https://www.phoenixcontact.com/us/products/2808001 10/17/2014 Page 1 / 8 Type 2 surge arrester - VAL-CP-RCD-3S/40/0.3/SEL - 2808001 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://phoenixcontact.com/download) Combination of pluggable type 2 arrester and selective residual current circuit breaker (RCD switch) for 3-phase power supply networks (5-conductor system: L1, L2, L3, N, PE). Product Features Combination of type 2 surge arrester and RCD residual current device Optical, mechanical status indication for all protective plugs Personal protection and device protection in a single device Residual current device is not triggered by magnetic influences caused by discharge currents in the type 2 arrester Type 2 consistent plug-in surge arresters Disconnect device on each individual plug For 5-conductor systems; L1, L2, L3, N, PE Key commercial data Packing unit 1 pc Weight per Piece (excluding packing) 900.0 GRM Custom tariff number 85363010 Country of origin Germany Technical data Dimensions Height 90 mm Width 121 mm Depth 76 mm Ambient conditions Degree of protection IP20

https://www.phoenixcontact.com/us/products/2808001 10/17/2014 Page 2 / 8 Type 2 surge arrester - VAL-CP-RCD-3S/40/0.3/SEL - 2808001 Technical data Ambient conditions Ambient temperature (operation) -25 °C ... 40 °C Ambient temperature (storage/transport) -40 °C ... 60 °C General IEC power supply system TT TN-S Housing material PBT / PA Inflammability class according to UL 94 V0 Color light gray Standards for air and creepage distances IEC 61643-1 IEC 60664-1 Mounting type DIN rail: 35 mm Type DIN rail module, two-section, divisible Number of positions 4 Surge protection fault message Optical Direction of action 3L-N & N-PE Protective circuit IEC test classification II EN type T2 Nominal voltage UN 240 V AC (230/400 V AC ... 240/415 V AC)

415 V AC (L-L)

Maximum continuous operating voltage UC (L-N) 350 V AC Maximum continuous operating voltage UC (N-PE) 264 V AC UT (TOV-proof) 415 V AC (5 s)

1200 V AC (200 ms / N-PE)

Nominal frequency fN 50 Hz 60 Hz Rated load current IL 40 A Residual current IPE ≤ 1 µA Standby power consumption PC ≤ 90 mVA Max. discharge current Imax (8/20) µs maximum (L-N) 90 kA (all channels) 30 kA Max. discharge current Imax (8/20) µs maximum (N-PE) 30 kA Nominal discharge current In (8/20) µs (L-N) 60 kA (all channels) 20 kA Nominal discharge current In (8/20) µs (N-PE) 20 kA

https://www.phoenixcontact.com/us/products/2808001 10/17/2014 Page 3 / 8 Type 2 surge arrester - VAL-CP-RCD-3S/40/0.3/SEL - 2808001 Technical data Protective circuit Front of wave sparkover voltage at 6 kV (1.2/50) µs (N-PE) ≤ 1.7 kV Voltage protection level Up (L-N) ≤ 2 kV Voltage protection level Up (N-PE) ≤ 2 kV Residual voltage (L-N) ≤ 1.8 kV (at In) ≤ 1.5 kV (at 10 kA) ≤ 1.2 kV (at 5 kA) ≤ 1 kV (at 3 kA) Residual voltage (L-PE) ≤ 2.5 kV (at In) ≤ 2 kV (at 10 kA) ≤ 1.4 kV (at 5 kA) ≤ 1.1 kV (at 3 kA) Residual voltage (N-PE) ≤ 0.7 kV (at In) ≤ 0.4 kV (at 10 kA) ≤ 0.3 kV (at 5 kA) ≤ 0.2 kV (at 3 kA) Response time (L-N) ≤ 25 ns Response time (L-PE) ≤ 100 ns Response time (N-PE) ≤ 100 ns Connection, protective circuit Connection name Protective ground connection Connection method Screw connection Connection type IN Biconnect screw terminal block Connection type OUT Biconnect screw terminal block Connection method Biconnect terminal block Screw thread M5 Tightening torque 4.5 Nm Stripping length 16 mm Conductor cross section stranded min. 4 mm² Conductor cross section stranded max. 16 mm² Conductor cross section solid min. 4 mm² Conductor cross section solid max. 16 mm² Conductor cross section AWG/kcmil min. 12 Conductor cross section AWG/kcmil max 4 Connection name Connection protective circuit Connection method Screw connection Connection type IN Biconnect screw terminal block

