycle Up to 100 % (depending on medium and ambient temperature) Power consumption < W in holding position Max. 12 W (depending on motor control) Medium data Operating medium Neutral gases, liquids Medium temperature • EPDM (seal material): - °C…+ FKM, NBR (seal material): 0 °C…+ Viscosity Max. 80 mm²/s (cSt) Process/Port connection & communication Port connection Threaded connection G (EN ISO 228 NPT (ASME B 1.20.1) Communication and control Standard signal (analogue) Setpoint: 0/4…20 mA, 0…5/10 V and digital input, see chapter “1.2. Electrical control and inter- faces” on page 4 Fieldbus (digital) • Bürkert system bus (büS) CANopen (optional) EDIP Field device for integration into the EDIP platform via Bürkert system bus (büS) Further information can be found in chapter “8.2. Bürkert Communicator Software” on page 13 Approvals and conformities Degree of protection IP50 North America (USA/Canada) Further information can be found in chapter “2.4. North America (USA/Canada)” on page 5 Drinking water Further information can be found in chapter “2.5. Drinking water” on page 5 Others Further information can be found in chapter “2.6. Others” on page 5
4 | 15Visit product website Environment and installation Installation position As required, preferably with actuator upright Ambient temperature - °C…+ (Derating see chapter “6.1. Duty cycle derating diagram” on page 10 1.) The characteristic values of the control behaviour depend on the operating conditions and refer to the final value. 1.2. Electrical control and interfaces Technical data Device variant Standard (G/H) Positioner (C) Process controller (D) ON/OFF (G) Control valve (H) 1.) Analogue Digital (fieldbus) Analogue Digital (fieldbus) Electrical connection M12 plug, A-coded, 8-pin M12 plug, A-coded, 8-pin M12 plug, A-coded, 8-pin M12 plug, A-coded, 5-pin M12 plug, A-coded, 8-pin and M12 socket, A-coded, 5-pin M12 plug, A-coded, 5-pin and M12 socket, A-coded, 5-pin Input signal (setpoint) Digital input: 0…5 V (log. 0, valve closed) or 10…30 V (log. 1, valve open) 4…20 mA, 0…10 V or PWM (800 Hz) min: 10 V | type: V | max: 30 4…20 mA, 0…20 mA, 0…10 V or 0…5 V – 4…20 mA, 0…20 mA, 0…10 V or 0…5 V Input signal (actual value from ext. Sensor) mA, 0…20 mA, 0…10 V or 0…5 V 4…20 mA, 0…20 mA, 0…10 0…5 V or frequency (5…2000 Hz) Input imped- ance for analogue input 22 kΩ 60 Ω (current), 22 kΩ (voltage) 60 Ω (current), 22 kΩ (voltage) – 60 Ω (current), 22 kΩ (voltage) 60 Ω (current), 22 kΩ (voltage) Output signal (actual value) Digital output: PNP, max. 100 mA current limits, feedback function (output signal active, when valve closed) Digital output: PNP, max. 100 mA current limits, feedback function (output signal active, when valve closed) 0/4…20 mA (max. load: 560 Ω), 0…5/10 V (max. current: mA) – 0/4…20 mA (max. load: 560 Ω), 0…5/10 V (max. current: mA) Fieldbus interface – – – büS/CANopen – büS/CANopen Parameteriza- tion Tool – – Bürkert Communicator (Connection via büS stick) Bürkert Communicator (Connection via büS stick) Bürkert Communicator (Connection via büS stick) Bürkert Communicator (Connection via büS stick) 1.) The standard control valve variant is a proportional valve which, like the positioner variant, changes the valve stroke continuously depending on the input signal. This variant has no büS interface and no analogue output signal.
