Technical content
Features
– Easy and tool-free I/O mapp ing via thumb wheel on the front – Modular design via TBUS DIN rail connector (hot-swap capable) – Channel-to-channel electrical isolation –F o u r P t 100 inputs (-50°C ... +250°C) – International approvals – Installation in Ex- Zone 2 WARNING: Explosion hazard when used in potentially explosive areas The module is a category 3 item of electrical equipment. Follow the instructions provided here during installa- tion and observe the safety instructions. Make sure you always use the latest documentation. It can be downloaded from the product at phoenixcontact.net/products. Use the I/O extension module in connection with IFS master devices (e.g., Radioline wireless modules) with the latest firmware version. For the latest firmware version, please visit phoenixcontact.net/products. This data sheet is valid for all products listed on the following page: 105366_en_00 2013-12-06
105366_en_00 PHOENIX CONTACT 2 2T a b l e o f c o n t e n t s
105366_en_00 PHOENIX CONTACT 3 Description Type Order No. Pcs. / Pkt. Temperature I/O extension module with 4 PT 100 inputs (-50+250 °C), with screw connection, including DIN rail connector RAD-PT100-4-IFS 2904035 1 3O r d e r i n g d a t a Accessories Type Order No. Pcs. / Pkt.
2400 MHz wireless transceiver with RS-232, RS-485 2-wire interface, ex-
pandable with I/O extension modules, with screw connection, antenna connection: RSMA (female), including DIN rail connector, without antenna RAD-2400-IFS 2901541 1 Bidirectional, Radioline 900 MHz transceiver for wireless transmission of serial and I/O data RAD-900-IFS 2901540 1 DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-plated contacts, 5-pos. ME 17,5 TBUS 1,5/ 5-ST-3,81 GN 2709561 10 Analog I/O extension module with 4 analog current/voltage outputs (0/4 mA ... 20 mA, 010 V), with screw connection, incl. DIN rail connector RAD-AO4-IFS 2901538 1
4 Technical data
Dimensions (nominal sizes in mm) Dimensions W / H / D 17.5 mm / 99 mm / 114.5 mm 17,599 114,5 General data Surge voltage category II Mounting position any , on standard DIN rail NS 35 in accordance with EN 60715 Degree of protection IP20 Pollution degree 2 Type of housing PA 6.6-FR , green MTTF (mean time to failure) Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)
1249 Years
MTTF (mean time to failure) Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)
506 Years
MTTF (mean time to failure) Telcordia standard, temperature 40°C, 100% operating cycle (7 days a week, 24 hours a day)
194 Years
105366_en_00 PHOENIX CONTACT 4 Supply Max. current consumption ≤ 38 mA (At 24 V DC, at 25°C) Transient surge protection Yes Pt 100 input Number of inputs 4 Sensor input current 1 mA (constant) Temperature measuring range -50 °C ... 250 °C Measuring accuracy 0.1% (From the measuring range final value) Connection method 2, 3-wire Max. permissible overall conductor resistance 25 Ω Process data channel 16 Bit (per channel) Electrical isolation Pt 100 inputs 50 V (Rated insulation voltag e (in each case between the Pt 100 inputs / TBUS supply, reinforced insulation in accordance with EN 61010)) Neighboring devices 300 V (Rated insulation voltage (to adjacent devices, basic insulation in accor- dance with EN 61010)) Connection data Connection method Screw connection Conductor cross section AWG/kcmil 24 ... 14 Stripping length 7 mm Tightening torque 0.6 Nm Status indication Status display Green LE D (supply voltage, PWR) Green LED (bus communication, DAT) Red LED (periphery error, ERR) Ambient conditions Ambient temperature (operation) -40 °C ... 70 °C -40 °F ... 158 °F Ambient temperature (storage/transport) -40 °C ... 85 °C -40 °F ... 185 °F Permissible humidity (operation) 20 % ... 85 % Permissible humidity (storage/transport) 20 % ... 85 % Altitude 2000 m Vibration (operation) In accordance with IEC 60068-2-6: 5 g, 10 Hz - 150 Hz Shock 16 g, 11 ms Certification Conformance CE-compliant ATEX II 3 G Ex nA IIC T4 Gc X IECEx Applied for UL, USA / Canada UL applied for
105366_en_00 PHOENIX CONTACT 5 Conformance EMC directive 2004/108/EC EN 61000-6-2; EN 61000-6-4 Ex directive (ATEX) EN 60079-0; EN 60079-15 Tolerances influenced by electromagnetic interference Type of electromagnetic interference Typical deviation of the measuring range final value (current input) - Relative Absolute Electromagnetic fields according to EN 61000-4-3/IEC 61000-4-3 < ±0.35% ±0.6 °C Conducted interference according to EN 61000-4-6/IEC 61000-4-6 < ±0.1% ±0.3 °C Fast transients (burst) according to EN 61000-4-4/IEC 61000-4-4 < ±0.1% ±0.3 °C
105366_en_00 PHOENIX CONTACT 6
5 Safety regulations and installation
5.1 Installation and operation
- The category 3 device is suitable for installation in po- tentially explosive area zone 2. It fulfills the require- ments of EN 60079-0:2012 and EN 60079-15:2010.
