Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user documentation. Our general terms of use for downloads are valid. QUINT UPS with IQ Technology, RJ45 communication interfaces (PROFINET), for DIN rail mounting, input: 24 V DC, output: 24 V DC / 10 A, charging current: 3 A Product description The intelligent QUINT UPS for integration into established industrial networks: your systems continue to be supplied with uninterrupted power, even in the event of a mains failure. The battery management system with IQ Technology and a powerful battery charger ensures superior system availability. Your advantages Easy integration into networks using PROFINET, EtherNet/IP, EtherCAT® and USB interfaces• Evaluation of state of health (SOH) and state of charge (SOC), thanks to the intelligent battery management system (BMS) Automatic recognition of the battery capacities and technologies (VRLA-WTR, LI-ION) Monitoring of output current and voltage, as well as manual connection and disconnection of the system SFB Technology selectively trips standard miniature circuit breakers. Loads connected in parallel continue working. Commercial data Item number 2907068 Packing unit 1 pc Minimum order quantity 1 pc Sales key CM21 Product key CMUI43 Catalog page Page 317 (C-4-2019) GTIN 4055626170084 Weight per piece (including packing) 543.4 g Weight per piece (excluding packing) 469 g Customs tariff number 85371091 Country of origin CN QUINT4-UPS/24DC/24DC/10/PN - Uninterruptible power supply 2907068 https://www.phoenixcontact.com/us/products/2907068 Mar 24, 2025, 4:21 AM Page 1 (15)
18 V DC ... 30 V DCInput voltage range 18 V DC ... 32 V DC Internal input fuse no Voltage type of supply voltage DC Inrush current ≤ 7 A (≤ 4 ms) Reverse polarity protection yes
22 V DCFixed backup threshold
30 V DC
Dynamic activation threshold > 1 V / 100 ms Switch-on time max. 3 s Switch-on time during battery operation (Bat.-Start) 8 s Voltage drop, input/output 0.4 V DC Current consumption IN (UN, IOUT = IN, Icharge = 0) 10.1 A Current consumption Imax (UN, IOUT = IStat.Boost, ICharge = max) 16.3 A Current consumption INo-Load(UN, IOUT = 0, Icharge = 0) 105 mA Current consumption Icharge (UN, IOUT = 0, Icharge = max) 3.7 A Power consumption PN (UN, IOUT = IN, Icharge = 0) 245 W Power consumption Pmax (UN, IOUT = IStat.Boost, Icharge = max) 386 W Power consumption PNo-Load (UN, IOUT = 0, Icharge = 0) 2.6 W Power consumption Pcharge (UN, IOUT = 0, Icharge = max) 92 W Output data Efficiency typ. 97 % Number of outputs 1 Short-circuit-proof yes No-load proof yes Switch-over time 0 ms UPS connection in parallel no UPS connection in series no Energy storage device connection in parallel Yes, 5 (observe line protection) Energy storage device connection in series no Mains operation Output voltage 24 V DC (UOUT = UIN - 0.4 V DC) 18 V DC ... 30 V DCOutput voltage range 18 V DC ... 32 V DC Output current IN 10 A Static Boost (IStat.Boost) 12.5 A QUINT4-UPS/24DC/24DC/10/PN - Uninterruptible power supply 2907068 https://www.phoenixcontact.com/us/products/2907068 Mar 24, 2025, 4:21 AM Page 2 (15)
Dynamic Boost (IDyn.Boost) 20 A (5 s) Selective Fuse Breaking (ISFB) 60 A (15 ms) Output power POUT (UN, IOUT = IN) 240 W Output power POUT (UN, IOUT = Istat.Boost) 300 W Output power POUT (UN, IOUT = Idyn.Boost) 480 W (5 s) Power dissipation No load (UN, IOut = 0, ICharge = 0) 1 W Power dissipation Nominal load (UN, IOut = IN, ICharge = 0) 6 W Battery operation Output voltage 24 V DC (UOUT = UBAT - 0.4 V DC) Output voltage range 19 V DC ... 