2031-A0023A ALLEN-BRADLEY | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 20

Technical content

Non Combination Systems (for North America) . . . 12-4 Non Combination Systems Combination Systems with Fusible Disconnect Combination Systems with Fusible Disconnect Combination Systems with Thermal-magnetic Combination Systems with Thermal-magnetic Circuit

ElectroGuard Overview The ElectroGuard Safety Isolation System is used in place of a disconnect switch for Lockout and Tagout (LOTO). It uses power contactors and Remote Lockout Stations to accomplish LOTO. Isolating the electrical energy usually involves calling an electrician to turn “Off ” the main disconnecting means. The electrician would then perform LOTO of the disconnecting means operating handle. This same procedure is required to perform cleaning, maintenance, setup, lubrication or adjustment. Machines or processes with multiple access points may require operator/maintenance intervention several times a shift (perhaps as often as 60 times per shift). To perform these activities, the operator/maintenance person may be required to place part of his or her body into an area not accessed during normal operation. This may cause serious or fatal injury if LOTO procedures are not followed. The ElectroGuard Safety Isolation System allows the machine operator to safely and quickly accomplish LOTO with dramatically reduced downtime. Provides Energy Isolation

  • Power isolation accomplished by means of contactors rather than disconnect switches.
  • Uses redundant, independent and self-monitoring circuits to detect a system fault.
  • Prevents accumulation of faults in order to maintain the integrity of the safety system.
  • Tamper-resistant design. Convenient Remote Lockout Station
  • Allows remote isolation of the electrical power to the machine or process—machine operator simply turns “Off ” a Remote Lockout Station.
  • A light on the Remote Lockout Station indicates that the three- phase power source to the machine or process has been isolated. No Light Means No Entry.
  • If a fault occurs in the Safety Isolation System, the “System Isolated” light on the Remote Lockout Stations will not illuminate.
  • E a s y L o c k o u t / T a g o u t . Certified by TUV to meet requirements of Category 4
  • Certified by TUV to meet Category 4, the most stringent safety category defined within International Standard EN 954-1/ISO 13849-1.
  • Subjected by TUV to rigorous third party testing and verification of the Failure Mode & Effect Analysis (FMEA). Status Communication Capability to a Remote PLC
  • Optional Remote I/O via Flex modules. Communication can be via the DeviceNet communication platform or the Remote I/O communication platform. Available from 23-1200 Amperes. Specifications ➊ Use of any of these input devices will not meet Lockout/Tagout (LOTO) requirements. Approvals CULUS Listed Industrial Control Panel; TUV Rheinland certified; CE marked for all applicable directives Standards IEC/EN 60204-1; IEC/EN 60439-1; Category 4 to International Standard EN 954-1/ISO 13849-1; 98/37/EC Machinery Directive; 89/336/EC EMC Directive; 73/23/EC Low Voltage Directive; Fulfils the function of an energy isolating device in accordance with the conditions set forth in the FedOSHA letter of interpretation pertaining to Section 1910.147(b); Cal/OSHA 3314. Estimated Component Life Remote Lockout Station 250,000 operations Power Contactors 23A - 85A: 2,000,000 operations (Isolation & Grounding) 110A-1200A: 1,000,000 operations Environmental Relative Humidity, Non condensing 90% Relative Humidity Power Panel Construction Tamper-resistant Control Module 23A-85A systems support up to 4 Remote Lockout Stations without an Expansion Module 110A-1200A systems support up to 6 Remote Lockout Stations without an Expansion Module Control Module with viewing window for visual check of status indicator lights Remote Lockout Station Construction T op and bottom 25.4mm (1.0in) conduit entry (removable plug in bottom conduit hole) Sealing provision for tamper-resistance Operating handle accepts up to 3 padlocks Expansion Module Construction 4 port—supports up to 4 lockout stations  allows the systems to accommodate up to 24 Remote Lockout Stations 10 port—supports up to 10 lockout stations  allows the systems to accommodate up to 60 Remote Lockout Stations Window for viewing status indicator lights; Sealed for tamper-resistance Safety Isolation Sys. Inputs Standard Inputs from Remote Lockout Stations Optional Inputs from Rockwell Automation Safety Products Safety Mats, ➊ Light Curtains, ➊ E-Stop Stations, ➊ Proximity Switches, ➊ Photo Switches ➊ System Operational Limits +10%, -15% of the line voltage

ElectroGuard Overview Principle of Operation Optional Features 2IC1IC GC Incoming

3 Phase

Circuit Protection ➊ Tr ans. Grd Voltage Decay Relays (VDR) To M o t o r Controllers Power Circuit To L o a d s After using the normal stopping method of the machine or process, the machine operator turns a Remote Lockout Station handle from the “On” to “Off ” position. The station signals the isolation contactors (1IC and 2IC) to drop out and isolate the supply voltage from the loads (see Control Circuit). When system residual voltage decays to pre-determined levels, the grounding contactor (GC) is energized, connecting the load to ground (see Power Circuit). The grounding contactor (GC) is electrically and mechanically interlocked with the isolation contactors (1IC and 2IC). The “System Isolated” Light will now illuminate on the Remote Lockout Station to indicate the system is isolated. The machine operator then Locks-Out and Tags-Out the station in the “Off ” position. Control Circuit Remote Lockout Station Off On Mechanically Interlocked 1IC, 2IC, & GC are mechanically and electrically interlocked System Isolated (*) (*) = “On” when the Remote Lockout Station switch is “Off” GC GC 2IC1ICVDR 2IC1ICGC 2IC 1IC GC➊ Available factory installed within the ElectroGuard as an option.

  • Four (4) or ten (10) port Expansion Modules to permit additional Remote Lockout Stations to be used (see page 12-16 for details).
  • Pneumatic Isolation Module to isolate pneumatic energy (see page 12-15 for details).
  • Status communication to a remote PLC (see page 12-17 for details).
  • Fusible disconnect switch (Bulletin 2032) or thermal-magnetic circuit breaker (Bulletin 2033) to provide branch circuit protection. Optional Pneumatic Isolation Module

ElectroGuard Non Combination Systems Product Selection: For North America (see page 12-19 for Ordering Instructions) T o order the Time Delay feature, add the following Catalogue String to the end of the Catalogue Number shown in the table: Example: Catalogue Number 2031-A0180A⊗ becomes Catalogue Number 2031-A0180A⊗ -1TD to include the time delay feature. * Input Power Feed Catalogue Number Code The Catalogue Number as listed is incomplete. Select an Input Power Feed Code from the table below. Example: Catalogue Number 2031*-A0630J⊗ becomes Catalogue Number 2031T-A0630J⊗ for a “Top Feed” input power requirement. ! Bussing Designation The Catalogue Number as listed is incomplete. Select a Bussing Designation Code from the table below. Example: Catalogue Number 2031-!0085J⊗ becomes Catalogue Number 2031-M0085J⊗ for “600A Line Side Incoming Bus and Outgoing Power Cables” bussing designation. ⊗ Input Line Voltage Code The Catalogue Number as listed is incomplete. Select an Input Line Voltage Code from the table below. Example: Catalogue Number 2031-A0085J⊗ becomes Catalogue Number 2031-A0085JB for a 480V 60Hz Input Line Voltage application. ➊ Optional Time Delay Feature. The Safety Isolation System may be ordered with a factory set time delay feature (30 seconds) in order to allow time for the machine operator to shut-down drives or other equipment that requires a controlled stop, after the operating handle on a Remote Lockout Station has been moved to the “Off” position. Consult your local Rockwell Automation sales office for other time settings. ➋ Bus Type: Copper with tin plating. Consult factory for other types of bussing. Ampere Rating (AC-3) 3-Phase Max. Hp Rating (60Hz) Catalogue Number ➊ 200V 230V 460V 575V T ype 1 General Purpose Enclosure T ype 12 Dust tight Enclosure Ty p e 1 2 M o t o r Control Centre Ty p e E n c l o s u r e (with bussing) Ty p e 4 Watertight Painted Steel Enclosure Ty p e 4 X Watertight Stainless Steel Enclosure 23 5 7.5 15 15 2031-A0023A⊗ 2031-A0023J⊗ 2031-!0023J⊗ 2031-A0023F⊗ 2031-A0023C⊗ 43 10 15 30 30 2031-A0043A⊗ 2031-A0043J⊗ 2031-!0043J⊗ 2031-A0043F⊗ 2031-A0043C⊗ 85 25 30 60 60 2031-A0085A⊗ 2031-A0085J⊗ 2031-!0085J⊗ 2031-A0085F⊗ 2031-A0085C⊗ 110 40 40 75 100 2031-A0110A⊗ 2031-A0110J⊗ 2031-!0110J⊗ 2031-A0110F⊗ 2031-A0110C⊗ 180 50 60 150 150 2031-A0180A⊗ 2031-A0180J⊗ 2031-!0180J⊗ 2031-A0180F⊗ 2031-A0180C⊗ 210 60 75 - 200 2031-A0210A⊗ 2031-A0210J⊗ 2031-!0210J⊗ 2031-A0210F⊗ 2031-A0210C⊗ 300 100 125 250 300 2031-A0300A⊗ 2031-A0300J⊗ 2031-!0300J⊗ 2031-A0300F⊗ 2031-A0300C⊗ 420 150 175 350 400 2031-A0420A⊗ 2031-A0420J⊗ 2031-!0420J⊗ 2031-A0420F⊗ 2031-A0420C⊗ 630 200 250 500 600 2031*-A0630A⊗ 2031*-A0630J⊗ 2031-!0630J⊗ 2031*-A0630F⊗ 2031*-A0630C⊗ 860 250 300 600 700 2031*-A0860A⊗ 2031*-A0860J⊗ 2031-!0860J⊗ 2031*-A0860F⊗ 2031*-A0860C⊗ 1200 450 450 900 900 2031*-A1200A⊗ 2031*-A1200J⊗ 2031-!1200J⊗ 2031*-A1200F⊗ 2031*-A1200C⊗ Factory set 30 second time delay feature: -1TD Input Power Feed Catalogue Number Code T op Feed T Bottom Feed B Ty p e o f B u s s i n g ➋ Catalogue Number Code 600A Line Side Incoming Bus and Outgoing Power Cables M 1200A Line Side Incoming Bus and Outgoing Power Cables S Line Side Incoming Power Cables and 600A Load Side Outgoing Bus F Line Side Incoming Power Cables and 1200A Load Side Outgoing Bus B Input Line Voltage 208V 60Hz 240V 60Hz 480V 60Hz 600V 60Hz Voltage Code for Catalogue Number HA B C Power Panel One or More Remote Lockout Stations (conduit hub not included)

