Technical content

Features

– 16 digital inputs according to EN 61131-2 type 1 and type 3 –2 4 V DC, 2.4 mA – Connection of sensors in 1-wire technology – Minimum update time < 100 μs – Filter times can be set in three increments: < 100 µs, 1000 µs or 3000 µs – Maximum input frequency: 5 kHz – Device type label stored – Diagnostic and status indicators This data sheet is only valid in association with the UM EN AXL F SYS INST user manual. Make sure you always use the latest documentation. It can be downloaded from the product at phoenixcontact.net/products. 8184_en_01 2014-06-18

8184_en_01 PHOENIX CONTACT 2 2T a b l e o f c o n t e n t s

8184_en_01 PHOENIX CONTACT 3 Description Type Order No. Pcs. / Pkt. Axioline F digital input module, 16 inputs, 24 V DC, 1-wire connection method (including bus base module and connectors) AXL F DI16/1 1H 2688310 1 3O r d e r i n g d a t a Accessories Type Order No. Pcs. / Pkt. Axioline F bus base module for housing type H (Replacement item) AXL F BS H 2700992 5 Axioline F connector set (for e.g., AXL F DI16/1 1H) (Replacement item) AXL CNS 2L-O/D/UI/E1/E2 2700985 1 Zack marker strip for Axioline F (device labeling), in 2 x 20.3 mm pitch, un- printed, 25-section, for individual labeling with B-STIFT 0.8, X-PEN, or CMS-P1-PLOTTER (Marking) ZB 20,3 AXL UNPRINTED 0829579 25 Zack marker strip, flat, in 10 mm pitch, unprinted, 10-section, for individual labeling with M-PEN 0,8, X-PEN, or CMS-P1-PLOTTER (Marking) ZBF 10/5,8 AXL UNPRINTED 0829580 50 Insert label, Roll, white, unlabeled, can be labeled with: THERMOMARK ROLL, THERMOMARK X, THERMOMARK S1.1, Mounting type: snapped into marker carrier, Lettering field: 35 x 28 mm (Marking) EMT (35X28)R 0801602 1 Documentation Type Order No. Pcs. / Pkt. User manual, English, Axioline F: System and installation UM EN AXL F SYS INST - - User manual, English, Axioline F: Diagnostic registers, and error messages UM EN AXL F SYS DIAG - - Dimensions (nominal sizes in mm) Width 35 mm Height 126.1 mm Depth 54 mm Note on dimensions The depth is valid when a TH 35-7.5 DIN rail is used (according to EN 60715).

4 Technical data

122,4126,1 General data Color traffic grey A RAL 7042 Weight 133 g (with connectors and bus base module) Ambient temperature (operation) -25 °C ... 60 °C Ambient temperature (storage/transport) -40 °C ... 85 °C Permissible humidity (operation) 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)

8184_en_01 PHOENIX CONTACT 4 Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level) Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level) Degree of protection IP20 Protection class III, IEC 61140, EN 61140, VDE 0140-1 Mounting position Any (no temperature derating) General data Connection data Designation Axioline F connector Connection method Push-in technology Conductor cross section [AWG] 24 ... 16 Stripping length 8 mm Interface Axioline F local bus Connection method Bus base module Transmission speed 100 MBit/s Communications power Communications power UBus 5 V DC (via bus base module) Current consumption from UBus max. 120 mA Power consumption at UBus max. 600 mW I/O supply Supply of digital input modules UI 24 V DC Maximum permissible voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple) Current consumption from UI 20 mA Power consumption at UI typ. 380 mW, max. 480 mW Surge protection of the supply voltage Electronic (35 V, 0.5 s) Polarity reversal protection of the supply voltage Parallel diode; with external 5 A fuse (for startup only) Protection max. 8 A (polarity re versal protection up to 5 A) When using for the first time, protect the module with a 5 A fuse. If all the modules are correctly connected in the system, the 5 A fuse can be replaced by an 8 A fuse. you can now load the module up to 8 A. NOTE: Damage to the electronics Provide the module with an external fuse to protect it against polarity reversal. The power supply unit must be able to supply four times the nominal current of the external fuse, to ensure that it trips in the event of an error. Digital inputs Number of inputs 16 Connection method Push-in technology Connection method 1-wire Description of the input EN 61131-2 types 1 and 3 Nominal input voltage 24 V DC Nominal input current 2.4 mA Current flow Linear until nominal current is reached, then constantly approx. 2.4 mA Input voltage range "0" signal -3 V DC ... 5 V DC Input voltage range "1" signal 11 V DC ... 30 V DC Input filter time 3000 µs (default), 1000 µs, < 100 µs Process data update < 100 µs Polarity reversal protection of the inputs Parallel diode (30 V, 5 s)