32 V DC Output current IN 10 A Static Boost (IStat.Boost) 12.5 A Selective Fuse Breaking (ISFB) 60 A (15 ms) Output power POUT (UN, IOUT = IN) 240 W Output power POUT (UN, IOUT = Istat.Boost) 300 W Output power POUT (UN, IOUT = Idyn.Boost) 480 W (5 s) Energy storage End-of-charge voltage 32 V DC End-of-charge voltage (temperature-compensated) 25 V DC ... 32 V DC Charging current (configurable) 3 A Nominal capacity (without additional charger) 1.2 Ah ... 60 Ah Max. capacity 80 Ah Charging time 120 h Buffer time 25 min (7.2 Ah) Deep discharge protection 19.2 V DC Battery technology VRLA, VRLA-WTR, LI-ION Charge characteristic curve IU0U IQ-Technology yes Temperature sensor yes Temperature compensation (configurable) 42 mV/K Connection data Input Position 1.x Conductor connection Connection method Screw connection recommended QUINT4-UPS/24DC/24DC/10/PN - Uninterruptible power supply 2907068 https://www.phoenixcontact.com/us/products/2907068 Mar 24, 2025, 4:21 AM Page 3 (15)
rigid (AWG) 30 ... 12 (Cu) Stripping length 6.5 mm (rigid/flexible) Drive form screw head Slotted L Output Position 2.x Conductor connection Connection method Screw connection rigid (AWG) 30 ... 12 (Cu) Stripping length 6.5 mm (rigid/flexible) Drive form screw head Slotted L Signal Position 3.x Conductor connection Connection method Push-in connection rigid 0.2 mm² ... 1 mm² flexible 0.2 mm² ... 1 mm² 0.5 mm² (recommended) rigid (AWG) 24 ... 16 (Cu) Stripping length 8 mm (rigid/flexible) Battery Position 4.x Connection technology Position marking 4.1 (+), 4.2 (-), 4.3 () Conductor connection Connection method Screw connection rigid (AWG) 30 ... 12 (Cu) QUINT4-UPS/24DC/24DC/10/PN - Uninterruptible power supply 2907068 https://www.phoenixcontact.com/us/products/2907068 Mar 24, 2025, 4:21 AM Page 4 (15)
Stripping length 6.5 mm (rigid/flexible) Drive form screw head Slotted L Interfaces Interface PROFINET Number of interfaces 2 Connection method RJ45 PROFINETSupported protocols LLPD Locking Locking clip Transmission physics Twisted-Pair Autonegotiation Autocrossing Autopolarity
Features
Transmission speed 100 Mbps Transmission length max. 100 m Cycle time 1 ms (RT) Access time ≤ 2 s IEEE 802.3 IEC 61158 Standards IEC 61784-2 Chipset Renesas TPS-1 Electrical isolation yes Device ID 0142hex Vendor ID 00B0hex Signaling LED signaling DC OK (green) Alarm (red) Bat.-Mode (yellow) SOC (red, green) Types of signaling Data (red, green) Product properties Product type DC UPS Product family QUINT UPS > 1189000 h (25 °C) QUINT4-UPS/24DC/24DC/10/PN - Uninterruptible power supply 2907068 https://www.phoenixcontact.com/us/products/2907068 Mar 24, 2025, 4:21 AM Page 5 (15)
736900 h (40 °C)MTBF (IEC 61709, SN 29500) > 372700 h (60 °C) RoHS Directive 2011/65/EU WEEE Environmental protection directive Reach Insulation characteristics Protection class III (without PE) Degree of pollution 2 Life expectancy (electrolytic capacitors) Time 137895 h Dimensions Item dimensions Width 35 mm Height 130 mm 125 mmDepth 125 mm (Device depth (DIN rail mounting)) Item dimensions with alternative mounting Width 123 mm Height 130 mm Depth 37 mm Installation dimensions Installation distance right/left (active) 5 mm / 5 mm (POut ≥50% ) Installation distance right/left (passive) 0 mm / 0 mm (POut ≥50% ) Installation distance right/left (active, passive) 0 mm / 0 mm (POut ≤50 %) Installation distance top/bottom (active) 50 mm / 50 mm (POut ≥50% ) Installation distance top/bottom (passive) 40 mm / 20 mm (POut ≥50% ) Installation distance top/bottom (active, passive) 40 mm / 20 mm (POut ≤50 %) Mounting Mounting type DIN rail mounting Mounting position On horizontal DIN rail NS 35/7.5 and NS 35/15 acc. to EN 60715 Material specifications Flammability rating according to UL 94 (housing / terminal blocks) Housing material Metal Hood version Stainless steel X6Cr17 Side element version Aluminum AlMg3 Environmental and real-life conditions QUINT4-UPS/24DC/24DC/10/PN - Uninterruptible power supply 2907068 https://www.phoenixcontact.com/us/products/2907068 Mar 24, 2025, 4:21 AM Page 6 (15)