ElectroGuard Non Combination Systems Product Selection: Remote Lockout Station ➊ Product Selection: For Outside of North America (see page 12-19 for Ordering Instructions) T o order the Time Delay feature, add the following Cat. String to the end of the Cat. No. shown in the table: Example: Catalogue Number 2031-C0180H⊗ becomes Catalogue Number 2031-C0180H⊗ -1TD to include the time delay feature. * Input Power Feed Catalogue Number Code The Catalogue Number as listed is incomplete. Select an Input Power Feed Code from the table below. Example: Catalogue Number 2031*-C0630H⊗ becomes Catalogue Number 2031T-C0630H⊗ for a “Top Feed” input power requirement. ! Bussing Designation The Catalogue Number as listed is incomplete. Select a Bussing Designation Code from the table. Example: Catalogue Number 2031-!0085H⊗ becomes Catalogue Number 2031-E0085H⊗ for “600A Line Side Incoming Bus and Outgoing Power Cables” bussing designation. ⊗ Input Line Voltage Code The Catalogue Number as listed is incomplete. Select an Input Line Voltage Code from the table below. Example: Catalogue Number 2031-C0085P⊗ becomes Catalogue Number 2031-C0085PN for a 380V 50Hz Input Line Voltage application. Product Selection: Remote Lockout Station ➊ ➊ Safety Isolation Systems rated up through 85A can support a maximum of four (4) Remote Lockout Stations (RLS). Systems rated from 110A - 1200A can support a maximum of six (6) RLS. If additional RLS are required, order the optional Expansion Module(s) (see page 12-16). ➋ Optional Time Delay Feature. The Safety Isolation System may be ordered with a factory set time delay feature (30 seconds) in order to allow time for the machine operator to shut-down drives or other equipment that requires a controlled stop, after the operating handle on a Remote Lockout Station has been moved to the “Off” position. Consult your local Rockwell Automation sales office for other time settings. ➌ Bus Type: Copper with tin plating. Consult factory for other types of bussing. “System Isolated” Light Colour Catalogue Number T ype 1 General Purpose Enclosure T ype 12 Dust tight Enclosure T ype 4 Watertight Painted Steel Enclosure T ype 4X Watertight Stainless Steel Enclosure White 2030-RLSAW 2030-RLSJW 2030-RLSFW 2030-RLSCW Ampere Rating (AC-3) 3-Phase Max. kW Rating (50Hz) Catalogue Number ➋ 230V 400V 500V 600V IP 30 Enclosure IP 54 Enclosure IP 54 Motor Control Centre T ype Enclosure (w/bussing) IP 65 Enclosure 23 7.5 11 11 11 2031-C0023P⊗ 2031-C0023H⊗ 2031-!0023H⊗ 2031-C0023W⊗ 43 13 22 22 22 2031-C0043P⊗ 2031-C0043H⊗ 2031-!0043H⊗ 2031-C0043W⊗ 85 25 45 45 45 2031-C0085P⊗ 2031-C0085H⊗ 2031-!0085H⊗ 2031-C0085W⊗ 110 32 55 63 100 2031-C0110P⊗ 2031-C0110H⊗ 2031-!0110H⊗ 2031-C0110W⊗ 180 55 90 110 160 2031-C0180P⊗ 2031-C0180H⊗ 2031-!0180H⊗ 2031-C0180W⊗ 210 63 110 150 200 2031-C0210P⊗ 2031-C0210H⊗ 2031-!0210H⊗ 2031-C0210W⊗ 300 90 160 200 300 2031-C0300P⊗ 2031-C0300H⊗ 2031-!0300H⊗ 2031-C0300W⊗ 420 132 220 300 425 2031-C0420P⊗ 2031-C0420H⊗ 2031-!0420H⊗ 2031-C0420W⊗ 630 200 355 450 500 2031*-C0630P⊗ 2031*-C0630H⊗ 2031-!0630H⊗ 2031*-C0630W⊗ 860 250 500 560 600 2031*-C0860P⊗ 2031*-C0860H⊗ 2031-!0860H⊗ 2031*-C0860W⊗ 1200 391 710 888 1043 2031*-C1200P⊗ 2031*-C1200H⊗ 2031-!1200H⊗ 2031*-C1200W⊗ Factory set 30 second time delay feature: -1TD Input Power Feed Catalogue Number Code T op Feed T Bottom Feed B Ty p e o f B u s s i n g ➌ Catalogue Number Code 600A Line Side Incoming Bus and Outgoing Power Cables E 1200A Line Side Incoming Bus and Outgoing Power Cables D Line Side Incoming Power Cables and 600A Load Side Outgoing Bus H Line Side Incoming Power Cables and 1200A Load Side Outgoing Bus R Input Line Voltage 220V 50HZ 380-400V 50Hz 400-415V 50Hz 440V 50Hz 500V 50Hz 550V 50Hz Voltage Code for Catalogue Number A N G B M C “System Isolated” Light Colour Catalogue Number IP 30 Enclosure IP 54 Enclosure IP 65 Enclosure Green 2030-RLSPG 2030-RLSHG 2030-RLSWG

ElectroGuard Combination Systems with Fusible Disconnect Switch Product Selection: For North America (see page 12-19 for Ordering Instructions) T o order the Time Delay feature, add the following Catalogue String to the end of the Cat. No. shown in the table: Example: Catalogue Number 2032-A0180A⊗ -27J becomes Catalogue Number 2032-A0180A⊗ -27J-1TD to include the time delay feature. * Input Power Feed Catalogue Number Code The Catalogue Number as listed is incomplete. Select an Input Power Feed Code from the table below. Example: Catalogue Number 2032*-A0630J⊗ -30L becomes Catalogue Number 2032T-A0630J⊗ -30L for a “Top Feed” input power requirement. ➊ Power fuses are not included with the disconnect switch. Select power fuses in accordance with applicable local codes. ➋ Optional Time Delay Feature. The Safety Isolation System may be ordered with a factory set time delay feature (30 seconds) in order to allow time for the machine operator to shut-down drives or other equipment that requires a controlled stop, after the operating handle on a Remote Lockout Station has been moved to the “Off” position. Consult your local Rockwell Automation sales office for other time settings. Amp. Rating (AC-3) 3-Phase Max. Hp Rating (60Hz) Fuse Clip Rating/ Ty p e ➊ Catalogue Number ➋ 200 V 230 V 460 V 575 V Ty p e 1 G e n e r a l Purpose Enclosure T ype 12 Dust tight Enclosure T ype 12 Motor Control Centre T ype Enclosure (with bussing) Ty p e 4 Watertight Painted Steel Enclosure Ty p e 4 X Watertight Stainless Steel Enclosure 23 5 7.5 15 15 30A Class J 2032-A0023A⊗ -24J 2032-A0023J ⊗ -24J 2032- !0023J⊗ -24J 2032-A0023F ⊗ -24J 2032-A0023C ⊗ -24J 60A Class J 2032-A0023A⊗ -25J 2032-A0023J ⊗ -25J 2032- !0023J⊗ -25J 2032-A0023F ⊗ -25J 2032-A0023C ⊗ -25J 43 10 15 30 30 60A Class J 2032-A0043A⊗ -25J 2032-A0043J ⊗ -25J 2032- !0043J⊗ -25J 2032-A0043F ⊗ -25J 2032-A0043C ⊗ -25J 100A Class J 2032-A0043A⊗ -26J 2032-A0043J ⊗ -26J 2032- !0043J⊗ -26J 2032-A0043F ⊗ -26J 2032-A0043C ⊗ -26J 85 25 30 60 60 100A Class J 2032-A0085A⊗ -26J 2032-A0085J ⊗ -26J 2032- !0085J⊗ -26J 2032-A0085F ⊗ -26J 2032-A0085C ⊗ -26J 200A Class J 2032-A0085A⊗ -27J 2032-A0085J ⊗ -27J 2032- !0085J⊗ -27J 2032-A0085F ⊗ -27J 2032-A0085C ⊗ -27J 110 40 40 75 100 200A Class J 2032-A0110A⊗ -27J 2032-A0110J ⊗ -27J 2032- !0110J⊗ -27J 2032-A0110F ⊗ -27J 2032-A0110C ⊗ -27J 400A Class J 2032-A0110A⊗ -28J 2032-A0110J ⊗ -28J 2032- !0110J⊗ -28J 2032-A0110F ⊗ -28J 2032-A0110C ⊗ -28J 180 50 60 125 150 200A Class J 2032-A0180A⊗ -27J 2032-A0180J ⊗ -27J 2032- !0180J⊗ -27J 2032-A0180F ⊗ -27J 2032-A0180C ⊗ -27J 400A Class J 2032-A0180A⊗ -28J 2032-A0180J ⊗ -28J 2032- !0180J⊗ -28J 2032-A0180F ⊗ -28J 2032-A0180C ⊗ -28J 210 60 75 150 200 400A Class J 2032-A0210A⊗ -28J 2032-A0210J ⊗ -28J 2032- !0210J⊗ -28J 2032-A0210F ⊗ -28J 2032-A0210C ⊗ -28J 300 75 125 250 300 400A Class J 2032-A0300A⊗ -28J 2032-A0300J ⊗ -28J 2032- !0300J⊗ -28J 2032-A0300F ⊗ -28J 2032-A0300C ⊗ -28J 600A Class J 2032-A0300A⊗ -29J 2032-A0300J ⊗ -29J 2032- !0300J⊗ -29J 2032-A0300F ⊗ -29J 2032-A0300C ⊗ -29J 420 150 175 350 400 600A Class J 2032-A0420A⊗ -29J 2032-A0420J ⊗ -29J 2032- !0420J⊗ -29J 2032-A0420F ⊗ -29J 2032-A0420C ⊗ -29J 800A Class L 2032-A0420A⊗ -30L 2032-A0420J ⊗ -30L 2032- !0420J⊗ -30L 2032-A0420F ⊗ -30L 2032-A0420C ⊗ -30L 630 200 250 500 600 800A Class L 2032*-A0630A⊗ -30L 2032*-A0630J ⊗ -30L 2032- !0630J⊗ -30L 2032*-A0630F ⊗ -30L 2032*-A0630C ⊗ -30L 2000A Class L 2032*-A0630A⊗ -34L 2032*-A0630J ⊗ -34L 2032- !0630J⊗ -34L 2032*-A0630F ⊗ -34L 2032*-A0630C ⊗ -34L 860 250 300 600 700 2000A Class L 2032*-A0860A⊗ -34L 2032*-A0860J ⊗ -34L 2032- !0860J⊗ -34L 2032*-A0860F ⊗ -34L 2032*-A0860C ⊗ -34L 1200 450 450 900 900 2000A Class L 2032*-A1200A⊗ -34L 2032*-A1200J ⊗ -34L 2032- !1200J⊗ -34L 2032*-A1200F ⊗ -34L 2032*-A1200C ⊗ -34L Factory set 30 second time delay feature: -1TD Input Power Feed Catalogue Number Code T op Feed T Bottom Feed B