5 | 15Visit product website 2. Approvals and conformities 2.1. General notes
- The approvals and conformities listed below must be stated when making enquiries. This is the only way to ensure that the pro duct complies with all required specifications. Not all available versions can be supplied with the below menti oned approvals or conformities. 2.2. Conformity In accordance with the Declaration of conformity, the product is compliant with the EU Directives. 2.3. Standards The applied standards which are used to demonstrate compliance with the EU Directives are listed in the EU-Type Examination Certificate and/or the EU Declaration of Conformity. 2.4. North America (USA/Canada) Approval Description Optional: UL Listed for the USA and Canada The products are UL Listed for the USA and Canada according to: UL 429 (Electrically operated valves) CSA C22.2 No. 139 (Electrically operated valves) 2.5. Drinking water Conformity Description Optional: Certification according to 1+ system of UBA (valid for variable code PF23) The materials comply with the assessment principles (UBA) for materials in contact with drinking water (Trinkwas serV). 2.6. Others Oxygen Conformity Description Oxygen In their composition, the products are suitable for use with gaseous oxygen (optional).
6 | 15Visit product website 3. Materials 3.1. Bürkert resistApp Bürkert resistApp – Chemical resistance chart You want to ensure the reliability and durability of the materials in your individual application case? Verify your combination of media and materials on our website or in our resistApp. Start chemical resistance check 3.2. Material specifications Note: The globe control valve Type 3285 is supplied with various port connections. These connections are not shown completely. However, they correspond to the material of the valve housing. Actuator No. Element Material
1 Housing cover PC (Polycarbonate)
2 Housing base PPS (Polyphenylene sulfide)
No. Element Material 3 Spindle Stainless steel 1.4404/1.4401
4 Spindle seal FKM/EPDM/NBR
5 Disc Technical ceramics
6 Valve seat Technical ceramics
7 Valve body Brass or stainless steel 1.4408
8 O-ring FKM/EPDM/NBR
9 O-ring FKM/EPDM/NBR
10 Parallel pin Stainless steel 1.4401
11 Spring Spring steel/Stainless steel
7 | 15Visit product website 4. Dimensions 4.1. Threaded version Note: Dimensions in mm H F C D B A E G X 92.5 X 36.2 A B C D E F G H H 8.2 13.7 – NPT ½ 97 138 31 58 26.6 – – 14 G ½ 97 138 31 58 26.6 8.6 14 – NPT ¾ 103.5 147 43 80 32 – – 16 G ¾ 103.5 147 43 80 32 10.2 16.8 – NPT 1 108.5 156.5 49 95 41 – – 18 G 1 108.5 156.5 49 95 41
8 | 15Visit product website 4.2. Capacitive buffer module Note: Dimensions in mm Further information can be found in chapter “8.1. Accessories capacitive buffer module” on page 127 63.5 182 179 186.5
9 | 15Visit product website 5. Device/Process connections 5.1. Analogue Note: For parameterisation and configuration of the positioner and the process controller variants, please use the Bürkert Communicator software tool, see “8.2. Bürkert Communicator Software” on page 13 Circular connector M12, 8-pin Pin Configuration 1 24 V DC
