2825_en_C IB IL EX-IS PWR IN-PAC Data sheet © PHOENIX CONTACT 2013-03-07 1D e s c r i p t i o n The IB IL EX-IS PWR IN-PAC terminal functions as the power supply for the intrinsically safe area. It is mandatory when IB IL EX-IS…IO… terminal s are incorporated into the Inline station. The terminal provides full isolation of the intrinsically safe I/O system. This isolation includes the logic supply (UL), I/O terminal power supply (UEX), and local bus communication. 2F e a t u r e s – Galvanically isolated powe r supply for communication to intrinsically safe IB IL EX-IS… terminals – LED indicators for normal, heavy and overload power levels – Provides the required 50 mm separation between non- intrinsically safe and intrinsically safe I/O wiring – 1000 mA to logic circuit (U L) – 1000 mA supply for I/O modules (U EX) – -25… +60°C operating range This data sheet is only valid in association with the IB IL SYS PRO UM E user manual or the Inline system manual for your bus system. Make sure you always use the latest documentation. It can be downloaded at www.phoenixcontact.net/products. This data sheet is valid for all products listed on the following page: Power supply for intrinsically safe Inline terminals used in hazardous locations
2825_en_C PHOENIX CONTACT 2 3O r d e r i n g d a t a
4 Technical data
Description Type Order No. Pcs./Pkt. Terminal, power supply, includes accessories (connectors and labeling fields) IB IL EX-IS PWR IN-PAC 2869910 1 Accessories Description Type Order No. Pcs./Pkt. Connector, colored-coded IB IL SCN-PWR IN-CP 2727637 10 Documentation Description Type Order No. Pcs./Pkt. User manual: "Configuring and Installing the INTERBUS Inline Product Range" IB IL SYS PRO UM E 2743048 1 User manual: "Automation Terminals of the Inline Product Range" IL SYS INST UM E 2698737 1 General data Housing dimensions (width x height x depth) 48.8 mm x 136.8 mm x 71.5 mm Weight 292 g Transmission speed 500 kbps Permissible temperature (operation) -25°C to +60°C Permissible temperature (storage/transport) -25°C to +85°C Permissible humidity (operation/storage/transport) 10% to 95%, according to DIN EN 61131-2 Permissible air pressure (operation/storage/transport) 70 kPa to 106 kPa (up to 3000 m above sea level) Degree of protection IP20 according to IEC 60529 Protection class Class 3 according to VDE 0106, IEC 60536 Connection data for connector Connection method Conductor cross section Spring-cage terminals 0.2 mm 2 - 1.5 mm2 (solid or stranded), 24 - 16 AWG Electrical supply data Nominal value 24 V DC Tolerance -15%/+20% Ripple ±5% Permissible range 19.2 V to 30 V Recommended cable lengths 30 m maximum, do not route cable through outdoor areas Current load, maximum 1.5 A Power dissipation, maximum 8 W UEX supply to I/O terminals Connection Potential jumpers Nominal value 24 V DC Current, maximum 1000 mA Isolation Galvanic isolation by transformer UL supply to logic circuit Connection Potential jumpers Nominal value 5 V DC Current, maximum 1000 mA Isolation Opto-isolation and galvanic isolation by transformer
2825_en_C PHOENIX CONTACT 3
5 Local diagnostic and status
indicators and terminal point assignment Figure 1 IB IL EX-IS PWR IN-PAC terminal LEDs and connector
5.1 Function identification
5.2 Local diagnostic and status indicators
5.3 Terminal point assignment
EN 60079-0:2006 EN 60079-0:2009 EN 60079-11:2007 IEC 60079-15:2010 X II 3G ATEX Sira 10ATEX2130X; II 3G Ex nA IIC T4 Gc Ta = -25°C… +60°C IECEx SIR 10.0085X; Ex nA IIC T4 Gc UL/cUL Class I, Div. 2, Groups A,B,C,D T4 FM Class I, Div. 2, Groups A,B,C,D T4 Fault UEX PWRPWR EX i Fault PWR UEX PWR EX i 1.1 2.1 1.2 2.2 1.3 2.3 2.41.4 1.11.1 1.21.2 1.31.3 1.41.4 2.12.1 2.22.2 2.32.3 2.42.4 Color Meaning Black Power supply (input) Des. Color Meaning PWR Green Power present 1 1 If power supply voltage is below 19.2 V DC or above 32 V DC, the PWR LED will be on and all other LEDs will be off. UEX Green Yellow UEX power supply normal with no faults UEX power supply use is high, no faults FAULT Red (on) Module fault exists (U EX or UL overload) or power supply low Terminal points Signal Assignment 1.1 –
1.2 U V (24 V) Voltage supply for IB IL EX-
IS…IO… modules
1.3 GND Ground of the 24 V supply
1.4 FE Functional earth/ground
2.1 – 2.2 – 2.3 – 2.4 –
2825_en_C PHOENIX CONTACT 4
6 Internal circuit diagram
Figure 2 Internal wiring of the terminal points Key: +24 V (U ) Local bus GND UL EX 5 V 24 V 19-32 V 24 V 24 V 24 V Power supply unit with electrical isolation LED Optocoupler /G78 /G78 /G78 /G58 /G58 /G58
2825_en_C PHOENIX CONTACT 5
7 Safety regulations and installation
7.1 Safety regulations for installation in the
potentially explosive area This Inline terminal conforms to standard EN 50021 and can be installed in a Zone 2 potentially explosive area. These Inline terminals are category 3 items of equipment. This Inline terminal for the indicated hardware version or later is suitable for use in Class I, Zone 2, Groups A, B, C, D. Installation in Zone 2 Observe the specified conditions for use in potentially explosive areas.