ElectroGuard Combination Systems with Fusible Disconnect Switch ! Bussing Designation The Catalogue Number as listed is incomplete. Select a Bussing Designation Code from the table below. Example: Cat. No. 2032-!0085J⊗ -26J becomes Cat. No. 2032-M0085J⊗ -26J for “600A Line Side Incoming Bus and Outgoing Power Cables” bussing designation. ⊗ Input Line Voltage Code The Catalogue Number as listed is incomplete. Select an Input Line Voltage Code from the table below. Example: Catalogue Number 2032-A0085J⊗ -26J becomes Catalogue Number 2032-A0085JB-26J for a 480V 60Hz Input Line Voltage application. Product Selection: Remote Lockout Station ➋ ➊ Bus Type: Copper with tin plating. Consult factory for other types of bussing. ➋ Safety Isolation Systems rated up through 85A can support a maximum of four (4) Remote Lockout Stations (RLS). Systems rated from 110A - 1200A can support a maximum of six (6) RLS. If additional RLS are required, order the optional Expansion Module(s) (see page 12-16). Ty p e o f B u s s i n g ➊ Catalogue Number Code 600A Line Side Incoming Bus and Outgoing Power Cables M 1200A Line Side Incoming Bus and Outgoing Power Cables S Line Side Incoming Power Cables and 600A Load Side Outgoing Bus F Line Side Incoming Power Cables and 1200A Load Side Outgoing Bus B Input Line Voltage 208V 60Hz 240V 60Hz 480V 60Hz 600V 60Hz Voltage Code for Catalogue Number HA B C “System Isolated” Light Colour Catalogue Number T ype 1 General Purpose Enclosure T ype 12 Dust tight Enclosure T ype 4 Watertight Painted Steel Enclosure T ype 4X Watertight Stainless Steel Enclosure White 2030-RLSAW 2030-RLSJW 2030-RLSFW 2030-RLSCW

ElectroGuard Combination Systems with Fusible Disconnect Switch Product Selection for Outside of North America (see page 12-19 for Ordering Instructions) ➊ Power fuses are not included with the disconnect switch. Select power fuses in accordance with applicable local codes. ➋ Optional Time Delay Feature. The Safety Isolation System may be ordered with a factory set time delay feature (30 seconds) in order to allow time for the machine operator to shut-down drives or other equipment that requires a controlled stop, after the operating handle on a Remote Lockout Station has been moved to the “Off” position. See next page for instructions on how to order the optional time delay feature. Consult your local Rockwell Automation sales office for other time settings. Amp. Rating (AC-3) 3-Phase Max. kW Rating (50Hz) Fuse Clip Rating/ Ty p e ➊ Catalogue Number ➋ 230V 400V 500V 600V IP 30 Enclosure IP 54 Enclosure IP 54 Motor Control Centre T ype Enclosure (with bussing) IP 65 Enclosure 2 3 5 . 51 11 11 1 20A BS 88 2032-C0023P⊗ -23B 2032-C0023H ⊗ -23B 2032- !0023H⊗ -23B 2032-C0023W ⊗ -23B 32A BS 88 2032-C0023P⊗ -24B 2032-C0023H ⊗ -24B 2032- !0023H⊗ -24B 2032-C0023W ⊗ -24B 63A BS 88 2032-C0023P⊗ -25B 2032-C0023H ⊗ -25B 2032- !0023H⊗ -25B 2032-C0023W ⊗ -25B 63A DIN 2032-C0023P⊗ -25D 2032-C0023H ⊗ -25D 2032- !0023H⊗ -25D 2032-C0023W ⊗ -25D 43 11 22 22 22 63A BS 88 2032-C0043P⊗ -25B 2032-C0043H ⊗ -25B 2032- !0043H⊗ -25B 2032-C0043W ⊗ -25B 63A DIN 2032-C0043P⊗ -25D 2032-C0043H ⊗ -25D 2032- !0043H⊗ -25D 2032-C0043W ⊗ -25D 100A BS 88 2032-C0043P⊗ -26B 2032-C0043H ⊗ -26B 2032- !0043H⊗ -26B 2032-C0043W ⊗ -26B 100A DIN 2032-C0043P⊗ -26D 2032-C0043H ⊗ -26D 2032- !0043H⊗ -26D 2032-C0043W ⊗ -26D 85 22 45 45 45 100A BS 88 2032-C0085P⊗ -26B 2032-C0085H ⊗ -26B 2032- !0085H⊗ -26B 2032-C0085W ⊗ -26B 100A DIN 2032-C0085P⊗ -26D 2032-C0085H ⊗ -26D 2032- !0085H⊗ -26D 2032-C0085W ⊗ -26D 200A BS 88 2032-C0085P⊗ -27B 2032-C0085H ⊗ -27B 2032- !0085H⊗ -27B 2032-C0085W ⊗ -27B 160A DIN 2032-C0085P⊗ -27D 2032-C0085H ⊗ -27D 2032- !0085H⊗ -27D 2032-C0085W ⊗ -27D 110 32 55 63 100 100A BS88 2032-C0110P⊗ -26B 2032-C0110H ⊗ -26B 2032- !0110H⊗ -26B 2032-C0110W ⊗ -26B 100A DIN 2032-C0110P⊗ -26D 2032-C0110H ⊗ -26D 2032- !0110H⊗ -26D 2032-C0110W ⊗ -26D 200A BS 88 2032-C0110P⊗ -27B 2032-C0110H ⊗ -27B 2032- !0110H⊗ -27B 2032-C0110W ⊗ -27B 160A DIN 2032-C0110P⊗ -27D 2032-C0110H ⊗ -27D 2032- !0110H⊗ -27D 2032-C0110W ⊗ -27D 250A DIN 2032-C0110P⊗ -28D 2032-C0110H ⊗ -28D 2032- !0110H⊗ -28D 2032-C0110W ⊗ -28D 180 45 90 110 110 200A BS 88 2032-C0180P⊗ -27B 2032-C0180H ⊗ -27B 2032- !0180H⊗ -27B 2032-C0180W ⊗ -27B 250A DIN 2032-C0180P⊗ -28D 2032-C0180H ⊗ -28D 2032- !0180H⊗ -28D 2032-C0180W ⊗ -28D 400A BS 88 2032-C0180P⊗ -29B 2032-C0180H ⊗ -29B 2032- !0180H⊗ -29B 2032-C0180W ⊗ -29B 400A DIN 2032-C0180P⊗ -29D 2032-C0180H ⊗ -29D 2032- !0180H⊗ -29D 2032-C0180W ⊗ -29D 210 63 110 150 200 200A BS 88 2032-C0210P⊗ -27B 2032-C0210H ⊗ -27B 2032- !0210H⊗ -27B 2032-C0210W ⊗ -27B 250A DIN 2032-C0210P⊗ -28D 2032-C0210H ⊗ -28D 2032- !0210H⊗ -28D 2032-C0210W ⊗ -28D 400A BS 88 2032-C0210P⊗ -29B 2032-C0210H ⊗ -29B 2032- !0210H⊗ -29B 2032-C0210W ⊗ -29B 400A DIN 2032-C0210P⊗ -29D 2032-C0210H ⊗ -29D 2032- !0210H⊗ -29D 2032-C0210W ⊗ -29D 300 90 160 200 257 400A BS 88 2032-C0300P⊗ -29B 2032-C0300H ⊗ -29B 2032- !0300H⊗ -29B 2032-C0300W ⊗ -29B 400A DIN 2032-C0300P⊗ -29D 2032-C0300H ⊗ -29D 2032- !0300H⊗ -29D 2032-C0300W ⊗ -29D 630A BS 88 2032-C0300P⊗ -30B 2032-C0300H ⊗ -30B 2032- !0300H⊗ -30B 2032-C0300W ⊗ -30B 630A DIN 2032-C0300P⊗ -30D 2032-C0300H ⊗ -30D 2032- !0300H⊗ -30D 2032-C0300W ⊗ -30D 420 132 220 300 425 400A BS88 2032-C0420P⊗ -29B 2032-C0420H ⊗ -29B 2032- !0420H⊗ -29B 2032-C0420W ⊗ -29B 400A DIN 2032-C0420P⊗ -29D 2032-C0420H ⊗ -29D 2032- !0420H⊗ -29D 2032-C0420W ⊗ -29D 630A BS 88 2032-C0420P⊗ -30B 2032-C0420H ⊗ -30B 2032- !0420H⊗ -30B 2032-C0420W ⊗ -30B 630A DIN 2032-C0420P⊗ -30D 2032-C0420H ⊗ -30D 2032- !0420H⊗ -30D 2032-C0420W ⊗ -30D 630 200 355 450 500 630A BS 88 2032*-C0630P⊗ -30B 2032*-C0630H ⊗ -30B 2032- !0630H⊗ -30B 2032*-C0630W ⊗ -30B