2 Power supply GND
3 Internal use 1.) 4 Internal use1.) 5 Internal use 1.)
6 Signal input +
7 Signal output
8 Signal GND
1.) Only for positioners and process controllers variant, for connection of the parameterization tools: Bürkert Communicator. The connec- tion is via the büS-Stick. Using an adapter cable (M12 8-pin to M12 5-pin) the büS-Stick can be connected, see “9.5. Ordering chart accessories” on page 15 Additional for process controller variant: Socket M12, 5-pin Pin Configuration 1 24 V DC sensor power supply
2 Analogue I N (0…20 mA, 4…20 mA, 0…5 V or 0…10 V)
3 GND
4 GND (bridge according to GND pin
5 Not connected
5.2. Digital (fieldbus) Note: For parameterisation and configuration of the positioner and the process controller variants, please use the Bürkert Communicator software tool, see “8.2. Bürkert Communicator Software” on page 13 Circular connector M12, 5-pin Pin Configuration
1 Shield
V DC
4 CAN high
5 CAN low
Additional for process controller variant: Socket M12, 5-pin Pin Configuration 1 24 V DC sensor power supply
2 Analogue I N (0…20 mA, 4…20 mA, 0…5 V, 0…10 V or
frequency)
10 | 15Visit product website 6. Performance specifications 6.1. Duty cycle derating diagram Note: The duty cycle is an important factor for motor valves. The self-heating of the engine limits the maximum duty cycle. High ambient temperatures additionally increase the risk of damage due to overheating. The following diagram shows the recommended maximum duty cycle as a function of the ambient temperature. In energy-saving mode (lower driving force), higher duty cycles are possible. The motor is optimised for the valve function in terms of size, power consumption and costs. The duty cycle does not mean the duty cycle of the device but t he duty cycle of the motor. This is only switched on when the valve is to move. Frequent set-point value changes drastically increase the duty cycle of the motor. Operating the valve outside the recommended duty cycle limits will result in a significantly reduced service life of the valve. Derating curve for standard version Derating curve for positioner and process controller 5 10 15 20 100 25 30 35 40 45 50 55 60 65 max. ambient temperature [°C] Duty cycle [%] Normal mode Power saving mode 5 10 15 20 100 25 30 35 40 45 50 55 60 65 max. ambient temperature [°C] Duty cycle [%] Normal mode Power saving mode 6.2. Pressure range Note: For orders from our standard product range, use the product filter in our eShop (see “9.1. Bürkert eShop” on page 14 Alternatively, you can use the Product Enquiry Form (see “9.4. Bürkert Product Enquiry Form” on page 15 ) for information about the device layout and send it to us after completion. Valve function Seat size Port connection1.) KVS-value water Pressure range3.) [mm] [m³/h]2.) [bar(g)] Control valve, without safety position in case of power failure 8 G ½ 1.8 6 10 G ½ 2.5 6 12 G ¾ 3.9 6 15 G ¾ 5.4 6 20 G 1 8.1 6 25 G 1 9.6 6 1.) Other port connections (NPT, …) on request 2.) Measurement at + °C, 1 bar pressure difference above the fully open valve 3.) Fuel gases may vary Further versions on request Temperature Low temperature variant: Suitable for minimum medium temperatures down to - (sealing material EPDM) (optional) bar Pressure Vacuum variant: This variant is suitable up to - 0.9 bar(g) (optional)
11 | 15Visit product website 6.3. Flow characteristic Determination of the KV value Note: Once the KV-value required for the application has been calculated, it can be compared with the KVS-values from the ordering chart. The KVS-value must be higher than the KV-value of the application, but should be neither too high nor too close to it - as a recommendation: % higher. Pressure drop KV value for liquids KV value for gases [m3/h] [m3/h] Sub-critical p2 > 2 = Q ρ Δp1000 = Q 514 QN ρNT1 Δ pp2 Supercritical p2 < 2 = Q ρ Δp1000 = Q QN ρNT1 257 p1 KV Flow coefficient [m3/h] 1.) QN Standard flow rate [mN 3/h] 2.) p1 Inlet pressure [bar] 3.) p2 Outlet pressure [bar] 3.) ∆p Differential pressure p 1…p2 [bar] ρ Density [kg/m3] ρN Standard density [kg/m3] T1 Medium temperature [(273+t)K] 1.) Measured for water, ∆p = bar 2.) At reference conditions 1.013 bar and 0 °C (273 K) 3.) Absolute pressure Exemplary characteristic curve of the motor valve Note: The design of the seat size is very important for the proper functioning of electromotive proportional valves within the application. The seat size must be selected in such a way that, on the one hand, the desired flow range is achieved and, on the other hand, when the valve is fully open, a sufficient part of the total pressure drop takes place via the valve. Reference value: Δp valve % of the total pressure drop Otherwise, an ideal, linear valve characteristic is deformed into a curved system charac teristic. 100 0 10 20 30 40 50 60 70 80 90 100 KV/KVS [%] Stroke [%] Linear flow characteristic - the KVS values of the respective seat sizes can be found in chapter “6.2. Pressure range” on page 10.
