PHOENIX CONTACT Inc., USA Page 1 / 6 http://www.phoenixcon.com May 6, 2011 Extract from the online catalog ELR H5-IES-SC- 24DC/500AC-2 Order No.: 2900414 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2900414 "4 in 1" hybrid motor starter for reversing 3~ AC motors up to 550 V AC, with 24 V DC input, 2.4 A output current, emergency stop function, and adjustable overload shutdown. Commercial data GTIN (EAN) 4 046356 504058 sales group G420 Pack 1 pcs. Customs tariff 85364900 Catalog page information Page 230 (NTK-2010) Product notes WEEE/RoHS-compliant since: 02/09/2010 http:// www.download.phoenixcontact.com Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation. The General Terms and Conditions of Use apply to Internet downloads. Technical data Input data Rated control supply voltage US 24 V DC Rated control supply voltage range with reference to US Rated control supply current IS 40 mA

ELR H5-IES-SC- 24DC/500AC-2 Order No.: 2900414 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2900414 PHOENIX CONTACT Inc., USA Page 2 / 6 http://www.phoenixcon.com May 6, 2011 Rated actuating voltage UC 24 V DC Rated actuating voltage range with reference to UC Rated actuating current IC 3 mA Switching threshold "0" signal, voltage 9.6 V Switching threshold "1" signal voltage 19.2 V Protective circuit Protection against polarity reversal Parallel polarity protection diode Surge protection Typical response time < 35 ms Typical turn-off time < 40 ms Operating voltage display Green LED Status display Yellow LED Indication Red LED Output data, load relay Output name AC output Nominal output voltage 500 V AC Nominal output voltage range 42 V AC ... 550 V AC Load current max. 2.4 A (see derating curve) Leakage current 0 mA Residual voltage < 0.3 V Surge current 100 A (t = 10 ms) Type of protection Surge protection Output name Acknowledge output Note Confirmation 01: Floating PDT contact Nominal output voltage max. 253 V AC 0% ... 100% (300 V DC) Continuous load current 2 A Output data, signaling contact Measuring via Current transformer for line current on L1 and L3 Connection data Connection method Screw connection Conductor cross section solid min. 0.14 mm² Conductor cross section solid max. 2.5 mm² Conductor cross section stranded min. 0.14 mm² Conductor cross section stranded max. 2.5 mm²

ELR H5-IES-SC- 24DC/500AC-2 Order No.: 2900414 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2900414 PHOENIX CONTACT Inc., USA Page 3 / 6 http://www.phoenixcon.com May 6, 2011 Conductor cross section AWG/kcmil min. 26 Conductor cross section AWG/kcmil max 12 General data Width 22.5 mm Height 99 mm Depth 114.5 mm Test voltage input/output 4 kVrms Ambient temperature (operation) -25 °C ... 70 °C Ambient temperature (storage/transport) -25 °C ... 70 °C Mounting position Vertical (horizontal DIN rail) Assembly instructions Can be aligned with spacing = 20 mm Operating mode 100% operating factor Degree of protection IP20 Name Standards/regulations Standards/regulations DIN EN 50178 EN 60947 Name Power station requirements Standards/regulations DWR 1300 / ZXX01/DD/7080.8d Name Air and creepage distances between the power circuits Standards/regulations DIN EN 50178 Rated surge voltage / insulation 6 kV/safe isolation Rated insulation voltage 500 V Pollution degree 2 Surge voltage category III Safety integrity level according to IEC 61508-1 SIL 3 (safe shutdown) SIL 2 (motor protection) Category as per ISO 13849-1 3 Performance Level as per ISO 13849-1 e Category in acc. with EN 954-1 3 Certificates / Approvals Certification CB, CUL Listed, UL Listed

ELR H5-IES-SC- 24DC/500AC-2 Order No.: 2900414 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2900414 PHOENIX CONTACT Inc., USA Page 4 / 6 http://www.phoenixcon.com May 6, 2011 Certification Ex: PTB Diagrams/Drawings Block diagram Diagram Derating curve ELR H5-IES-SC- 24DC/500AC-2 and ELR H5- IES-SC- 24DC/500AC-9

ELR H5-IES-SC- 24DC/500AC-2 Order No.: 2900414 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2900414 PHOENIX CONTACT Inc., USA Page 5 / 6 http://www.phoenixcon.com May 6, 2011 Circuit diagram Conventional structure Main current path for reversing contactor according to category 3 K1 + K2 = Emergency stop contactor K3 = Left contactor K4 = Right contactor F4 = Motor protection relay Conventional structure Control current path for reversing contactor according to category 3 K1 + K2 = Emergency stop contactor K3 = Left contactor K4 = Right contactor K5 = PSR SCP-24DC.../safety relay T1 = Left, T2 = Right, T3 = Reset S2 = Emergency stop F4 = Motor protection relay Structure with CONTACTRON Main and control current path for "4 in 1" hybrid motor starter with reversing function according to category 3 K1 = "4 in 1" hybrid motor starter with reversing function K5 = PSR SCP-24DC.../safety relay T1 = Left, T2 = Right, T3 = Reset S2 = Emergency stop

ELR H5-IES-SC- 24DC/500AC-2 Order No.: 2900414 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2900414 PHOENIX CONTACT Inc., USA Page 6 / 6 http://www.phoenixcon.com May 6, 2011 Address PHOENIX CONTACT Inc., USA

586 Fulling Mill Road

Middletown, PA 17057,USA Phone (800) 888-7388 Fax (717) 944-1625 http://www.phoenixcon.com © 2011 Phoenix Contact Technical modifications reserved;