ElectroGuard Combination Systems with Fusible Disconnect Switch Product Selection for Outside North America (see page 12-19 for Ordering Instructions) T o order the Time Delay feature, add the following Cat. String to the end of the Catalogue Number shown in the table: Example: Catalogue Number 2032-C0180P⊗ -29B becomes Catalogue Number 2032-C0180P⊗ -29B-1TD to include the time delay feature. * Input Power Feed Catalogue Number Code The Catalogue Number as listed is incomplete. Select an Input Power Feed Code from the table below. Example: Catalogue Number 2032*-C0630P⊗ -31B becomes Catalogue Number 2032T-C0630P⊗ -31B for a “Top Feed” input power requirement. ! Bussing Designation The Catalogue Number as listed is incomplete. Select a Bussing Designation Code from the table below. Example: Catalogue Number 2032-!0085H⊗ -27D becomes Catalogue Number 2032-E0085H⊗ -27D for “600A Line Side Incoming Bus and Outgoing Power Cables” bussing designation. ⊗ Input Line Voltage Code The Catalogue Number as listed is incomplete. Select an Input Line Voltage Code from the table below. Example: Catalogue Number 2032-C0085W⊗ -26B becomes Catalogue Number 2032-C0085WN-26B for a 380V 50Hz Input Line Voltage application. Product Selection: Remote Lockout Station ➍ ➊ Power fuses are not included with the disconnect switch. Select power fuses in accordance with applicable local codes. ➋ Optional Time Delay Feature. The Safety Isolation System may be ordered with a factory set time delay feature (30 seconds) in order to allow time for the machine operator to shut-down drives or other equipment that requires a controlled stop, after the operating handle on a Remote Lockout Station has been moved to the “Off” position. Consult your local Rockwell Automation sales office for other time settings. ➌ Bus Type: Copper with tin plating. Consult factory for other types of bussing. ➍ Safety Isolation Systems rated up through 85A can support a maximum of four (4) Remote Lockout Stations (RLS). Systems rated from 110A - 1200A can support a maximum of six (6) RLS. If additional RLS are required, order the optional Expansion Module(s) (see page 12-16). Ampere Rating (AC-3) 3-Phase Max. kW Rating (50Hz) Fuse Clip Rating/ Ty p e ➊ Catalogue Number ➋ 230V 400V 500V 600V IP 30 Enclosure IP 54 Enclosure IP 54 Motor Control Centre T ype Enclosure (with bussing) IP 65 Enclosure 630 200 355 450 500 630A DIN 2032*-C0630P⊗ -30D 2032*-C0630H ⊗ -30D 2032- !0630H⊗ 30D 2032*-C0630W ⊗ -30D 800A BS 88 2032*-C0630P⊗ -31B 2032*-C0630H ⊗ -31B 2032- !0630H⊗ -31B 2032*-C0630W ⊗ -31B 1600A DIN 2032*-C0630P⊗ -31D 2032*-C0630H ⊗ -31D 2032- !0630H⊗ -31D 2032*-C0630W ⊗ -31D 860 250 500 560 600 800A BS 88 2032*-C0860P⊗ -31B 2032*-C0860H ⊗ -31B 2032- !0860H⊗ -31B 2032*-C0860W ⊗ -31B 1250A BS 88 2032*-C0860P⊗ -32B 2032*-C0860H ⊗ -32B 2032- !0860H⊗ -32B 2032*-C0860W ⊗ -32B 1600A DIN 2032*-C0860P⊗ -31D 2032*-C0860H ⊗ -31D 2032- !0860H⊗ -31D 2032*-C0860W ⊗ -31D 1200 391 710 888 1043 1250A BS 88 2032*-C1200P⊗ -32B 2032*-C1200H ⊗ -32B 2032- !1200H⊗ -32B 2032*-C1200W ⊗ -32B 1600A DIN 2032*-C1200P⊗ -31D 2032*-C1200H ⊗ -31D 2032- !1200H⊗ -31D 2032*-C1200W ⊗ -31D Factory set 30 second time delay feature: -1TD Input Power Feed Catalogue Number Code T op Feed T Bottom Feed B Ty p e o f B u s s i n g ➌ Catalogue Number Code 600A Line Side Incoming Bus and Outgoing Power Cables E 1200A Line Side Incoming Bus and Outgoing Power Cables D Line Side Incoming Power Cables and 600A Load Side Outgoing Bus H Line Side Incoming Power Cables and 1200A Load Side Outgoing Bus R Input Line Voltage 220V 50Hz 380-400V 50Hz 400-415V 50Hz 440V 50Hz 500V 50Hz 550V 50Hz Voltage Code for Catalogue Number AN G B M C “System Isolated” Light Colour Catalogue Number IP 30 Enclosure IP 54 Enclosure IP 65 Enclosure Green 2030-RLSPG 2030-RLSHG 2030-RLSWG

ElectroGuard Combination Systems with Thermal-magnetic Circuit Breaker Product Selection for North America (see page 12-19 for Ordering Instructions) ➊ Optional Time Delay Feature. The Safety Isolation System may be ordered with a factory set time delay feature (30 seconds) in order to allow time for the machine operator to shut-down drives or other equipment that requires a controlled stop, after the operating handle on a Remote Lockout Station has been moved to the “Off” position. See next page for instructions on how to order the optional time delay feature. Consult your local Rockwell Automation sales office for other time settings. Ampere Rating (AC-3) 3-Phase Max. Hp Rating (60Hz) Catalogue Number ➊ 200V 230V 460V 575V Ty p e 1 G e n e r a l Purpose Enclosure T ype 12 Dust tight Enclosure Ty p e 1 2 M o t o r Control Centre Ty p e E n c l o s u r e (with bussing) T ype 4 Watertight Painted Steel Enclosure Ty p e 4 X Watertight Stainless Steel Enclosure 5555 2033-A0023A⊗ -39 2033-A0023J ⊗ -39 2033- !0023J⊗ -39 2033-A0023F ⊗ -39 2033-A0023C ⊗ -39 -7 . 5 7 . 5 7 . 5 2033-A0023A⊗ -40 2033-A0023J ⊗ -40 2033- !0023J⊗ -40 2033-A0023F ⊗ -40 2033-A0023C ⊗ -40 -- 1 0 1 0 2033-A0023A⊗ -41 2033-A0023J ⊗ -41 2033- !0023J⊗ -41 2033-A0023F ⊗ -41 2033-A0023C ⊗ -41 -- 1 5 1 5 2033-A0023A⊗ -42 2033-A0023J ⊗ -42 2033- !0023J⊗ -42 2033-A0023F ⊗ -42 2033-A0023C ⊗ -42 7.5 - - - 2033-A0043A⊗ -40 2033-A0043J ⊗ -40 2033- !0043J⊗ -40 2033-A0043F ⊗ -40 2033-A0043C ⊗ -40 10 10 - - 2033-A0043A⊗ -41 2033-A0043J ⊗ -41 2033- !0043J⊗ -41 2033-A0043F ⊗ -41 2033-A0043C ⊗ -41 -1 5- - 2033-A0043A⊗ -42 2033-A0043J ⊗ -42 2033- !0043J⊗ -42 2033-A0043F ⊗ -42 2033-A0043C ⊗ -42 -- 2 0 2 0 2033-A0043A⊗ -43 2033-A0043J ⊗ -43 2033- !0043J⊗ -43 2033-A0043F ⊗ -43 2033-A0043C ⊗ -43 -- 2 5 2 5 2033-A0043A⊗ -44 2033-A0043J ⊗ -44 2033- !0043J⊗ -44 2033-A0043F ⊗ -44 2033-A0043C ⊗ -44 -- 3 0 3 0 2033-A0043A⊗ -45 2033-A0043J ⊗ -45 2033- !0043J⊗ -45 2033-A0043F ⊗ -45 2033-A0043C ⊗ -45 15 - - - 2033-A0085A⊗ -42 2033-A0085J ⊗ -42 2033- !0085J⊗ -42 2033-A0085F ⊗ -42 2033-A0085C ⊗ -42 20 20 - - 2033-A0085A⊗ -43 2033-A0085J ⊗ -43 2033- !0085J⊗ -43 2033-A0085F ⊗ -43 2033-A0085C ⊗ -43 25 25 - - 2033-A0085A⊗ -44 2033-A0085J ⊗ -44 2033- !0085J⊗ -44 2033-A0085F ⊗ -44 2033-A0085C ⊗ -44 -3 0- - 2033-A0085A⊗ -45 2033-A0085J ⊗ -45 2033- !0085J⊗ -45 2033-A0085F ⊗ -45 2033-A0085C ⊗ -45 -- 4 0 4 0 2033-A0085A⊗ -46 2033-A0085J ⊗ -46 2033- !0085J⊗ -46 2033-A0085F ⊗ -46 2033-A0085C ⊗ -46 -- 5 0 5 0 2033-A0085A⊗ -47 2033-A0085J ⊗ -47 2033- !0085J⊗ -47 2033-A0085F ⊗ -47 2033-A0085C ⊗ -47 -- 6 0 6 0 2033-A0085A⊗ -48 2033-A0085J ⊗ -48 2033- !0085J⊗ -48 2033-A0085F ⊗ -48 2033-A0085C ⊗ -48 110 30 - - - 2033-A0110A⊗ -45 2033-A0110J ⊗ -45 2033- !0110J⊗ -45 2033-A0110F ⊗ -45 2033-A0110C ⊗ -45 40 40 - - 2033-A0110A⊗ -46 2033-A0110J ⊗ -46 2033- !0110J⊗ -46 2033-A0110F ⊗ -46 2033-A0110C ⊗ -46 -- 7 5 7 5 2033-A0110A⊗ -49 2033-A0110J ⊗ -49 2033- !0110J⊗ -49 2033-A0110F ⊗ -49 2033-A0110C ⊗ -49 --- 1 0 0 2033-A0110A⊗ -50 2033-A0110J ⊗ -50 2033- !0110J⊗ -50 2033-A0110F ⊗ -50 2033-A0110C ⊗ -50 180 50 50 - - 2033-A0180A⊗ -47 2033-A0180J ⊗ -47 2033- !0180J⊗ -47 2033-A0180F ⊗ -47 2033-A0180C ⊗ -47 -6 0- - 2033-A0180A⊗ -48 2033-A0180J ⊗ -48 2033- !0180J⊗ -48 2033-A0180F ⊗ -48 2033-A0180C ⊗ -48 - - 100 - 2033-A0180A⊗ -50 2033-A0180J ⊗ -50 2033- !0180J⊗ -50 2033-A0180F ⊗ -50 2033-A0180C ⊗ -50 - - 125 125 2033-A0180A⊗ -51 2033-A0180J ⊗ -51 2033- !0180J⊗ -51 2033-A0180F ⊗ -51 2033-A0180C ⊗ -51 - - 150 150 2033-A0180A⊗ -52 2033-A0180J ⊗ -52 2033- !0180J⊗ -52 2033-A0180F ⊗ -52 2033-A0180C ⊗ -52 210 60 - - - 2033-A0210A⊗ -48 2033-A0210J ⊗ -48 2033- !0210J⊗ -48 2033-A0210F ⊗ -48 2033-A0210C ⊗ -48 -7 5- - 2033-A0210A⊗ -49 2033-A0210J ⊗ -49 2033- !0210J⊗ -49 2033-A0210F ⊗ -49 2033-A0210C ⊗ -49 --- 1 7 5 2033-A0210A⊗ -53 2033-A0210J ⊗ -53 2033- !0210J⊗ -53 2033-A0210F ⊗ -53 2033-A0210C ⊗ -53 --- 2 0 0 2033-A0210A⊗ -54 2033-A0210J ⊗ -54 2033- !0210J⊗ -54 2033-A0210F ⊗ -54 2033-A0210C ⊗ -54 300 75 - - - 2033-A0300A⊗ -49 2033-A0300J ⊗ -49 2033- !0300J⊗ -49 2033-A0300F ⊗ -49 2033-A0300C ⊗ -49 100 100 - - 2033-A0300A⊗ -50 2033-A0300J ⊗ -50 2033- !0300J⊗ -50 2033-A0300F ⊗ -50 2033-A0300C ⊗ -50 -1 2 5- - 2033-A0300A⊗ -51 2033-A0300J ⊗ -51 2033- !0300J⊗ -51 2033-A0300F ⊗ -51 2033-A0300C ⊗ -51