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) Ambient temperature (storage/transport) -40 °C ... 85 °C Ambient temperature (start-up type tested) -40 °C Maximum altitude ≤ 4000 m Climatic class 3K3 (EN 60721) Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing) Shock 18 ms, 30g, in each space direction (according to IEC 60068-2- 27) Vibration (operation) 2.3g Standards and regulations Overvoltage category EN 61010-1 II (≤ 4000 m) EN 61010-2-201 II (≤ 4000 m) Protective extra-low voltage Standard designation Protective extra-low voltage IEC 61010-1 (SELV)Standards/specifications IEC 61010-2-201 (PELV) Approvals UL approval Identification UL/C-UL Listed UL 61010-1 UL approval Identification UL/C-UL Listed UL 61010-2-201 UL approval Identification UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) CSA Identification CAN/CSA-C22.2 No. 61010-1-12 CSA Identification CAN/CSA-IEC 61010-2-201 CSA Identification CAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) CB scheme IEC 61010-1Identification QUINT4-UPS/24DC/24DC/10/PN - Uninterruptible power supply 2907068 https://www.phoenixcontact.com/us/products/2907068 Mar 24, 2025, 4:21 AM Page 7 (15)
Identification Class Guideline DNVGL-CG-0339 Note Location classes: Temperature D (see Application/Limitation), Humidity B, Vibration A/C, EMC B EMC data Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC EN 61000-6-3EMC requirements for noise emission EN 61000-6-4 EN 61000-6-1EMC requirements for noise immunity EN 61000-6-2 Noise immunity Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (power supply) Noise emission Standards/regulations Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) Electrostatic discharge Standards/regulations EN 61000-4-2 Electrostatic discharge Contact discharge 8 kV (Test Level 4) Discharge in air 15 kV (Test Level 4) Comments Criterion B Electromagnetic HF field Standards/regulations EN 61000-4-3 Electromagnetic HF field Frequency range 80 MHz ... 1 GHz Test field strength 20 V/m (Test Level 3) Frequency range 1 GHz ... 6 GHz Test field strength 10 V/m (Test Level 3) Frequency range 1 GHz ... 6 GHz Test field strength 10 V/m (Test Level 3) Comments Criterion A Fast transients (burst) Standards/regulations EN 61000-4-4 Fast transients (burst) Input 4 kV (Test Level 4 - asymmetrical) QUINT4-UPS/24DC/24DC/10/PN - Uninterruptible power supply 2907068 https://www.phoenixcontact.com/us/products/2907068 Mar 24, 2025, 4:21 AM Page 8 (15)
Output 4 kV (Test Level 4 - asymmetrical) Signal 4 kV (Test Level 4 - asymmetrical) Comments Criterion B Surge voltage load (surge) Standards/regulations EN 61000-4-5 Surge voltage load (surge) 1 kV (Test Level 3 - symmetrical)Input 2 kV (Test Level 3 - asymmetrical) 1 kV (Test Level 3 - symmetrical)Output 2 kV (Test Level 3 - asymmetrical) Signal 1 kV (Test Level 2 - asymmetrical) Comments Criterion B Conducted interference Standards/regulations EN 61000-4-6 Conducted interference Input/output/signal asymmetrical Frequency range 0.15 MHz ... 80 MHz Comments Criterion A Voltage 10 V (Test Level 3) Power frequency magnetic field Standards/regulations EN 61000-4-8 16.67 Hz 50 Hz Frequency 60 Hz Test field strength 100 A/m Additional text 60 s Comments Criterion A
50 HzFrequency