7.2 Installation and operation
Follow the installation instructions. When installing and operating the device, the applicable safety directives (including national safety directives), accident prevention regulations, as well as general technical regulations, must be observed. Do not repair the device yourself, but replace it with an equivalent device. Repairs may only be carried out by the manufacturer. Install the device in a suitable housing with a suitable degree of protection in accordance with IEC 60529 in order to protect it from mechanical and electrical damage. For the safety data, please refer to the operating instructions and certificates and other approvals, if necessary. For a list of terminals that are approved for the potentially explosive areas of Zone 2, please refer to the AH EN IL EX ZONE 2 application note. Verify use by checking the label on the Inline terminal and the packaging. WARNING: Explosion hazard The device is classed as category 3 electrical equipment and is suitable for installation in zone 2. WARNING: Explosion hazard Install the device in suitable housing with a minimum of IP54 degree of protection. Observe the requirements of IEC 60079-14/EN 60079-14, e.g., steel housing with a wall thickness of 3 mm. WARNING: Explosion hazard Disconnect the block power supply before: – Snapping it on or disconnecting it – Connecting or disconnecting cables WARNING: Explosion hazard Only use category 3G modules (ATEX 94/9/EC). NOTE: Installation, operation, and maintenance may only be carried out by qualified personnel. NOTE: The circuits inside the device must not be accessed. NOTE: The device is designed to meet IP20 protection when: – It is installed outsid e potentially explosive areas. – The environment is clean and dry.
2825_en_C PHOENIX CONTACT 6
8 Installation
8.1 Overview
Inline intrinsically safe IO terminals can be installed in a standard Inline station and is supported by all major industrial networks. Basic and intrinsically safe wiring practices need to be followed by the following concept. Figure 3 Intrinsically safe Inline terminals power supply The IB IL EX-IS PWR IN-PAC terminal: – provides isolation between unsafe power and power into the safe zone. – limits the available energy to the intrinsically safe I/O modules. – provides the required separation of 50 mm between safe and non-safe wire connections. Intrinsically safe wiring must be installed separately from non-intrinsically safe wiring (must not be mixed within a wire channel). Only one IS power supply can be installed in an Inline station. Onboard I/Os on a bus coupler may be used. If additional power is required, a new node must be installed.
8.2 Power budget
The IB IL EX-IS PWR IN-PAC provides power to the IB IL EX-IS…IO… terminals in two ways: – 1000 mA is available for the logic functions (U L). – 1000 mA is available for the I/O functions (U EX). The number of terminals that can be powered via the IB IL EX-IS PWR IN-PAC varies according to the type of terminal and the number and type of I/O connections. 24 V 7.5 V OPC UEX Local Bus GND UL Fieldbus US UM IN OUT UBK 24 V 24 V 24 V 5 V IBSIL24BK-T/U IB IL EX-IS PWR-IN IB IL EX-IS… IB IL EX-IS… The IB IL EX-IS PWR IN-PAC contains no logic function and therefore, does not draw power for itself.
2825_en_C 7PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany www.phoenixcontact.com Based on the logic functions, the maximum number of terminals that can be connected is 10. To determine the number of I/O points that can be connected, refer to Table 1. To calculate the power requirements of a system, list the number and type of each connected point. From this list, determine the number and type of terminals required. Multiply the number of each I/O point by the appropriate current draw listed in Table 1. Add the terminal overhead current for each terminal used. The sum of the I/O point current draw and the terminal overhead current draw determines the current draw from the IB IL EX-IS PWR IN-PAC. The maximum current draw is 1000 mA. Example: For the following point count: To connect this number of points, the following number of terminals are required (four channels per terminal). Add the total current draw for each terminal to determine the total terminal overhead. Add the subtotals together and the total current draw from U EX is 645 mA. This is less than 1000 mA and does not exceed the maximum UEX current draw. The total number of terminals is 7 (less than 10). Based on the these totals, this is a viable configuration.
8.3 Connections
The IB IL EX-IS PWR IN-PAC terminal must be installed along within an existing IB IL system. The IB IL EX-IS PWR IN-PAC separates the existing IB IL system from the intrinsically safe area by providing isolation to the local bus as well as the I/O terminals (UEX). Figure 4 Connections Table 1 U EX Current Draw IB IL EX-IS DIO 4/NAM- PAC IB IL EX-IS AIO 4/EF- PAC IB IL EX-IS TEMP 4 RTD/TC-PAC Terminal overhead 20 mA 45 mA 45 mA Output channel 45 mA 25 mA – Input channel 10 mA 25 mA 10 mA Number of points Current per point Total Digital Inputs 10 10 mA 100 mA Digital Outputs 1 45 mA 45 mA Temp/RTD inputs 6 10 mA 60 mA Analog Inputs/Outputs 8 25 mA 200 mA Subtotal 405 mA Digital points Number of terminals Current per terminal Total Digital I/O 11 3 20 mA 60 mA Temperature 6 2 45 mA 90 mA Analog I/O 8 2 45 mA 90 mA Number of terminals 7 Subtotal 240 mA - U24 VDC