ElectroGuard Combination Systems with Thermal-magnetic Circuit Breaker Product Selection for North America (see page 12-19 for Ordering Instructions) T o order the Time Delay feature, add the following Catalogue String to the end of the Catalogue Number shown in the table: Example: Catalogue Number 2033-A0180A⊗ -50 becomes Catalogue Number 2033-A0180A⊗ -50-1TD to include the time delay feature. * Input Power Feed Catalogue Number Code The Catalogue Number as listed is incomplete. Select an Input Power Feed Code from the table below. Example: Catalogue Number 2033*-A0630A⊗ -60 becomes Catalogue Number 2033T-A0630A⊗ -60 for a “Top Feed” input power requirement. ➊ Optional Time Delay Feature. The Safety Isolation System may be ordered with a factory set time delay feature (30 seconds) in order to allow time for the machine operator to shut-down drives or other equipment that requires a controlled stop, after the operating handle on a Remote Lockout Station has been moved to the “Off” position. Consult your local Rockwell Automation sales office for other time settings. Ampere Rating (AC-3) 3-Phase Max. Hp Rating (60Hz) Catalogue Number ➊ 200V 230V 460V 575V T ype 1 General Purpose Enclosure Ty p e 1 2 Dust tight Enclosure T ype 12 Motor Control Centre T ype Enclosure (with bussing) T ype 4 Watertight Painted Steel Enclosure Ty p e 4 X Watertight Stainless Steel Enclosure 300 -- 1 7 5 - 2033-A0300A⊗ -53 2033-A0300J ⊗ -53 2033- !0300J⊗ -53 2033-A0300F ⊗ -53 2033-A0300C ⊗ -53 -- 2 0 0 - 2033-A0300A⊗ -54 2033-A0300J ⊗ -54 2033- !0300J⊗ -54 2033-A0300F ⊗ -54 2033-A0300C ⊗ -54 - - 250 250 2033-A0300A⊗ -56 2033-A0300J ⊗ -56 2033- !0300J⊗ -56 2033-A0300F ⊗ -56 2033-A0300C ⊗ -56 - - - 300 2033-A0300A⊗ -57 2033-A0300J ⊗ -57 2033- !0300J⊗ -57 2033-A0300F ⊗ -57 2033-A0300C ⊗ -57 420 125 - - - 2033-A0420A⊗ -51 2033-A0420J ⊗ -51 2033- !0420J⊗ -51 2033-A0420F ⊗ -51 2033-A0420C ⊗ -51 150 150 - - 2033-A0420A⊗ -52 2033-A0420J ⊗ -52 2033- !0420J⊗ -52 2033-A0420F ⊗ -52 2033-A0420C ⊗ -52 - 175 - - 2033-A0420A⊗ -53 2033-A0420J ⊗ -53 2033- !0420J⊗ -53 2033-A0420F ⊗ -53 2033-A0420C ⊗ -53 -- 3 0 0 - 2033-A0420A⊗ -57 2033-A0420J ⊗ -57 2033- !0420J⊗ -57 2033-A0420F ⊗ -57 2033-A0420C ⊗ -57 - - 350 350 2033-A0420A⊗ -58 2033-A0420J ⊗ -58 2033- !0420J⊗ -58 2033-A0420F ⊗ -58 2033-A0420C ⊗ -58 - - - 400 2033-A0420A⊗ -59 2033-A0420J ⊗ -59 2033- !0420J⊗ -59 2033-A0420F ⊗ -59 2033-A0420C ⊗ -59 630 175 - - - 2033*-A0630A⊗ -53 2033*-A0630J ⊗ -53 2033- !0630J⊗ -53 2033*-A0630F ⊗ -53 2033*-A0630C ⊗ -53 200 200 - - 2033*-A0630A⊗ -54 2033*-A0630J ⊗ -54 2033- !0630J⊗ -54 2033*-A0630F ⊗ -54 2033*-A0630C ⊗ -54 - 250 - - 2033*-A0630A⊗ -56 2033*-A0630J ⊗ -56 2033- !0630J⊗ -56 2033*-A0630F ⊗ -56 2033*-A0630C ⊗ -56 -- 4 0 0 - 2033*-A0630A⊗ -59 2033*-A0630J ⊗ -59 2033- !0630J⊗ -59 2033*-A0630F ⊗ -59 2033*-A0630C ⊗ -59 - - 450 450 2033*-A0630A⊗ -60 2033*-A0630J ⊗ -60 2033- !0630J⊗ -60 2033*-A0630F ⊗ -60 2033*-A0630C ⊗ -60 - - 500 500 2033*-A0630A⊗ -61 2033*-A0630J ⊗ -61 2033- !0630J⊗ -61 2033*-A0630F ⊗ -61 2033*-A0630C ⊗ -61 - - - 600 2033*-A0630A⊗ -62 2033*-A0630J ⊗ -62 2033- !0630J⊗ -62 2033*-A0630F ⊗ -62 2033*-A0630C ⊗ -62 860 250 - - - 2033*-A0860A⊗ -56 2033*-A0860J ⊗ -56 2033- !0860J⊗ -56 2033*-A0860F ⊗ -56 2033*-A0860C ⊗ -56 - 300 - - 2033*-A0860A⊗ -57 2033*-A0860J ⊗ -57 2033- !0860J⊗ -57 2033*-A0860F ⊗ -57 2033*-A0860C ⊗ -57 -- 6 0 0 - 2033*-A0860A⊗ -62 2033*-A0860J ⊗ -62 2033- !0860J⊗ -62 2033*-A0860F ⊗ -62 2033*-A0860C ⊗ -62 - - - 700 2033*-A0860A⊗ -63 2033*-A0860J ⊗ -63 2033- !0860J⊗ -63 2033*-A0860F ⊗ -63 2033*-A0860C ⊗ -63 1200 300 - - - 2033*-A1200A⊗ -57 2033*-A1200J ⊗ -57 2033- !1200J⊗ -57 2033*-A1200F ⊗ -57 2033*-A1200C ⊗ -57 350 350 - - 2033*-A1200A⊗ -58 2033*-A1200J ⊗ -58 2033- !1200J⊗ -58 2033*-A1200F ⊗ -58 2033*-A1200C ⊗ -58 400 400 - - 2033*-A1200A⊗ -59 2033*-A1200J ⊗ -59 2033- !1200J⊗ -59 2033*-A1200F ⊗ -59 2033*-A1200C ⊗ -59 450 450 - - 2033*-A1200A⊗ -60 2033*-A1200J ⊗ -60 2033- !1200J⊗ -60 2033*-A1200F ⊗ -60 2033*-A1200C ⊗ -60 - - 900 900 2033*-A1200A⊗ -66 2033*-A1200J ⊗ -66 2033- !1200J⊗ -66 2033*-A1200F ⊗ -66 2033*-A1200C ⊗ -66 Factory set 30 second time delay feature: -1TD Input Power Feed Catalogue Number Code T op Feed T Bottom Feed B

ElectroGuard Combination Systems with Thermal-magnetic Circuit Breaker ! Bussing Designation The Catalogue Number as listed is incomplete. Select a Bussing Designation Code from the table below. ⊗ Input Line Voltage Code The Catalogue Number as listed is incomplete. Select an Input Line Voltage Code from the table below. Example: Catalogue Number 2033-A0085J⊗ -44 becomes Catalogue Number 2033-A0085JB-44 for a 480V 60Hz Input Line Voltage application. Product Selection: Remote Lockout Station ➋ Combination Systems with Thermal-magnetic Circuit Breaker Product Selection for Outside of North America (see page 12-19 for Ordering Instructions) ➊ Bus Type: Copper with tin plating. Consult factory for other types of bussing. ➋ Safety Isolation Systems rated up through 85A can support a maximum of four (4) Remote Lockout Stations (RLS). Systems rated from 110A - 1200A can support a maximum of six (6) RLS. If additional RLS are required, order the optional Expansion Module(s) (see page 12-16). ➌ Optional Time Delay Feature. The Safety Isolation System may be ordered with a factory set time delay feature (30 seconds) in order to allow time for the machine operator to shut-down drives or other equipment that requires a controlled stop, after the operating handle on a Remote Lockout Station has been moved to the “Off” position. See page 12-14 for instructions on how to order the optional time delay feature. Consult your local Rockwell Automation sales office for other time settings. Ty p e o f B u s s i n g ➊ Catalogue Number Code 600A Line Side Incoming Bus and Outgoing Power Cables M 1200A Line Side Incoming Bus and Outgoing Power Cables S Line Side Incoming Power Cables and 600A Load Side Outgoing Bus F Line Side Incoming Power Cables and 1200A Load Side Outgoing Bus B Input Line Voltage 208V 60Hz 240V 60Hz 480V 60Hz 600V 60Hz Voltage Code for Catalogue Number HABC “System Isolated” Light Colour Catalogue Number T ype 1 General Purpose Enclosure T ype 12 Dust tight Enclosure T ype 4 Watertight Painted Steel Enclosure T ype 4X Watertight Stainless Steel Enclosure White 2030-RLSAW 2030-RLSJW 2030-RLSFW 2030-RLSCW Ampere Rating (AC-3) 3-Phase Max. kW Rating (50Hz) Catalogue Number ➌ 230V 400V 500V 600V IP 30 Enclosure IP 54 Enclosure IP 54 Motor Control Centre T ype Enclosure (w/bussing) IP 65 Enclosure 4444 2033-C0023P⊗ -39K 2033-C0023H ⊗ -39K 2033- !0023H⊗ -39K 2033-C0023W ⊗ -39K 5.5 5.5 5.5 5.5 2033-C0023P⊗ -40K 2033-C0023H ⊗ -40K 2033- !0023H⊗ -40K 2033-C0023W ⊗ -40K 7.5 7.5 7.5 7.5 2033-C0023P⊗ -41K 2033-C0023H ⊗ -41K 2033- !0023H⊗ -41K 2033-C0023W ⊗ -41K - 1 11 11 1 2033-C0023P⊗ -42K 2033-C0023H ⊗ -42K 2033- !0023H⊗ -42K 2033-C0023W ⊗ -42K 1 1 --- 2033-C0043P⊗ -42K 2033-C0043H ⊗ -42K 2033- !0043H⊗ -42K 2033-C0043W ⊗ -42K 13 13 13 13 2033-C0043P⊗ -43K 2033-C0043H ⊗ -43K 2033- !0043H⊗ -43K 2033-C0043W ⊗ -43K - 1 51 51 5 2033-C0043P⊗ -44K 2033-C0043H ⊗ -44K 2033- !0043H⊗ -44K 2033-C0043W ⊗ -44K - 18.5 18.5 18.5 2033-C0043P⊗ -45K 2033-C0043H ⊗ -45K 2033- !0043H⊗ -45K 2033-C0043W ⊗ -45K - 2 22 22 2 2033-C0043P⊗ -46K 2033-C0043H ⊗ -46K 2033- !0043H⊗ -46K 2033-C0043W ⊗ -46K 1 5 --- 2033-C0085P⊗ -44K 2033-C0085H ⊗ -44K 2033- !0085H⊗ -44K 2033-C0085W ⊗ -44K 1 8 . 5 --- 2033-C0085P⊗ -45K 2033-C0085H ⊗ -45K 2033- !0085H⊗ -45K 2033-C0085W ⊗ -45K 2 2 --- 2033-C0085P⊗ -46K 2033-C0085H ⊗ -46K 2033- !0085H⊗ -46K 2033-C0085W ⊗ -46K 25 25 25 25 2033-C0085P⊗ -47K 2033-C0085H ⊗ -47K 2033- !0085H⊗ -47K 2033-C0085W ⊗ -47K - 3 23 23 2 2033-C0085P⊗ -48K 2033-C0085H ⊗ -48K 2033- !0085H⊗ -48K 2033-C0085W ⊗ -48K - 3 73 73 7 2033-C0085P⊗ -49K 2033-C0085H ⊗ -49K 2033- !0085H⊗ -49K 2033-C0085W ⊗ -49K - 4 54 54 5 2033-C0085P⊗ -50K 2033-C0085H ⊗ -50K 2033- !0085H⊗ -50K 2033-C0085W ⊗ -50K 110 3 2 --- 2033-C0110P⊗ -48K 2033-C0110H ⊗ -48K 2033- !0110H⊗ -48K 2033-C0110W ⊗ -48K - 5 55 55 5 2033-C0110P⊗ -51K 2033-C0110H ⊗ -51K 2033- !0110H⊗ -51K 2033-C0110W ⊗ -51K - - 63 63 2033-C0110P⊗ -52K 2033-C0110H ⊗ -52K 2033- !0110H⊗ -52K 2033-C0110W ⊗ -52K