8184_en_01 PHOENIX CONTACT 5 Fieldbus data telegram Fieldbus system PROFIBUS DP Required parameter data 3 Byte Need for configuration data 6 Byte Error messages to the higher level control or computer system I/O supply failure Yes Electrical isolation/isolation of the voltage areas Test section Test voltage

5 V communications power (logic), 24 V supply (I/O) 500 V AC, 50 Hz, 1 min

5 V supply (logic)/functional earth ground 500 V AC, 50 Hz, 1 min

24 V supply (I/O) / functional earth ground 500 V AC, 50 Hz, 1 min

Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5 g Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30 g Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10 g Conformance with EMC Directive 2004/108/EC Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B; 6 kV contact discharge, 8 kV air discharge Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A; Field intensity: 10 V/m Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV Transient surge voltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical) Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A; Test voltage 10 V Noise emission test according to EN 61000-6-3 Radio interference properties EN 55022 Class B Approvals For the latest approvals, please visit phoenixcontact.net/products.

8184_en_01 PHOENIX CONTACT 6

5 Internal circuit diagram

Figure 1 Internal wiring of the terminal points Key:

6 Terminal point assignment

Figure 2 Terminal point assignment

7 Connection example

Figure 3 Example of a connection of sensors when using external busbars Ensure that GND of the sensors and GND for UI have the same potential. Local bus Axioline F local bus (hereinafter referred to as local bus) Microcontroller Transistor Optocoupler LED Power supply unit Electrically isolated areas Input circuit Input circuit µC D UI IN 1...16U 24 V I UBus Local bus Input circuit 013233 00 0032 0133 µC Termi- nal point Color Assignment Supply voltage input a1, a2 Red 24 V DC (UI) Digital input module sup- ply (internally jumpered) b1, b2 Blue GND Reference potential of the supply voltage (inter- nally jumpered) Digital inputs IN16 Digital inputs 13 ... 16 0300 1310 2320 3330 +24 V IN13 +24 V IN1 +24 V IN4 +24 V IN16 +24 V

8184_en_01 PHOENIX CONTACT 7

8 Local status and diagnostic indicators

Figure 4 Local status and diagnostic indicators D UI 30 32 31 33 20 22 21 23 10 12 11 13 00 02 01 03 Designa- tion Color Meaning State Description DR e d / yellow/ green Diagnostics of local bus communication Power down OFF Device in (power) reset. Not con- nected Red flash- ing Device operating, but there is no connection to previous device. Reset Red ON Application reset Device operating, but there is still a connection to the previous device, the application is reset. Ready Yellow ON Device operating, there is still a connection to the previous device, but the device has not yet detected a valid cycle after power on. Connected Yellow flashing Valid data cycles have been detected, but the device is (not) yet part of the current configuration. Device ap- plication not active Green/yel- low alter- nating Valid data cycles are being detected. The master application set the output data to valid, however, the slave ap- plication has not set the input data to valid as yet. Active Green flashing Device operating, communications within the station is OK. The master application does not read the input data. (The connection to the controller has not yet been established, for example.) Run Green ON Valid data cycles are being detected. All data is valid UI Green U Input ON Supply of digital input modules present. OFF Supply of digital input modules not present. 00 ... 03, 10 ... 13, 20 ... 23, 30 ... 33 Yellow Status of the inputs ON Input is set. OFF Input is not set. For more information on the meaning of local diagnostic and status indicators, please refer to the UM EN AXL F SYS INST user manual.

8184_en_01 PHOENIX CONTACT 8 9P r o c e s s d a t a The I/O data is displayed in S7-compatible format.

10 Parameter, diagnostics and

information (PDI) Parameter and diagnostic data as well as other information is transmitted via the PDI channel of the Axioline F station. The standard and application objects stored in the module are described in the following section. The following applies to all tables below: Please refer to the UM EN AXL F SYS INST for an explana- tion of the object codes and data types. Byte 0 B i t 76543210 C h a n n e l 87654321 Terminal point 13 12 11 10 03 02 01 00 Byte 1 B i t 76543210 C h a n n e l1 61 51 41 31 21 11 0 9 Terminal point 33 32 31 30 23 22 21 20 Abbreviation Meaning A Number of elements L Length of the elements RR e a d WW r i t e Every visible string is terminated with a zero terminator (00 hex). The length of a visible string element is therefore one byte larger than the amount of user data. For detailed information on PDI and the ob- jects, please refer to the UM EN AXL F SYS INST user manual.

