DATASHEET SEARCH SITE | WWW.ALLDATASHEET.COM

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 5

Technical content

https://www.phoenixcontact.com/us/products/2298221 09/03/2014 Page 1 / 5 Power contactor - ELR 2/I-230/Z - 2298221 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://phoenixcontact.com/download) Electronic load relay, 1-phase, 2-channel, for intelligent control of ohmic and inductive loads Key commercial data Packing unit 1 pc Weight per Piece (excluding packing) 754.3 GRM Custom tariff number 85371099 Country of origin Germany Technical data Dimensions Width 62 mm Height 84 mm Depth 110 mm Ambient conditions Ambient temperature (operation) -25 °C ... 40 °C Ambient temperature (storage/transport) -25 °C ... 70 °C Degree of protection IP20 Input data Input name Device supply Nominal supply voltage 24 V DC Protective circuit Protection against polarity reversal Polarity protection diode Surge protection Suppressor diode Operating voltage display Yellow LED

https://www.phoenixcontact.com/us/products/2298221 09/03/2014 Page 2 / 5 Power contactor - ELR 2/I-230/Z - 2298221 Technical data Output data Output name OUT 1, OUT 2 Nominal output voltage range 180 V AC ... 275 V AC Periodic peak reverse voltage 600 V Mains frequency 50 Hz 60 Hz Continuous load current 2x 13 A (see derating curve) Load current min. 75 mA Leakage current typ. 6.5 mA Residual voltage 1.5 V Surge current 200 A (tp = 10 ms) Max. load value 220 A s (tp = 10 ms) Protective circuit/component RC element Varistor Surge voltage protection 275 V AC Connection data Connection method Screw connection Stripping length 8 mm Conductor cross section solid min. 0.2 mm² Conductor cross section solid max. 6 mm² Conductor cross section stranded min. 0.2 mm² Conductor cross section stranded max. 4 mm² Conductor cross section AWG/kcmil min. 24 Conductor cross section AWG/kcmil max 10 Screw thread M3 General Test voltage input/output 4 kV AC Mounting position Vertical (horizontal DIN rail) Assembly instructions Can be aligned with spacing = 20 mm Operating mode 100% operating factor Standards/regulations EN 50178 Pollution degree 2 Surge voltage category III

https://www.phoenixcontact.com/us/products/2298221 09/03/2014 Page 3 / 5 Power contactor - ELR 2/I-230/Z - 2298221 Classifications eCl@ss eCl@ss 4.0 27371102 eCl@ss 4.1 27371102 eCl@ss 5.0 27371601 eCl@ss 5.1 27371601 eCl@ss 6.0 27371601 ETIM ETIM 2.0 EC000066 ETIM 3.0 EC000066 ETIM 4.0 EC000066 ETIM 5.0 EC002055 UNSPSC UNSPSC 6.01 30211915 UNSPSC 7.0901 39121514 UNSPSC 11 39121514 UNSPSC 12.01 39121514 UNSPSC 13.2 39121514 Drawings

https://www.phoenixcontact.com/us/products/2298221 09/03/2014 Page 4 / 5 Power contactor - ELR 2/I-230/Z - 2298221 Diagram

https://www.phoenixcontact.com/us/products/2298221 09/03/2014 Page 5 / 5 Power contactor - ELR 2/I-230/Z - 2298221 Circuit diagram 1 = power section Phoenix Contact 2014 © - all rights reserved http://www.phoenixcontact.com