ElectroGuard Combination Systems with Thermal-magnetic Circuit Breaker Product Selection for Outside of North America (see page 12-19 for Ordering Instructions) ➊ Optional Time Delay Feature. The Safety Isolation System may be ordered with a factory set time delay feature (30 seconds) in order to allow time for the machine operator to shut-down drives or other equipment that requires a controlled stop, after the operating handle on a Remote Lockout Station has been moved to the “Off” position. See next page for instructions on how to order the optional time delay feature. Consult your local Rockwell Automation sales office for other time settings. Ampere Rating (AC-3) 3-Phase Max. kW Rating (50Hz) Catalogue Number ➊ 230V 400V 500V 600V IP 30 Enclosure IP 54 Enclosure IP 54 Motor Control Centre T ype Enclosure (w/bussing) IP 65 Enclosure 110 --- 7 5 2033-C0110P⊗ -53K 2033-C0110H ⊗ -53K 2033- !0110H⊗ -53K 2033-C0110W ⊗ -53K --- 1 0 0 2033-C0110P⊗ -55K 2033-C0110H ⊗ -55K 2033- !0110H⊗ -55K 2033-C0110W ⊗ -55K 180 3 7 --- 2033-C0180P⊗ -49K 2033-C0180H ⊗ -49K 2033- !0180H⊗ -49K 2033-C0180W ⊗ -49K 4 5 --- 2033-C0180P⊗ -50K 2033-C0180H ⊗ -50K 2033- !0180H⊗ -50K 2033-C0180W ⊗ -50K 5 5 --- 2033-C0180P⊗ -51K 2033-C0180H ⊗ -51K 2033- !0180H⊗ -51K 2033-C0180W ⊗ -51K -6 3- - 2033-C0180P⊗ -52K 2033-C0180H ⊗ -52K 2033- !0180H⊗ -52K 2033-C0180W ⊗ -52K -7 5 7 5- 2033-C0180P⊗ -53K 2033-C0180H ⊗ -53K 2033- !0180H⊗ -53K 2033-C0180W ⊗ -53K -9 0 9 0- 2033-C0180P⊗ -54K 2033-C0180H ⊗ -54K 2033- !0180H⊗ -54K 2033-C0180W ⊗ -54K - - 110 110 2033-C0180P⊗ -56K 2033-C0180H ⊗ -56K 2033- !0180H⊗ -56K 2033-C0180W ⊗ -56K --- 1 3 2 2033-C0180P⊗ -57K 2033-C0180H ⊗ -57K 2033- !0180H⊗ -57K 2033-C0180W ⊗ -57K --- 1 5 0 2033-C0180P⊗ -58K 2033-C0180H ⊗ -58K 2033- !0180H⊗ -58K 2033-C0180W ⊗ -58K --- 1 6 0 2033-C0180P⊗ -59K 2033-C0180H ⊗ -59K 2033- !0180H⊗ -59K 2033-C0180W ⊗ -59K 210 6 3 --- 2033-C0210P⊗ -52K 2033-C0210H ⊗ -52K 2033- !0210H⊗ -52K 2033-C0210W ⊗ -52K - 110 - - 2033-C0210P⊗ -56K 2033-C0210H ⊗ -56K 2033- !0210H⊗ -56K 2033-C0210W ⊗ -56K - - 132 - 2033-C0210P⊗ -57K 2033-C0210H ⊗ -57K 2033- !0210H⊗ -57K 2033-C0210W ⊗ -57K - - 150 - 2033-C0210P⊗ -58K 2033-C0210H ⊗ -58K 2033- !0210H⊗ -58K 2033-C0210W ⊗ -58K --- 1 8 5 2033-C0210P⊗ -60K 2033-C0210H ⊗ -60K 2033- !0210H⊗ -60K 2033-C0210W ⊗ -60K --- 2 0 0 2033-C0210P⊗ -61K 2033-C0210H ⊗ -61K 2033- !0210H⊗ -61K 2033-C0210W ⊗ -61K 300 7 5 --- 2033-C0300P⊗ -53K 2033-C0300H ⊗ -53K 2033- !0300H⊗ -53K 2033-C0300W ⊗ -53K 9 0 --- 2033-C0300P⊗ -54K 2033-C0300H ⊗ -54K 2033- !0300H⊗ -54K 2033-C0300W ⊗ -54K - 132 - - 2033-C0300P⊗ -57K 2033-C0300H ⊗ -57K 2033- !0300H⊗ -57K 2033-C0300W ⊗ -57K - 150 - - 2033-C0300P⊗ -58K 2033-C0300H ⊗ -58K 2033- !0300H⊗ -58K 2033-C0300W ⊗ -58K - 160 160 - 2033-C0300P⊗ -59K 2033-C0300H ⊗ -59K 2033- !0300H⊗ -59K 2033-C0300W ⊗ -59K - - 185 - 2033-C0300P⊗ -60K 2033-C0300H ⊗ -60K 2033- !0300H⊗ -60K 2033-C0300W ⊗ -60K - - 200 - 2033-C0300P⊗ -61K 2033-C0300H ⊗ -61K 2033- !0300H⊗ -61K 2033-C0300W ⊗ -61K --- 2 2 0 2033-C0300P⊗ -62K 2033-C0300H ⊗ -62K 2033- !0300H⊗ -62K 2033-C0300W ⊗ -62K --- 2 5 0 2033-C0300P⊗ -63K 2033-C0300H ⊗ -63K 2033- !0300H⊗ -63K 2033-C0300W ⊗ -63K --- 3 0 0 2033-C0300P⊗ -64K 2033-C0300H ⊗ -64K 2033- !0300H⊗ -64K 2033-C0300W ⊗ -64K 420 110 - - - 2033-C0420P⊗ -56K 2033-C0420H ⊗ -56K 2033- !0420H⊗ -56K 2033-C0420W ⊗ -56K 132 - - - 2033-C0420P⊗ -57K 2033-C0420H ⊗ -57K 2033- !0420H⊗ -57K 2033-C0420W ⊗ -57K - 185 - - 2033-C0420P⊗ -60K 2033-C0420H ⊗ -60K 2033- !0420H⊗ -60K 2033-C0420W ⊗ -60K