8184_en_01 PHOENIX CONTACT 9

11 Standard objects

11.1 Objects for identificati on (device rating plate)

(hex) Object name Object type Data type A L Rights Meaning Contents Manufacturer

0001 VendorName Var Visible String 1 16 R Manufacturer name Phoenix Contact

0002 VendorID Var Visible String 1 7 R Manufacturer identifi-

0003 VendorText Var Visible St ring 1 49 R Comment on the

0012 VendorURL Var Visible String 1 30 R URL of the manufac-

http://www.phoenix- contact.com Module - general

0004 DeviceFamily Var Visible String 1 15 R Device family I/O digital IN

0006 ProductFamily Var Visible String 1 33 R Product family Axioline - High

000E CommProfile Var Visible String 1 4 R Communication pro- file 633 000F DeviceProfile Var Visible String 1 5 R Device profile 0010

0011 ProfileVersion Record Visible String 2 11; 20 R Device profile version 2011-12-07; Basic

Profile V2.0 003A VersionCount Array Unsigned 16 4 4 * 2 R Version counter 0006 0001 0000 0000hex Module - special

0005 Capabilities Array Visible String 1 8 R Properties Nothing

0007 ProductName Var Visible String 1 16 R Product designation AXL F DI16/1 1H

0008 SerialNo Var Visible String 1 11 R Serial number xxxxxxxxxx (e. g., 1234512345)

0009 ProductText Var Visible String 1 37 R Product text 16 digital inputs, ad-

000A OrderNumber Var Visible String 1 8 R Order No. 2688310 000B HardwareVersion Record Visible String 2 11; 3 R Hardware version e. g., 2011-02-04; 00 000C FirmwareVersion Record Visible String 2 11; 3 R Firmware version 0000-00-00; -- 000D PChVersion Record Visible String 2 11; 6 R Parameter channel version 2010-01-08; V1.00

0037 DeviceType Var Octet string 1 8 R Module identification 00 80 00 02 00 00 00

0014 Location Var Visible String 1 59 R/W Insta llation location Can be filled out by

the user.

0015 EquipmentIdent Var Visible String 1 59 R/W Eq uipment identifier Can be filled out by

the user.

0016 ApplDeviceAddr Var Unsigned 16 1 2 R/W User-defined device

the user.

8184_en_01 PHOENIX CONTACT 10

11.2 Object for multilingual capacity

11.3 Diagnostics objects

Diagnostics state (0018hex: DiagState) This object is used for a structured message of an error. Index (hex) Object name Object type Data type A L Rights Meaning Contents

0017 Language Record Visible String 2 6; 8 R Language en-us; English

(hex) Object name Object type Data type A L Rights Assignment/content

0018 DiagState Record 6 2; 1; 1;

2; 1; 1 R Diagnostics state; see below 0018hex: DiagState (Read) Subindex Data type Length in bytes Meaning Contents

0 Record 8 Diagnostic state Complete diagnostics information

1 Unsigned 16 2 Error number 0 ... 65535 dec

2 Unsigned 8 1 Priority 00 hex No error

3U n s i g n e d 8 1 G r o u p 0 0 hex No error FFhex entire device

4 Unsigned 16 2 Error code See table below

5 Unsigned 8 1 More information fol-

00hex (not supported)

6 Visible String 1 Text 00 hex (not supported)

The message with the priority 81hex or 82hex is a one-time internal message to the bus cou- pler that is implemented onto the error mech- anisms of the higher-level system by the bus coupler.

8184_en_01 PHOENIX CONTACT 11 Error code and status of the local status and diagnostics indicators

11.4 Objects for process data management

The objects 003Bhex and 003Chex are only applicable to tools. IN process data (0025hex: PDIN) You can read the IN process data of the module with this object. The structure corresponds to the representation in the "Process data" section. Error code Error Priority Group D LED UI LED 0000hex No error 00 hex 00hex Green ON ON 3412hex I/O supply failure 01 hex FFhex Flashing green/yellow OFF After all errors have been eliminated, it is au- tomatically reset. Index (hex) Object name Object type Data type A L Rights Assignment

0025 PDIN Var Octet string 1 2 R Input process data

003B PDIN_Descr Array of Records 3 8; 2; 2 R Description of the IN process data 003C PDOUT_Descr Array of Records 3 8; 2; 2 R Description of the output pro- cess data 0025hex: PDIN (Read) Subindex Data type Length in bytes Meaning

0 Octet string 2 Input process data

8184_en_01 12PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany phoenixcontact.com Filter time (FF8Fhex: Input_Filter) Configure the filter time of the module using this object.

13 Device descriptions

The device is described in the device description files. The device descriptions for controllers from Phoenix Con- tact are included in PC Worx and the corresponding service packs. The device description files for other systems are available for download at phoenixcontact.net/products in the down- load area of the bus coupler used. Index (hex) Object name Object type Data type A L Rights Assignment FF8F Input_Filter Var Unsigned 8 1 1 R/W Filter time FF8Fhex: Input_Filter (read, write) Subindex Data type Length in bytes Contents 0V a r 10 0 hex (Default) 3000 µs 01hex 1000 µs 02hex < 100 µs