- Installation, operation, and maintenance may only be carried out by qualified electricians. Follow the installa- tion instructions as described. When installing and op- erating the device, the applicable regulations and safety directives (including national safety directives), as well as general technical regulations, must be observed. For the safety technology data, see this packing slip and the certificates (EC examination certificate and other ap- provals if appropriate).
- With the exception of configuration of the thumb wheel, opening or modifying the device is not permitted. Do not repair the device yourself; replace it with an equivalent device. Repairs may only be performed by the manu- facturer. The manufacturer is not liable for harm result- ing from noncompliance.
- The IP20 protection (IEC 60529/EN 60529) of the de- vice is intended for use in a clean and dry environment. The device must not be subject to mechanical strain and/or thermal loads, which exceed the limits de- scribed.
- To protect the device against mechanical or electrical damage, install it in a suitable housing with appropriate degree of protection as per IEC 60529.
- The device is not designed for use in atmospheres with a danger of dust explosions.
- If dust is present, it is necessary to install into a suitable approved housing, whereby the surface temperature of the housing must be taken into consideration. WARNING: Risk of electric shock – Provide a switch/circuit breaker close to the device, which is labeled as the dis- connect device for this device or the en- tire control cabinet. – Provide overcurrent protection (I ≤ 6 A) in the installation. – Disconnect the device from all power sources during maintenance work and configuration (the device can remain con- nected to SELV or PELV circuits). – The housing of the device provides a ba- sic insulation against the neighboring de- vices, for 300 V eff. If several devices are installed next to each other, this has to be taken into account, and additional insula- tion has to be installed if necessary. If the neighboring device is equipped with ba- sic insulation, no additional insulation is necessary. CAUTION: Observe the following safety notes when us- ing the device.
105366_en_00 PHOENIX CONTACT 7
5.2 Safety regulations for installation in potentially
- Observe the specified conditions for use in potentially explosive areas! Install the device in a suitable ap- proved housing with a minimum of IP54 protection) that meets the requirements of EN 60079-15. Observe the requirements of EN 60079-14.
- In zone 2, only connect devices to the supply and signal circuits that are suitable for operation in the Ex zone 2 and the conditions at the installation location.
- In potentially explosive areas, terminals may only be snapped onto or off the DIN rail connector and wires may only be connected or disconnected when the pow- er is switched off.
- The switches of the device that can be accessed may only be actuated when the power supply to the device is disconnected.
- The device must be stopped and immediately removed from the Ex area if it is damaged, was subject to an im- permissible load, stored incorrectly or if it malfunctions. WARNING: Explosion hazard when used in potentially explosive areas Please make sure that the following notes and instructions are observed.
105366_en_00 PHOENIX CONTACT 8
6 Installation
6.1 Structure
6.2 Basic circuit diagram
Figure 2 RAD-PT100-4-IFS basic circuit diagram NOTE: electrostatic discharge! The device contains components that can be damaged or destroyed by electrostatic dis- charge. When handling the device, observe the necessary safety precautions against electrostatic discharge (ESD) according to EN 61340-5-1 and IEC 61340-5-1. Pos. Designation 1P t 100 input 2 for 2- and 3-wire sensors 2P t 100 input 1 for 2- and 3-wire sensors
3 White thumbwheel for se tting the I/O-MAP address
4 Connection option for TBUS DIN rail connector
6 Metal foot catch for DIN rail fixing
7P t 100 input 3 for 2- and 3-wire sensors 8P t 100 input 4 for 2- and 3-wire sensors
9 ERR status LED, red (communication error)
10 DAT status LED, green (BUS communication)
11 PWR status LED, green (supply voltage)
2.1 2.3 +I1 -I1 3-wire 2.2 -U1 µC2.1 2.2 2.3 3.1 3.2 3.3 5.1 5.2 5.3 4.1 4.2 4.3 IO-MAP 0 1 DC DC IFS IFS A D 1mA A D 1mA A D 1mA A D 1mA -I2 -U2 +I2 +I1 -U1 -I1 +I3 -U3 -I3 +I4 -U4 -I4 2.1 2.3 +I1 -I1 2.2 +I1 2-wire
105366_en_00 PHOENIX CONTACT 9
6.3 I/O MAP address in the Radioline wireless
Use the thumbwheel to set the I/O-MAP address. The exten- sion module in the Radioline wireless system is addressed using the I/O-MAP address. On the entire wireless network, addresses 1 to 99 (I/O MAP) (maximum) may be assigned for the I/O extension modules.
