Features

– Supply of the 24 V voltage U L for generating the communications power UBus – Diagnostic and status indicators This module does not have a microprocessor and is therefore not a local bus device. It is not mapped to engineering tools. NOTE: Malfunction The power module only boosts the UBus voltage, if the corresponding red bus base module is snapped on and if the UBus voltage is present in the segment downstream of the power module. This data sheet is only valid in association with the UM EN AXL F SYS INST user manual. Make sure you always use the latest documentation. It can be downloaded from the product at phoenixcontact.net/products. 105688_en_02 2016-03-02

105688_en_02 PHOENIX CONTACT 2 / 6 2T a b l e o f c o n t e n t s

105688_en_02 PHOENIX CONTACT 3 / 6 Description Ty pe Order No. Pcs./Pkt. Axioline F power module for the communications power UBus, max. 4 A (including bus base module and connector) AXL F PWR 1H 2688297 1 3O r d e r i n g d a t a Accessories Ty pe Order No. Pcs./Pkt. Axioline F bus base module for power modules in housing type H (Replacement item) AXL F BS H PWR 2702051 5 item) AXL CN S/UL 2701421 5 Zack marker strip for Axioline F (device labeling), in 2 x 20.3 mm pitch, unprinted, 25-section, for individual labeling with B-STIFT 0.8, X-PEN, or CMS-P1-PLOTTER (Marking) ZB 20,3 AXL UNPRINTED 0829579 25 Zack marker strip, flat, in 10 mm pitch, unprinted, 10-section, for individual labeling with M-PEN 0,8, X-PEN, or CMS-P1-PLOTTER (Marking) ZBF 10/5,8 AXL UNPRINTED 0829580 50 Insert label, Roll, white, unlabeled, can be labeled with: THERMOMARK ROLL, THERMOMARK ROLL X1, THERMOMARK X, THERMOMARK S1.1, Mounting type: snapped into marker carrier, Lettering field: 35 x 28 mm (Marking) EMT (35X28)R 0801602 1Documentation Ty pe Order No. Pcs./Pkt. User manual, English, Axioline F: System and installation UM EN AXL F SYS INST - - Dimensions (nominal sizes in mm) Width 35 mm Height 126.1 mm Depth 54 mm Note on dimensions The depth is valid when a TH 35-7.5 DIN rail is used (according to EN 60715).

4 Technical data

122,4125,9 General data Color traffic grey A RAL 7042 Weight 107 g (with connector and bus base module) Ambient temperature (operation) -25 °C ... 60 °C Ambient temperature (storage/transport) -40 °C ... 85 °C Permissible humidity (operation) 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)

105688_en_02 PHOENIX CONTACT 4 / 6 Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level) Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level) Degree of protection IP20 Protection class III, IEC 61140, EN 61140, VDE 0140-1 Mounting position Any (no temperature derating) General data Connection data Designation Axioline F connector Connection method Push-in connection Conductor cross section [AWG] 24 ... 16 Stripping length 8 mm Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. Interface Axioline F local bus Connection method Bus base module Transmission speed 100 MBit/s Communications power Supply of communications power UL 24 V DC Maximum permissible voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple) Current supply at UBus max. 4 A Current consumption from UL max. 1.2 A (IBus = 4 A; UL = 19,2 V) Power consumption at UL max. 22 W (IBus = 4 A) NOTE: Damage to the electronics Provide the module with an external fuse to protect it against polarity reversal. The power supply unit must be able to supply four times the nominal current of the external fuse, to ensure that it trips in the event of an error. Error messages to the higher level control or computer system None Mechanical tests Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g Conformance with EMC Directive 2004/108/EC (valid until 19.04.2016) / 2014/30/EU (valid from 20.04.2016) Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A; Field intensity: 10 V/m Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, DC supply lines: ±0 .5 kV/±0.5 kV (symmetrical/asymmetrical) Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A; Test voltage 10 V Noise emission test according to EN 61000-6-3 Radio interference properties EN 55022 Class B Approvals For the latest approvals, please visit phoenixcontact.net/products.

105688_en_02 PHOENIX CONTACT 5 / 6

5 Internal circuit diagram

Figure 1 Basic circuit diagram Key: The module disconnects the incoming voltage routing for UBus and re-establishes it for the subsequent modules.

6 Terminal point assignment

Figure 2 Terminal point assignment

7 Connection example

Figure 3 Connection of the cables

8 Installation instructions

The bus base module belonging to the power module is red. As such, it differs from all other bus base modules. The bus base module is coded in such a way that it cannot accommodate any other modules. Local bus Axioline F local bus (hereinafter referred to as local bus) Diag circuit Diagnostics circuit Power supply unit LED Electrically isolated areas UL U 24 V L UBUS 24 V Diag circuit UL U Bus U Bus GND Bus XXX XXX Termina l point Color Assignment Supply voltage input a1, a2 Red 24 V DC (UL) Supply of the logic voltage (internally jumpered) b1, b2 Blue GND Reference potential of the supply voltage (internally jumpered) NOTE: Malfunction Ensure you insert the power module into the associated bus base module! If you use an incorrect bus base module both LEDs will illuminate red and the power module will be inoperative.

24 V DC

(U )L

105688_en_02 6 / 6PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany phoenixcontact.com

9 Local diagnostic and status indicators

Figure 4 Local diagnostic and status indicators UL Designati on Color Meaning State Description UL Green/red ULogic Green ON Communications power U Bus is present. Red ON Communications power U Bus is not present or overloaded. Communications power UBus downstream of the power module is not present. OFF Communications power supply not present. E1 Red Error Red ON Module has been snapped on to the wrong bus base. OFF Module has been snapped on to the right bus base.