12 | 15Visit product website 7. Product operation Standard on/off valve In the ON/OFF variant, an external voltage signal is digitized and the valve is closed or opened. The status of the two end positions of the valve are indicated on the LED. In addition, the valve position “closed” is reached via the digital output. Standard control valve The standard proportional valve converts an external standard signal (position set-point value) into a valve position. Both valve end positions are indicated by the LED status. Additionally, the digital output indicates when the “closed” valve position has been achieved. Process diagram Description Valve opening Electromotive actuator Position sensor PositionerSet-point position CMD CTRL POS POS Position control loop + - Valve body Xd1 Positioner variant The proportional valve in the position control variant converts an external standard signal, the position set-point value, into a valve position. The position of the actuator is controlled according to the set-point position. The position sensor records the current position (POS) of the electromotive valve. This actual position is compared by the positioner with the set-point value (CMD) specified as the standard signal. If there is a control difference (Xd1), a motor control signal is given to the actuator as the actuating variable. Z1 is a disturbance value. The two end positions of the valve are indicated by the LED status. In addition, the actual position recorded by the position sensor is output via the M12 circular plug-in connector. Process controller Position control loop SP CMD PV Measured quantity Xd2 Transmitter ProcessProcess set point value Valve opening Process controller variant The additionally implemented PID controller can perform not only the actual position control but also a process control in the sense of a cascade control. The process controller is integrated into a control loop. The position setpoint of the valve is calculated from the process setpoint and the actual process value via the control parameters (PID controller). The process setpoint can be specified by an external signal. During the process control the position control mentioned above becomes the subordinate auxiliary control circuit; this results in a cascade control. The process controller in the main control circuit has a PID function. The process set-point value (SP) is specified as a set-point value and is compared with the actual value (PV) of the process variable to be controlled. The position measuring system records the current position (POS) of the electromotive linear actuator. This position actual value is compared by the position controller with the set-point value (CMD) specified by the process controller. If there is a control difference (Xd2), the actual position (POS) and therefore the valve opening are changed by the control variable (CTRL). Z2 represents a disturbance variable.
13 | 15Visit product website 8. Product accessories 8.1. Accessories capacitive buffer module Note: See “4.2. Capacitive buffer module” on page for information about dimensions. See “Standard accessories” on page 15 for ordering information. Accessories Description Motor valve(s) connection
24 V DC power supply
For example: Single phase, primary switched mode power supply Type 1573
- Capacitive buffer module for moving to a safety position in case of power failure In order to be able to move to a safety position of the valve in the event of a power failure, the valve must be supplied with voltage via the capacitive buffer module . In the event of a power failure, the buffer module provides an output voltage of 18 V DC for a few seconds. The reduced input voltage is detected by the valve and the safety position is approached accordingly. Up to 3 valves of Type 3280 or 2 valves of Type 3281 and Type 3285 can be connected to a buffer module. Factory setting of the safety position: “valve closed” For standard version (functionality available from software version A.08): Adjustable via DIP switch (when the operating direction is reversed, the safety position changes to “valve open”) For positioner and process controller variant (functionality available from software version A.06): Adjustable via Bürkert Communicator (user-defined safety position) 8.2. Bürkert Communicator Software Note: An adjustment of the valve by the Bürkert Communicator is only possible with the positioner or process controller variants. The corresponding communication software can be downloaded from the website Type 8920 The Bürkert Communicator is the most important software component of the EDIP (Efficient Device Integration Platform). Various features of this universal tool simplify the configuration and parametrisation of devices equipped with a digital CANopen-based interface. With this tool, the user has a complete overview of cyclic process values as well as acyclic diagnostic data. The integrated graphical programming environment enables the creation of decentralised sub-system control functions. The connection to the PC is established with a USB-CAN adapter. The adapter is available as an accessory (see “9.5. Ordering chart accessories” on page 15 The Bürkert Communicator enables: Configuration, parametrisation and diagnosis of EDIP devices / networks Easy and comfortable mapping of cyclic values Graphical display of process values Firmware update for the connected EDIP devices Backup and restoring of device configurations