Frequency range 50 Hz ... 60 Hz Test field strength 1 kA/m Additional text 3 s Frequency 0 Hz Test field strength 300 A/m Additional text DC, 60 s Criteria Criterion A Normal operating behavior within the specified limits. Criterion B Temporary impairment to operational behavior that is corrected by the device itself. QUINT4-UPS/24DC/24DC/10/PN - Uninterruptible power supply 2907068 https://www.phoenixcontact.com/us/products/2907068 Mar 24, 2025, 4:21 AM Page 9 (15)
C COM C 1.1 1.2 4.1 4.2 4.3 2.1 2.2 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 QUINT DC-UPS t SOC U I AB C Battery DC 24V Input DC 24V Output DC 24V 24V 20mA Alarm (DO) Bat.-Mode (DO) Ready (DO) Remote (DI) PS Boost (DI/AI) Bat.-Start (DI) SGnd IF PN C COM Battery 24VD C Power supply 24VD C Buffered load Block diagram Graphic Load Current 5 6 7 8 9 10 20 30 40 45 50 1 2 3 4 5 6 7 8 9 10 12 14 16 18 20 50 100 Buffertime Minutes Hours 1 2 3 4 1 A 2 A 3 A 5 A 7 A 10 A 15 A 20 A 25 A 30 A 35 A
40 A 2x2x2x
2x: In this case, two battery modules of the same capacity are required. The data is based on an ambient temperature of +25 °C at the start of use. 1274520 UPS-BAT/PB/24DC/1.2AH
1274117 UPS-BAT/PB/24DC/4AH
1274118 UPS-BAT/PB/24DC/7AH
1274119 UPS-BAT/PB/24DC/12AH 1474660 UPS-BAT/PB/24DC/110AH
1348516 UPS-BAT/PB/24DC/20AH
1354641 UPS-BAT/PB/24DC/40AH
QUINT DC UPS buffer times for PB battery module QUINT4-UPS/24DC/24DC/10/PN - Uninterruptible power supply 2907068 https://www.phoenixcontact.com/us/products/2907068 Mar 24, 2025, 4:21 AM Page 10 (15)
1 2 3 4 5 6 7 8 9 10 15 20 30 35 40 45 50 55 1 2 3 4 1 A 2 A 3 A 5 A 7 A 10 A 15 A 20 A 25 A 30 A 35 A 40 A The data is based on an ambient temperature of +25 °C at the start of use. QUINT DC UPS buffer times for LI battery module Graphic Load Current Buffertime Minutes Hours 10 12 15 20 25 30 35 40 45 50 55 1 3 4 5 6 7 8 9 10 12 14 16 18 20 1 A 2 A 3 A 5 A 7 A 10 A 15 A 20 A 25 A 30 A 35 A 40 A The data is based on an ambient temperature of +25 °C at the start of use.
2320416 UPS-BAT/VRLA-WTR/24DC/13AH 2320429 UPS-BAT/VRLA-WTR/24DC/26AH
QUINT DC UPS buffer times and VRLA-WTR battery module QUINT4-UPS/24DC/24DC/10/PN - Uninterruptible power supply 2907068 https://www.phoenixcontact.com/us/products/2907068 Mar 24, 2025, 4:21 AM Page 11 (15)
To download certificates, visit the product detail page: https://www.phoenixcontact.com/us/products/2907068 EAC Approval ID: RU S-DE.BL08.W.00764 UL Listed Approval ID: E123528 cUL Listed Approval ID: E123528 EAC Approval ID: RU-DE.B.00184/20 DNV Approval ID: TAA00002K4 KC Approval ID: R-R-PCK-2907068 LR Approval ID: LR21417906TA NK Approval ID: TA22372M BV Approval ID: 69394/A0 BV RINA Approval ID: ELE382621XG ABS Approval ID: 23-2416092-PDA QUINT4-UPS/24DC/24DC/10/PN - Uninterruptible power supply 2907068 https://www.phoenixcontact.com/us/products/2907068 Mar 24, 2025, 4:21 AM Page 12 (15)
cUL Listed Approval ID: E199827 UL Listed Approval ID: E199827 cULus Listed cULus Listed QUINT4-UPS/24DC/24DC/10/PN - Uninterruptible power supply 2907068 https://www.phoenixcontact.com/us/products/2907068 Mar 24, 2025, 4:21 AM Page 13 (15)
ECLASS-11.0 27040705 ECLASS-12.0 27040705 ECLASS-13.0 27040705 ETIM ETIM 9.0 EC000382 UNSPSC UNSPSC 21.0 39121000 QUINT4-UPS/24DC/24DC/10/PN - Uninterruptible power supply 2907068 https://www.phoenixcontact.com/us/products/2907068 Mar 24, 2025, 4:21 AM Page 14 (15)
Environmental product compliance EU RoHS Fulfills EU RoHS substance requirements Yes Exemption 7(a), 7(c)-I China RoHS EFUP-25Environment friendly use period (EFUP) An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. EU REACH SVHC REACH candidate substance (CAS No.) Lead(CAS: 7439-92-1) SCIP 5ef9c374-4b50-4a6f-855e-9b55dc5dbea7 Phoenix Contact 2025 © - all rights reserved https://www.phoenixcontact.com Phoenix Contact USA