https://www.phoenixcontact.com/us/products/2808001 10/17/2014 Page 4 / 8 Type 2 surge arrester - VAL-CP-RCD-3S/40/0.3/SEL - 2808001 Technical data Connection, protective circuit Connection type OUT Biconnect screw terminal block Connection method Biconnect terminal block Screw thread M5 Tightening torque 4.5 Nm Stripping length 16 mm Conductor cross section stranded min. 4 mm² Conductor cross section stranded max. 25 mm² Conductor cross section solid min. 4 mm² Conductor cross section solid max. 25 mm² Conductor cross section AWG/kcmil min. 12 Conductor cross section AWG/kcmil max 2 Standards and Regulations Standards/regulations IEC 61643-1 2005 EN 61643-11 2002 IEC 61008-1 2004 IEC 61008-1/A11 2007 IEC 61008-2-1 2000 IEC 60947-3 2005 RCD switch Dimensioning error current 300 mA Rated making and breaking capacity Im 630 A Rated residual making and breaking capacity IΔm 630 A Surge withstand capability 6 kV (1.2/50 µs) Immunity to short-circuiting Inc 10 kA (Back-up fuse: 63 A) Tripping time for IΔn ≤ 300 ms Tripping time for 5xIΔn ≤ 40 ms Cycles, max. 20000 Utilization category AC 23 A Class A selective Insulation voltage Ui 440 V Classifications eCl@ss eCl@ss 4.0 27140201 eCl@ss 4.1 27130801

https://www.phoenixcontact.com/us/products/2808001 10/17/2014 Page 5 / 8 Type 2 surge arrester - VAL-CP-RCD-3S/40/0.3/SEL - 2808001 Classifications eCl@ss eCl@ss 5.0 27130801 eCl@ss 5.1 27130801 eCl@ss 6.0 27130805 eCl@ss 7.0 27130805 eCl@ss 8.0 27130805 ETIM ETIM 2.0 EC000941 ETIM 3.0 EC000941 ETIM 4.0 EC000941 ETIM 5.0 EC000941 UNSPSC UNSPSC 6.01 30212010 UNSPSC 7.0901 39121610 UNSPSC 11 39121610 UNSPSC 12.01 39121610 UNSPSC 13.2 39121620 Approvals Approvals Approvals KEMA-KEUR / VDE Zeichengenehmigung / ÖVE / GOST / CCA / IECEE CB Scheme Ex Approvals Approvals submitted Approval details KEMA-KEUR

https://www.phoenixcontact.com/us/products/2808001 10/17/2014 Page 6 / 8 Type 2 surge arrester - VAL-CP-RCD-3S/40/0.3/SEL - 2808001 Approvals VDE Zeichengenehmigung ÖVE GOST CCA IECEE CB Scheme Drawings Connection diagram IN N N RCD Type□A N F LN L L PE IN Functional drawing N N 1□on 0□off N N white o.k. red fault

https://www.phoenixcontact.com/us/products/2808001 10/17/2014 Page 7 / 8 Type 2 surge arrester - VAL-CP-RCD-3S/40/0.3/SEL - 2808001 Functional drawing VALVETRAB VALVETRAB green red Functional drawing Functional drawing Functional drawing N N 1□on =>□ok Dimensioned drawing

76 Circuit diagram

N T

https://www.phoenixcontact.com/us/products/2808001 10/17/2014 Page 8 / 8 Type 2 surge arrester - VAL-CP-RCD-3S/40/0.3/SEL - 2808001 Application drawing L1 L1 F1 F1 F2*F2* F2* L2 L2 N L3 L3 PE N N PE PE Phoenix Contact 2014 © - all rights reserved http://www.phoenixcontact.com