ElectroGuard Combination Systems with Thermal-magnetic Circuit Breaker Product Selection for Outside of North America (see page 12-19 for Ordering Instructions) T o order the Time Delay feature, add the following Catalogue String to the end of the Cat. No. shown in the table: Example: Catalogue Number 2033-C0180P⊗ -54K becomes Catalogue Number 2033-C0180P⊗ -54K-1TD to include the time delay feature. * Input Power Feed Catalogue Number Code The Catalogue Number as listed is incomplete. Select an Input Power Feed Code from the table below. Example: Catalogue Number 2033*-C0630P⊗ -58K becomes Catalogue Number 2033T-C0630P⊗ -58K for a “Top Feed” input power requirement. ➊ Optional Time Delay Feature. The Safety Isolation System may be ordered with a factory set time delay feature (30 seconds) in order to allow time for the machine operator to shut-down drives or other equipment that requires a controlled stop, after the operating handle on a Remote Lockout Station has been moved to the “Off” position. Consult your local Rockwell Automation sales office for other time settings. Ampere Rating (AC-3) 3-Phase Max. kW Rating (50Hz) Catalogue Number ➊ 230V 400V 500V 600V IP 30 Enclosure IP 54 Enclosure IP 54 Motor Control Centre T ype Enclosure (w/bussing) IP 65 Enclosure 420 -2 0 0- - 2033-C0420P⊗ -61K 2033-C0420H ⊗ -61K 2033- !0420H⊗ -61K 2033-C0420W ⊗ -61K - 220 220 - 2033-C0420P⊗ -62K 2033-C0420H ⊗ -62K 2033- !0420H⊗ -62K 2033-C0420W ⊗ -62K -- 2 5 0 - 2033-C0420P⊗ -63K 2033-C0420H ⊗ -63K 2033- !0420H⊗ -63K 2033-C0420W ⊗ -63K -- 3 0 0 - 2033-C0420P⊗ -64K 2033-C0420H ⊗ -64K 2033- !0420H⊗ -64K 2033-C0420W ⊗ -64K - - - 355 2033-C0420P⊗ -65K 2033-C0420H ⊗ -65K 2033- !0420H⊗ -65K 2033-C0420W ⊗ -65K - - - 390 2033-C0420P⊗ -66K 2033-C0420H ⊗ -66K 2033- !0420H⊗ -66K 2033-C0420W ⊗ -66K - - - 425 2033-C0420P⊗ -67K 2033-C0420H ⊗ -67K 2033- !0420H⊗ -67K 2033-C0420W ⊗ -67K 630 150 - - - 2033*-C0630P⊗ -58K 2033*-C0630H ⊗ -58K 2033- !0630H⊗ -58K 2033*-C0630W ⊗ -58K 160 - - - 2033*-C0630P⊗ -59K 2033*-C0630H ⊗ -59K 2033- !0630H⊗ -59K 2033*-C0630W ⊗ -59K 185 - - - 2033*-C0630P⊗ -60K 2033*-C0630H ⊗ -60K 2033- !0630H⊗ -60K 2033*-C0630W ⊗ -60K 200 - - - 2033*-C0630P⊗ -61K 2033*-C0630H ⊗ -61K 2033- !0630H⊗ -61K 2033*-C0630W ⊗ -61K -2 5 0- - 2033*-C0630P⊗ -63K 2033*-C0630H ⊗ -63K 2033- !0630H⊗ -63K 2033*-C0630W ⊗ -63K -3 0 0- - 2033*-C0630P⊗ -64K 2033*-C0630H ⊗ -64K 2033- !0630H⊗ -64K 2033*-C0630W ⊗ -64K - 355 355 - 2033*-C0630P⊗ -65K 2033*-C0630H ⊗ -65K 2033- !0630H⊗ -65K 2033*-C0630W ⊗ -65K -- 3 9 0 - 2033*-C0630P⊗ -66K 2033*-C0630H ⊗ -66K 2033- !0630H⊗ -66K 2033*-C0630W ⊗ -66K - - 450 450 2033*-C0630P⊗ -68K 2033*-C0630H ⊗ -68K 2033- !0630H⊗ -68K 2033*-C0630W ⊗ -68K - - - 500 2033*-C0630P⊗ -69K 2033*-C0630H ⊗ -69K 2033- !0630H⊗ -69K 2033*-C0630W ⊗ -69K 860 250 - - - 2033*-C0860P⊗ -63K 2033*-C0860H ⊗ -63K 2033- !0860H⊗ -63K 2033*-C0860W ⊗ -63K -4 5 0- - 2033*-C0860P⊗ -68K 2033*-C0860H ⊗ -68K 2033- !0860H⊗ -68K 2033*-C0860W ⊗ -68K - 500 500 - 2033*-C0860P⊗ -69K 2033*-C0860H ⊗ -69K 2033- !0860H⊗ -69K 2033*-C0860W ⊗ -69K - - 560 560 2033*-C0860P⊗ -70K 2033*-C0860H ⊗ -70K 2033- !0860H⊗ -70K 2033*-C0860W ⊗ -70K - - - 600 2033*-C0860P⊗ -71K 2033*-C0860H ⊗ -71K 2033- !0860H⊗ -71K 2033*-C0860W ⊗ -71K 1200 300 - - - 2033*-C1200P⊗ -64K 2033*-C1200H ⊗ -64K 2033- !1200H⊗ -64K 2033*-C1200W ⊗ -64K 390 - - - 2033*-C1200P⊗ -66K 2033*-C1200H ⊗ -66K 2033- !1200H⊗ -66K 2033*-C1200W ⊗ -66K - 600 600 - 2033*-C1200P⊗ -71K 2033*-C1200H ⊗ -71K 2033- !1200H⊗ -71K 2033*-C1200W ⊗ -71K - 710 710 710 2033*-C1200P⊗ -72K 2033*-C1200H ⊗ -72K 2033- !1200H⊗ -72K 2033*-C1200W ⊗ -72K - - 750 750 2033*-C1200P⊗ -73K 2033*-C1200H ⊗ -73K 2033- !1200H⊗ -73K 2033*-C1200W ⊗ -73K - - 850 850 2033*-C1200P⊗ -74K 2033*-C1200H ⊗ -74K 2033- !1200H⊗ -74K 2033*-C1200W ⊗ -74K - - 888 888 2033*-C1200P⊗ -75K 2033*-C1200H ⊗ -75K 2033- !1200H⊗ -75K 2033*-C1200W ⊗ -75K - - - 1043 2033*-C1200P⊗ -76K 2033*-C1200H ⊗ -76K 2033- !1200H⊗ -76K 2033*-C1200W ⊗ -76K Factory set 30 second time delay feature: -1TD Input Power Feed Catalogue Number Code T op Feed T Bottom Feed B

ElectroGuard Combination Systems with Thermal-magnetic Circuit Breaker/Optional Features Product Selection for Outside of North America (see page 12-19 for Ordering Instructions) ! Bussing Designation The Catalogue Number as listed is incomplete. Select a Bussing Designation Code from the table below. Example: Catalogue Number 2033-!0085H⊗ -44K becomes Catalogue Number 2033-E0085H⊗ -44K for “600A Line Side Incoming Bus and Outgoing Power Cables” bussing designation. ⊗ Input Line Voltage Code The Catalogue Number as listed is incomplete. Select an Input Line Voltage Code from the table below. Example: Catalogue Number 2033-C0085W⊗ -48K becomes Catalogue Number 2033-C0085WN-48K for a 380V 50Hz Input Line Voltage application. Product Selection: Remote Lockout Station ➋ Optional Features Pneumatic Isolation Module (Must be ordered with Safety Isolation System): The Safety Isolation System is available with an optional means of isolating the pneumatic energy source for the machine or process. If the machine operator/maintenance personnel initiates isolation of the electrical energy by operating one of the Remote Lockout Stations, a safety valve is simultaneously actuated to bleed pressure from the air line between the valve and the machine. When the air pressure has fallen to a predetermined level, the unit will allow the light on the Remote Lockout Station to illuminate, if electrical isolation has also been achieved. T o order the Pneumatic Isolation option: Step 1: Add the following Catalogue String to the Safety Isolation System Catalogue Number: e.g. 2031-A0085JB-1PN to indicate an 85A Safety Isolation System that is to be “Pneumatic Ready.” Step 2: Order suitably enclosed Pneumatic Isolation Module as separate item: For North America: For Outside of North America: ➊ Bus Type: Copper with tin plating. Consult factory for other types of bussing. ➋ Safety Isolation Systems rated up through 85A can support a maximum of four (4) Remote Lockout Stations (RLS). Systems rated from 110A - 1200A can support a maximum of six (6) RLS. If additional RLS are required, order the optional Expansion Module(s) (see page 12-16). Ty p e o f B u s s i n g ➊ Catalogue Number Code 600A Line Side Incoming Bus and Outgoing Power Cables E 1200A Line Side Incoming Bus and Outgoing Power Cables D Line Side Incoming Power Cables and 600A Load Side Outgoing Bus H Line Side Incoming Power Cables and 1200A Load Side Outgoing Bus R Input Line Voltage 220V 50Hz 380-400V 50Hz 400-415V 50Hz 440V 50Hz 500V 50Hz 550V 50Hz Voltage Code for Catalogue Number AN GB M C “System Isolated” Light Colour Catalogue Number IP 30 Enclosure IP 54 Enclosure IP 65 Enclosure Green 2030-RLSPG 2030-RLSHG 2030-RLSWG T o indicate that the Safety Isolation System should be supplied as “Pneumatic Ready.” -1PN Pressure Range Valve Port Size Catalogue Number T ype 1 General Purpose Enclosure T ype 12 Dust tight Enclosure T ype 4 Watertight Painted Steel Enclosure T ype 4X Watertight Stainless Steel Enclosure 30-120 psi 1in 2030-PA1201 2030-PJ1201 2030-PF1201 2030-PC1201 3/4in 2030-PA1203 2030-PJ1203 2030-PF1203 2030-PC1203 Pressure Range Valve Port Size Catalogue Number IP 30 Enclosure IP 54 Enclosure IP 65 Enclosure 2-7 bar 1in 2030-PP0071 2030-PH0071 2030-PW0071 3/4in 2030-PP0073 2030-PH0073 2030-PW0073

ElectroGuard Optional Features (continued) Expansion Module (Can be ordered separately): For applications requiring more than the maximum allowable Remote Lockout Stations, or total wire lengths longer than those permitted with the Remote Lockout Stations. Expansion Modules are available in 4 or 10 port configurations. Each Expansion Module is wired to a port on the Control Module, and takes the connection port that would normally accommodate a Remote Lockout Station (see page 12-18 to determine if an Expansion Module is required due to wire length considerations). The 23A through 85A systems will accommodate connection of a maximum of 4 Expansion Modules, and the 110A through 1200A systems will accommodate connection of a maximum of 6 Expansion Modules. Certain ampere size Safety Isolation System Power Panels can accommodate either 1 or 2 Expansion Modules installed internally. In all other instances the Expansion Module(s) must be located external to the Safety Isolation System in a suitably rated enclosure. Expansion Modules may be ordered with an adjustable time delay feature (1-30 seconds) in order to allow time for the machine operator to shut-down drives or other equipment that requires a controlled stop after a Remote Lockout Station has been switched to the “Off ” position. Consult your Rockwell Automation sales office for other time settings. Enclosed Expansion Modules are available with optional “Flex” modules to provide status communication to a remote PLC. Communication can be via DeviceNet or Remote I/O. Note: The status communication option allows a remote PLC to receive status signals from the Expansion Module. The Expansion Module does not accept input signals from DeviceNet or Remote I/O. Ampere Size of Safety Isolation System Internal Provisions to Accommodate Expansion Modules 23A - 85A None 110A - 420A Provisions to accept one (1) Expansion Module (Bulletins 2031, 2032 or 2033) 630A - 1200A Provisions to accept up to two (2) Expansion Modules in Bulletin 2032 or 2033 combination systems, or one (1) Expansion Module in Bulletin 2031 non combination systems. T o order the optional enclosed Expansion Module for field addition for North America:

Description

Catalogue Number ➌ T ype 1 Enclosure T ype12 Enclosure T ype 4 Painted Enclosure T ype 4X Stainless Steel Enclosure 4 port 2030-EUAF 2030-EUJF 2030-EUFF 2030-EUCF 4 port w/ time delay 2030-EUAF-1TDA 2030-EUJF-1TDA 2030-EUFF-1TDA 2030-EUCF-1TDA 10 port 2030-EUAT 2030-EUJT 2030-EUFT 2030-EUCT 10 port w/time delay 2030-EUAT -1TDA 2030-EUJT -1TDA 2030-EUFT -1TDA 2030-EUCT -1TDA T o order the optional enclosed Expansion Module for field addition for outside of North America: Catalogue Number ➌ IP30 Enclosure IP54 Enclosure IP65 Enclosure 4 port 2030-EUPF 2030-EUHF 2030-EUWF 4 port w/ time delay 2030-EUPF-1TDA 2030-EUHF-1TDA 2030-EUWF-1TDA 10 port 2030-EUPT 2030-EUHT 2030-EUWT 10 port w/time delay 2030-EUPT -1TDA 2030-EUHT -1TDA 2030-EUWT -1TDA Note: The time delay feature affects all input devices wired to the Expansion Module. For Expansion Module(s) Factory Installed: Add One of the Following Catalogue Number Strings to the Safety Isolation System Catalogue Number: ➊ e.g. Catalogue Number 2032T -A0630JB-30L becomes Catalogue Number 2032T -A0630JB-30L-2EUT to indicate a 630A Safety Isolation System that includes 2 internally installed 10 port Expansion Modules without the time delay feature. Open T ype Expansion Module for Field Addition ➋ Requires user supplied enclosure if not installed in the Safety Isolation System Power Panel. ➌ T o order the Status Communication to a remote PLC option installed in an enclosed Expansion Module, add one of the following Catalogue Strings to the Expansion Module Catalogue Number: ➍ e.g. Catalogue Number 2030-EUJF becomes Catalogue Number 2030-EUJF- 1COM to indicate a Type 12 enclosed, 4-port expansion module, with 16 points of remote I/O. Number of Expansion Modules Number of Ports per Expansion Module Catalogue Number String ➊ One (available on Bulletin 2031, 2032, or 2033, 110A– 1200A Systems only) 4 -1EUF 4 w/time delay -1EUFTDA 10 -1EUT 10 w/time delay -1EUTTDA T wo (available on 630A – 1200A Bulletin 2032 or 2033 Systems only) 4 -2EUF 4 w/time delay -2EUFTDA 10 -2EUT 10 w/time delay -2EUTTDA Open T ype ➋ Catalogue Number 4 port 2030-EUNF 4 port w/ time delay 2030-EUNF-1TDA 10 port 2030-EUNT 10 port w/time delay 2030-EUNT -1TDA Communication Platform Number of I/O Points Catalogue Number String ➍ Remote I/O 16 points -1COM DeviceNet 16 points -1DNET