6.4 Network applications (operating mode)
You can set the network application of the wireless module with the PSI-CONF software. All RAD-2400-IFS Radioline wireless modules are set to I/O data mode (wire in/wire out) by default. Radioline wireless module in I/O data mode The input device must be provided with the same I/O MAP address as the assigned output device at the other Radio- line wireless station (I/O mapping). Only the RAD-AO4-IFS module can be assigned to the RAD-PT100-4-IFS module. The Pt 100 inputs, T1 ... T4, can be configured to the analog outputs I1/U1 ... I4/U4 of the RAD-AO4-IFS extension mod- ule. Radioline wireless module in PLC/Modbus RTU mode The I/O MAP address of an input module may only appear once in the network. The input data is saved in a Modbus memory map in the Radioline master wireless module. You can read or write the process data via the serial inter- face of the RAD-2400-IFS master wireless module (RAD-ID = 01) using the Modbus RTU command (see Section 7). The I/O MAP address of an input module may only appear once in the network. Thumb wheel settings
Description
00 Delivery state
**, 1* - 9* Setting not permitted *1 - *9 Interface System sl ave address, for use with other Interface System (IFS) master devices Example: I/O MAP address RAD-PT100-4-IFS 02 RAD-AO4-IFS 02 Pt 100 input Analog output -50°C 0 mA or 0 V +250°C 20 mA or 10 V
105366_en_00 PHOENIX CONTACT 10
6.5 Display and di agnostic elements
The I/O extension module uses a total of three LEDs to indi- cate the operating states. Figure 4 Display and diagnostic elements
6.6 Temperature input (Pt 100)
The Pt 100 inputs of the extension module can process tem- peratures from -50 °C ... +250 °C. All the inputs are electrically isolated from one another, from the supply voltage (via bus foot), and from other electronic components. Pt 100 resistance thermometers can be connected to the RAD-PT100-4-IFS I/O extension module. The thermome- ters change their resistance depending on the temperature. The Pt 100 input signals are acquired by the RAD-PT100-4- IFS and can be mapped to proportional, analog voltage or current signals of the RAD-AO4-IFS output module. Thus, conclusions can be made about the temperature via the standard analog signal. 1 °C 66.66 μA Figure 5 Current strength [mA] depending on the tem- perature [°C] PWR LED The green PWR LED indicates the supply voltage status. OFF No supply voltage ON Supply voltage OK DAT LED The green DAT LED indicates the bus communication sta- tus. OFF No communication Flashing Configuration/addressing mode ON Cyclic data communication ERR LED The red ERR LED indicates the error status, e.g., no corre- sponding output module found (e.g., incorrect address- ing). OFF No error Flashing Slow (1.4 Hz) I/O-MAP address changed Fast (2.8 Hz) No bus communication ON Critical internal error T [°C] I [mA] -50 0 50 100 150 200 250
105366_en_00 PHOENIX CONTACT 11
6.7 Assembly/removal
Figure 6 Mounting and removing When using the device in a connection station, use the 17.5 mm wide DIN rail connector supplied. Only use the DIN rail connector in connection with 24 V DC devices.
- Connect the DIN rail connectors together for a connec- tion station.
- Push the connected DIN rail connectors into the DIN rail.
- Place the device onto the DIN rail from above. Ensure the device and DIN rail connector are aligned correctly.
- Holding the device by the housing cover, carefully push the device towards the mounting surface so that the de- vice bus connector is securely fixed onto the DIN rail connector.
- Once the snap-on foot has been audibly snapped onto the DIN rail, check that it is fixed securely. The device is only mechanically secured via the DIN rail.
- Connect the desired number of I/O extension modules to the wireless module via the DIN rail connector.
- Install the device in suitable housing to meet the re- quirements for the protection class.
- During startup, check that the device is operating, wired, and marked correctly.
- You can establish a connection between two DIN rail connectors using MINI COMBICON connectors: MC 1,5/5-ST-3,81 (female, 1803604); IMC 1,5/5-ST-3,81 (male, 1857919).
6.8 Connecting the cables
Figure 7 Connecting the cables
- Crimp ferrules to the wires.
- Insert the wire with ferrule into the corresponding con- nection terminal block.