14 | 15Visit product website Connection Type 3285 with Bürkert Communicator software The interface to the “Bürkert Communicator” software tool is based on CANopen. A corresponding bus termination is mandatory. For variants with standard signal interfaces, please activate the switchable terminating resistor on the büS stick. For variants with büS/ CANopen communication interface, this terminating resistor should not be switched on if the device is already integrated in a properly terminated bus network. A büS stick is required to connect the motor valve to the “Bürkert Communicator” software tool. The büS stick sets contain the neces sary accessories. For variants with büS/CANopen communication interface, the connection is made directly via the 5-pin M12 plug (büS stick set 1 contains the necessary accessories). Variants with standard signal interfaces are connected via the 8-pin M12 plug on the device (büS stick set 1 + büS adapter; socket 8-pin M12 to plug 5-pin M12 contain the necessary accessories). 9. Ordering information 9.1. Bürkert eShop Bürkert eShop – Easy ordering and quick delivery You want to find your desired Bürkert product or spare part quickly and order directly? Our online shop is available for you 24/7. Sign up and enjoy all the benefits. Order online now 9.2. Recommendation regarding product selection Note: The configuration of the seat size is very important for proportional valves to ensure proper functioning within the application. The seat size must be selected in such a way that on the one hand the desired flow range is achieved and on the other hand a sufficient part of the total pressure drop across the valve takes place when the valve is fully open. Reference value: pressure drop of the valve > % of the total pressure drop Let Bürkert engineers advise you already in the planning phase. 9.3. Bürkert product filter Bürkert product filter – Get quickly to the right product You want to select products comfortably based on your technical requirements? Use the Bürkert product filter and find suitable articles for your application quickly and easily. Try out our product filter
15 | 15Visit product website 9.4. Bürkert Product Enquiry Form Bürkert Product Enquiry Form – Your enquiry quickly and compactly Would you like to make a specific product enquiry based on your technical requirements? Use our Product Enquiry Form for this purpose. There you will find all the relevant informa- tion for your Bürkert contact. This will enable us to provide you with the best possible advice. Fill out the form now 9.5. Ordering chart accessories Standard accessories Description Article no. Power supply unit Phoenix Class2 (Type 1573), 85…240 V AC/24 V DC, 1.25 A, NEC Class 2 (UL 1310) 772438 Power supply unit for standard rail (Type 1573), 100…240 V AC/24 V DC, 1 A, NEC Class 2 (UL 1310) 772361 Power supply unit for standard rail (Type 1573), 100…240 V AC/24 V DC, 2 A, NEC Class 2 (UL 1310) 772362 Power supply unit for standard rail (Type 1573), 100…240 V AC/24 V DC, 4 A 772363 Buffer module (Type 1573) for safety position when power failure 773440 Accessories cable Description Article no. M12 circular socket with cable, 8-pin, cable length: 2 m, ready-made cable for input and output signals (for analogue variant) 919061 M12 circular female connector with cable, 8-pin, cable length: 2 m, ready-made shielded cable for input and output signals (for analogue variant) 918991 M12 cable shielded, 5-pin, cable length: 2 m, ready-made shielded cable for actual process value input signals (only for variant with analogue/digital process controller) 559177 Bürkert accessories Note: For connection to a büS/CANopen network, see cabling guide . Detailed accessory tables can be found in the wiring guide Can only be used with positioner and process controller variant. Description Article no. Software Bürkert Communicator Type 8920 büS adapter, M12 socket, 8-pin to M12 plug, 5-pin (for büS stick connection) 773286 USB büS interface set 1 (Type 8923) for connection to the Bürkert Communicator software: including connection cable (M12 and micro USB), stick with integrated terminating resistor, power supply and software 772426 USB büS interface set 2 (Type 8923) for connection to the Bürkert Communicator software: including büS stick, connec- tion cable to M12 plug, M12 connection cable on micro USB for the büS service interface and Y distributor, cable length: 0.7 m 772551