ElectroGuard Optional Features (continued) Status Communication to a remote PLC (Should be ordered with Safety Isolation System) This option provides Remote I/O via “Flex” modules. Communication can be via:

  • The DeviceNet communication platform, or
  • The Remote I/O communication platform. Note: The status communication option allows a remote PLC to receive status signals from the ElectroGuard Safety Isolation System. The ElectroGuard does not accept input signals through these communication platforms. Status communication capabilities:
  • Overall system status,
  • Status of each Remote Lockout Station,
  • Status of the Pneumatic Isolation Module (if used),
  • Status of other optional Safety Input devices. Note: Each communication module provides sixteen (16) data points. In determining which Catalogue Number String to specify from the t able below, please keep the following in mind:
  • Overall system status information requires one (1) data point.
  • The Pneumatic Isolation Module (if used) requires one (1) data point.
  • Each Remote Lockout Station used in the application requires one (1) data point.
  • Each optional Rockwell Automation Safety Input device (i.e. Safety Mat, Light Curtain, E-Stop Station, Proximity Switch, Photo Switch) requires one (1) data point. T o order the Status Communication to a remote PLC option, add one of the following Catalogue Strings to the Safety Isolation System Catalogue Number: " Maximum available for units from 23A through 85A. ! Only available on units from 110A through 1200A. ➊ e.g. Catalogue Number 2031-A0085JB becomes Catalogue Number 2031-A0085JB-1COM to indicate an 85A Safety Isolation System that includes 16 points of Remote I/O for status communication to a remote PLC. Cover Mounted Metering (Must be ordered with Safety Isolation System): Cover mounted ammeters and/or voltmeters are available as factory installed options in order to provide visual indication of line side system current and/or voltage. T o order metering, add one or more of the following Catalogue Strings to the Safety Isolation System Catalogue Number: ➋ e.g. Catalogue Number 2031-A0085JB becomes Catalogue Number 2031-A0085JB-1AM to indicate an 85A Safety Isolation System that includes a cover mounted single-phase Ammeter. Communication Platform Number of I/O points Catalogue Number String ➊ Remote I/O 16 points -1COM 32 points -2COM 48 points -3COM" 64 points -4COM! DeviceNet 16 points -1DNET 32 points -2DNET 48 points -3DNET" 64 points -4DNET! T ype of Metering Required Catalogue Number String ➋ Single-phase Ammeter -1AM Three-phase Ammeter -3AM Single-phase Voltmeter -1VM Three-phase Voltmeter -3VM

ElectroGuard Typical Wiring Diagram/Wire Length Considerations Typical Wiring Diagram Wire Length Considerations Each Remote Lockout Station is connected to the Control Module in the Power Panel of the Safety Isolation System. The total length of the wire used to connect the Remote Lockout Stations to the Control Module should not exceed the maximum values shown in the following tables. Calculate the total wire length as follows: 1. Determine the distance in feet or meters from each Remote Lockout Station to the Control Module (located inside the Safety Isolation System Power Panel). 2. Sum the distances for all of the Remote Lockout Stations. 3. Double this value. 4. Compare this doubled value with the maximum values for total wire length shown in the table below: T otal Wire Length for Remote Lockout Stations If the application requires a total wire length greater than those shown in the table, one or more Expansion Modules should be used. The maximum wire length for the Expansion Modules is shown in the following table: For North America For Outside of North America Wire Gauge Max. T otal Wire Length Wire Gauge Max. T otal Wire Length 14AWG 4,600 feet 18 Gauge Metric 1,400 meters 16AWG 2,600 feet 14 Gauge Metric 800 meters 18AWG 1,300 feet Safety Isolation System with Optional Fusible Disconnecting Means Designates field connection points Remote Lockout Station(s) To M o t o r Starters To Loads GC 1IC 2IC ATTENTION: It is important not to exceed the maximum wire length values shown in this section. If the maximum values are exceeded, this may result in an unreliable signal to the Safety Isolation System. Consider using an Expansion Module if wire lengths greater than those shown for the Remote Lockout Stations are needed. T otal Wire Length for Expansion Modules Sample Calculation: An application for a 630A Safety Isolation System will require 8 Remote Lockout Stations (RLS): The wire length from RLS # 1 to the Control Module (in the ElectroGuard Power Panel) will be 50ft. The wire length from RLS # 2 to the Control Module will be 200ft. The wire length from RLS # 3 to the Control Module will be 100ft. The wire length from RLS # 4 to the Control Module will be 300ft. The wire length from RLS # 5 to the Control Module will be 500ft. The wire length from RLS # 6 to the Control Module will be 1000ft. The wire length from RLS # 7 to the Control Module will be 850ft. The wire length from RLS # 8 to the Control Module will be 750ft. 14AWG wire will be used to connect the RLS to the Control Module (see illustration below). Analysis: The Control Module furnished with the 630A Safety Isolation System is capable of supporting a maximum of six (6) RLS. Since this installation will require eight (8) RLS, an optional 4 port Expansion Module will also be used. The Expansion Module will be wired to the Control Module and will take the place of one of the original six RLS. We will, therefore, plan to wire five (5) of the RLS directly to the Control Module and three (3) of the RLS to the Expansion Module. Since the Expansion Module allows greater wire lengths than the Control Module, we will plan to wire the RLS to be installed furthest away from the Power Panel to the Expansion Module. For RLS # 1: wire length = 50ft x 2 = 100ft For RLS # 2: wire length = 200ft x 2 = 400ft For RLS # 3: wire length = 100ft x 2 = 200ft For RLS # 4: wire length = 300ft x 2 = 600ft For RLS # 5: wire length = 500ft x 2 = 1000ft For North America For Outside North America Wire Gauge Max. T otal Wire Length Wire Gauge Max. T otal Wire Length 14AWG 40,000 feet 18 Gauge Metric 12,200 meters 16AWG 23,000 feet 14 Gauge Metric 7,000 meters 18AWG 11,700 feet 152m (500ft) 304m (1000ft) 259m (850ft) 228m (750ft) RLS RLS RLS RLS RLS RLS #6RLS RLS 91m (300ft) 30m (100ft) 61m (200ft) 15m (50ft) Expansion Module Control Module Power Panel

ElectroGuard Wire Length Considerations/Ordering Instructions The total wire length for the 5 RLS to be wired to the Control Module will be: 100ft + 400ft + 200ft + 600ft + 1,000ft = 2,300ft Per the table entitled Total Wire Length for Remote Lockout Stations on page 12-18, the maximum allowable wire length for 14AWG wire is 4,600ft for the RLS to be wired to the Control Module. This portion of the installation will be within the maximum wire length permitted. Next, we need to check the wire length calculation for the RLS to be wired to the Expansion Module. For RLS # 6: wire length = 1000ft x 2 = 200ft For RLS # 7: wire length = 850ft x 2 = 1700ft For RLS # 8: wire length = 750ft x 2 = 1500ft The total wire length for the 3 RLS to be wired to the Expansion Module will be: 2000ft + 1700ft + 1500ft = 5,200ft Per the table entitled Total Wire Length for Expansion Modules on page 12-18, the maximum allowable wire length for 14AWG wire is 40,000ft for the RLS to be wired to the Expansion Module. This portion of the installation will also be within the maximum wire length permitted. Ordering Instructions 1. Determine the Catalogue Number of the Safety Isolation System based on the rating of the load(s) to which it will be connected as follows: If the Safety Isolation System is connected to a single motor load, the horsepower or kilowatt rating of the system should be determined as follows: a. Select the Safety Isolation System that meets or exceeds the horsepower or kilowatt rating of the load at the required voltage and frequency. If the Safety Isolation System is connected to two or more motors or one or more motors in combination with other loads, the horsepower or kilowatt rating of the system should be determined as follows: a. Identify the types of loads (i.e. motor, resistive) and the values of the currents of each of the loads (i.e. steady-state current for resistive loads, full-load and locked-rotor currents for motor loads) to be connected to the Safety Isolation System. b. Sum the full-load currents of all the motor loads to be connected to the Safety Isolation System. To this value add the current values of all resistive loads to be connected to the Safety Isolation System. This value is the “combined load full-load current.” c. Find the horsepower or kilowatt rating of a single motor with a full-load current value greater than or equal to the “combined load full-load current” value determined in Step “b”. d. Select the Safety Isolation System that meets or exceeds this horsepower or kilowatt rating at the required voltage and frequency. e. Sum the locked-rotor currents of all the motor loads to be connected to the Safety Isolation System. To this value add the current values of all resistive loads to be connected to the Safety Isolation System. This value is the “combined load locked-rotor current”. f. Find the horsepower or kilowatt rating of a single motor with a locked-rotor current value greater than or equal to the “combined load locked-rotor current” value determined in Step “e”. g. Select the Safety Isolation System that meets or exceeds this horsepower or kilowatt rating at the required voltage and frequency. h. Compare the ratings of the Safety Isolation Systems selected in Steps “d” and “g”. Select the larger of the two systems for your application. 2. Determine how many Remote Lockout Stations are required for the application. 3. Determine how many Expansion Modules (if any) are required for the application. 4. Pick suitable enclosure type(s) for the Safety Isolation System Power Panel, Remote Lockout Stations and enclosed modules (e.g., Expansion Modules, Pneumatic Isolation Module). 5. Determine what, if any, factory installed options are required for the application (e.g. Pneumatic Isolation, Status Communication to remote PLC, metering).