https://www.phoenixcontact.com/pi/products/2702017 10/16/2018 Page 1 / 6 I/O module - AXL F DI8/1 DO8/1 XC 1H - 2702017 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://phoenixcontact.com/download) Axioline F XC, Digital I/O module, Digital inputs: 8, 24 V DC, connection method: 1-wire, Digital outputs: 8,
24 V DC, 500 mA, connection method: 1-wire, Extreme conditions version, transmission speed in the local
bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors The figure shows the standard item Product Description The module is designed for use within an Axioline F station. It is used to acquire and output digital signals. The filter times of the inputs can be adjusted to increase noise immunity. Filter times of 100 μs enable the user to implement a counting function with a maximum input frequency of 5 kHz in the application. The outputs are protected against short circuit and overload. Your advantages 8 digital inputs 8 digital outputs
24 V DC, 500 mA
Connection of actuators in single-wire technology Minimum update time of < 100 μs Device rating plate stored Diagnostic and status indicators Can be used under extreme ambient conditions Extended temperature range of -40°C ... +70°C (see “Tested successfully: use under extreme ambient conditions” in the data sheet) Partially coated PCBs Key Commercial Data Packing unit 1 pc GTIN GTIN 4046356901246 Technical data Note Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
https://www.phoenixcontact.com/pi/products/2702017 10/16/2018 Page 2 / 6 I/O module - AXL F DI8/1 DO8/1 XC 1H - 2702017 Technical data Dimensions Width 35 mm Height 126.1 mm Depth 54 mm Note on dimensions The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715). Ambient conditions Ambient temperature (operation) -25 °C ... 60 °C (Standard) -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) Ambient temperature (storage/transport) -40 °C ... 85 °C Permissible humidity (operation) 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing) Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level) Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level) Degree of protection IP20 Connection data Designation Axioline F connector Connection method Push-in connection Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. Conductor cross section solid min. 0.2 mm² Conductor cross section solid max. 1.5 mm² Conductor cross section flexible min. 0.2 mm² Conductor cross section flexible max. 1.5 mm² Conductor cross section AWG min. 24 Conductor cross section AWG max. 16 Stripping length 8 mm General Mounting type DIN rail Net weight 133 g Note on weight specifications with connectors and bus base module Diagnostics messages I/O supply failure Yes Short-circuit / overload of the digital outputs Yes Interfaces Designation Axioline F local bus No. of channels 2 Connection method Bus base module Transmission speed 100 Mbps Axioline potentials
https://www.phoenixcontact.com/pi/products/2702017 10/16/2018 Page 3 / 6 I/O module - AXL F DI8/1 DO8/1 XC 1H - 2702017 Technical data Axioline potentials Designation Axioline F local bus supply (UBus) Supply voltage 5 V DC (via bus base module) Current consumption max. 120 mA Power consumption max. 600 mW Designation Supply for digital input and output modules (UIO) Supply voltage 24 V DC Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple) Current consumption max. 8 A (provide external protection) Power consumption max. 97.35 W (of which 1.35 W internal losses) Type of protection Surge protection of the supply voltage Polarity reversal protection of the supply voltage Protection max. 8 A (polarity reversal protection up to 5 A) Digital inputs Input name Digital inputs Description of the input EN 61131-2 types 1 and 3 Connection method Push-in connection Connection technology 1-wire Number of inputs 8 Type of protection Polarity reversal protection of the inputs Input filter time 3000 µs (default) Input voltage range "0" signal -3 V DC ... 5 V DC Input voltage range "1" signal 11 V DC ... 30 V DC Nominal input current at UIN 2.4 mA Digital outputs Output name Digital outputs Connection method Push-in connection Connection technology 1-wire Number of outputs 8 Type of protection Short-circuit protection, overload protection of the outputs Output voltage 24 V DC Nominal output voltage 24 V DC Maximum output current per channel 500 mA Maximum output current per module 4 A (provide external protection) Nominal load, inductive max. 12 VA (1.2 H, 48 Ω, with nominal voltage) Nominal load, lamp max. 12 W (at nominal voltage) Nominal load, ohmic max. 12 W (48 Ω, with nominal voltage) Electrical isolation Test section 5 V communications power (logic), 24 V supply (I/O) 500 V AC 50 Hz 1 min.
https://www.phoenixcontact.com/pi/products/2702017 10/16/2018 Page 4 / 6 I/O module - AXL F DI8/1 DO8/1 XC 1H - 2702017 Technical data Electrical isolation 5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min. 24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min. Standards and Regulations Mechanical tests Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g Protection class III, IEC 61140, EN 61140, VDE 0140-1 Environmental Product Compliance China RoHS Environmentally friendly use period: unlimited = EFUP-e No hazardous substances above threshold values Drawings Connection diagram +24 V IN7 +24 V IN1 +24 V OUT8 OUT2 Typical connection of sensors and actuators when using external busbars Dimensional drawing 35 54 122,4126,1 Block diagram µC D UI DI 1...8 U 24 V IO UBus Local bus Input circuit 01 30 31 00 0030 0131 DO 1...8 Output circuit 32 03 0233 03 0232 33 Internal wiring of the terminal points
https://www.phoenixcontact.com/pi/products/2702017 10/16/2018 Page 5 / 6 I/O module - AXL F DI8/1 DO8/1 XC 1H - 2702017 Approvals Approvals Approvals LR / NK / UL Listed / cUL Listed / BV / DNV GL / PRS / BSH / KR / BSH / cULus Listed Ex Approvals Approval details LR http://www.lr.org/en 14-20019 NK http://www.classnk.or.jp/hp/en/ 14A006 UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705 cUL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705 BV http://www.veristar.com/portal/veristarinfo/generalinfo/ approved/approvedProducts/equipmentAndMaterials 36433/A2 BV DNV GL http://exchange.dnv.com/tari/ TAA00000DF PRS http://www.prs.pl/ TE/2106/880590/16 BSH http://www.bsh.de/de/index.jsp 840 KR http://www.krs.co.kr/eng/main/main.aspx HMB17372-AC002
https://www.phoenixcontact.com/pi/products/2702017 10/16/2018 Page 6 / 6 I/O module - AXL F DI8/1 DO8/1 XC 1H - 2702017 Approvals BSH http://www.bsh.de/de/index.jsp 840 cULus Listed Phoenix Contact 2018 © - all rights reserved http://www.phoenixcontact.com PHOENIX CONTACT GmbH & Co. KG Flachsmarktstr. 8