- Use a screwdriver to tighten the screw in the opening above the connection terminal block. Tightening torque: 0.6 Nm Outside the Ex area, module extension or module replacement is also possible during operation. A B C DE A B PWR DAT ERR
105366_en_00 PHOENIX CONTACT 12
6.9 Connecting the sensors
You can connect 2-wire or 3-wire sensors to the extension module. Take into account the measuring errors depending on the different measuring methods. 2-wire connection method With 2-wire technology, you need an insertion bridge be- tween terminals x.2 and x.3. For short distances (< 10 m).
- Connect the Pt 100 sensor to terminals x.1 and x.3.
- Bridge the terminals x.2 and x.3. 2-wire connection technology is the most cost-effective con- nection method. The temperature-related voltage is not di- rectly measured at the sensor and is therefore falsified by the two cable resistances. The measuring errors that occur may render the entire measurement useless. Figure 8 2-wire connection technology Cable resistances R L1 and RL2 are incorpo- rated in the measurement result directly and falsify the result accordingly. µC2.1 2.2 2.3 3.1 3.2 3.3 5.1 5.2 5.3 4.1 4.2 4.3 IO-MAP 0 1 DC DC IFS IFS A D 1mA A D 1mA A D 1mA A D 1mA -I2 -U2 +I2 +I1 -U1 -I1 +I3 -U3 -I3 +I4 -U4 -I4 RL RL RTD ϑ
105366_en_00 PHOENIX CONTACT 13 3-wire connection method For long distances between the Pt 100 sensor and the ex- tension module. To compensate the wire resistances, all wire resistances must have exactly the same values (RL1 = RL2 = RL3).
- Connect the Pt 100 sensor to terminals x.1, x.2, and x.3. With 3-wire connection technology, the temperature-related voltage is measured several times. Corresponding calcula- tions additionally reduce the effect of the cable resistance on the measurement result. The results are almost as good as those achieved using 4-wire technology. The cable resistances RL at terminals +I and -I must have the same value. This allows you to subtract the established cable resistance from the measurement result and to get the Pt 100 platinum resistance value. Figure 9 3-wire connection method µC2.1 2.2 2.3 3.1 3.2 3.3 5.1 5.2 5.3 4.1 4.2 4.3 IO-MAP 0 1 DC DC IFS IFS A D 1mA A D 1mA A D 1mA A D 1mA -I2 -U2 +I2 +I1 -U1 -I1 +I3 -U3 -I3 +I4 -U4 -I4 RLI+ RTD ϑ RLI–
105366_en_00 PHOENIX CONTACT 14 4-wire connection method The extension module does not support 4-wire connection technology.
- If you want to use a 4-wire sensor, only connect three of the four wires.
- The fourth wire should be left unwired. Otherwise there will be a different resistance in the +I and -I cables owing to the parallel connection of two cable resistances. Figure 10 4-wire connection technology µC2.1 2.2 2.3 3.1 3.2 3.3 5.1 5.2 5.3 4.1 4.2 4.3 IO-MAP 0 1 DC DC IFS IFS A D 1mA A D 1mA A D 1mA A D 1mA -I2 -U2 +I2 +I1 -U1 -I1 +I3 -U3 -I3 +I4 -U4 -I4 RLI+ (U+) RTD ϑ RLI–
105366_en_00 15PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany phoenixcontact.com 7P r o c e s s d a t a With the PSI-CONF software, you can set the wireless mod- ule's network application to “PLC/Modbus RTU mode”. You can read the process data via the serial interface of the RAD-2400-IFS master wireless module (RAD-ID = 01) using the Modbus RTU command. xx = I/O-MAP address set using the thumbwheel X = Currentness of data, bit 8 The read I/O data is only valid and current if a valid module type value is returned by the slave and the “Currentness of data” register value equals 0.
8 Error codes and formats for Pt 100 values
hex 06hex 30xx0 ... 30xx5 fc04 30xx0 Module type and currentness of data 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 XM o d u l e t y p e Register values: Module type If the module type in the register is invalid or unavailable, then the register value is 0 Currentness of data If the data in the register is not up-to-date, then the register value is 1. This is the case, for example, if the wire- less connection or communication with an input module fails. The IN process data is retained in the Modbus table, but is no longer updated. 30xx1 Reserved 30xx2 Pt 100 input 1, terminal point 2.x 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 30xx3 Pt 100 input 2, terminal point 3.x 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 30xx4 Pt 100 input 3, terminal point 4.x 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 30xx5 Pt 100 input 4, terminal point 5.x 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 30xx6 ... 30xx9 Reserved Data word Pt 100 input RAD-AO4-IFS, analog output hex dec/error code -50 °C ... +250 °C 0000 0 -50°C 0 mA 0 V 7530 30000 +250°C 20 mA 10 V 7F00 32512 +275.12 °C 21.67 mA 10.84 V
8001 Overrange
8002 Open circuit Sensor wired incorrectly,
measuring line too long, cable resistance too high