Features

  • At-Motor Disconnect Switch
  • 125, 160, 250, 315 A Versions of Inductive Load-Rated Switches
  • IP65/Type 1/3/3R/12 Operating Handles
  • IP2LX Finger-Safe Terminals
  • 3- and 4-Pole Versions
  • Front/Door or DIN/Base Mounting Configurations
  • OFF-ON Configurations
  • Box Lug and Bolt-on Terminals Available
  • Switches Include Operating Shaft
  • Suitable as Motor Disconnect Conformity to Standards
  • IEC 207
  • IEC 947-1
  • IEC 947-3 low-voltage switchgear and control gear part 3: switches, disconnecters, switch-disconnecters and fuse- combination units. CE
  • UL 508: Industrial Control Equipment. CUL Approvals
  • UL listed (Box Lug Version)
  • UR recognized (Bolt-on Version)
  • CUL listed (Box Lug Version)
  • CUR recognized (Bolt-on Version)
  • Meets IEC, VDE and BS standard requirements
  • IEC/CE marked for all applicable directives (per EN 60947-3) Y our order must include:
  • Catalogue Number of switch body.
  • Catalogue Number of actuator.
  • If required, Catalogue Number of accessories.

125 Amps to 315 Amps

OFF-ON Base-Mounted Switch — with Box Lugs — UL Listed OFF-ON Base-Mounted Switch — with Bolt-on Wiring — UR Recognized OFF-ON Front-Mounted Switch — with Box Lugs — UL-Listed OFF-ON Front-Mounted Switch — with Bolt-on Wiring — UR-Recognized Switch Body Function Sw. Angle No. of Poles OFF/0 ON/1 Max. Load (Amps) AC23 Rated kw 690V AC 50 Hz Hp @ 480V AC

60 Hz 3 ∅ Catalogue Number

X X X 125 37 60 194E-A125-1753 160 37 60 194E-A160-1753 250 45 75 194E-A250-1753 315 45 100 194E-A315-1753 X X X X 125 37 60 194E-A125-1754 160 37 60 194E-A160-1754 250 45 75 194E-A250-1754 315 45 100 194E-A315-1754 Switch Body Function Sw. Angle No. of Poles OFF/0 ON/1 Max. Load (Amps) AC23 Rated kw 690V AC 50 Hz Hp @ 480V AC X X X 125 37 60 194E-B125-1753 160 37 60 194E-B160-1753 250 45 75 194E-B250-1753 315 45 100 194E-B315-1753 X X X X 125 37 60 194E-B125-1754 160 37 60 194E-B160-1754 250 45 75 194E-B250-1754 315 45 100 194E-B315-1754 Switch Body Function Sw. Angle No. of Poles OFF/0 ON/1 Max. Load (Amps) AC23 Rated kw 690V AC 50 Hz Hp @ 480V AC X X X 125 37 60 194E-E125-1753 160 37 60 194E-E160-1753 250 45 75 194E-E250-1753 315 45 100 194E-E315-1753 X X X X 125 37 60 194E-E125-1754 160 37 60 194E-E160-1754 250 45 75 194E-E250-1754 315 45 100 194E-E315-1754 Switch Body Function Sw. Angle No. of Poles OFF/0 ON/1 Max. Load (Amps) AC23 Rated kw 690V AC 50 Hz Hp @ 480V AC 1 0 X 125 37 60 194E-F125-1753 2 0 X 160 37 60 194E-F160-1753 3 0 X 250 45 75 194E-F250-1753 315 45 100 194E-F315-1753 X X X X 125 37 60 194E-F125-1754 160 37 60 194E-F160-1754 250 45 75 194E-F250-1754 315 45 100 194E-F315-1754 ON OFF O ON OFF O ON OFF O ON OFF O ON OFF O ON OFF O ON OFF O ON OFF O

Actuators 194E — 125…315 A Actuators with Screw Fixing (Includes Legend Plate and Control Knob) Rating Colour Legend Plate Size Use with Catalogue Number Legend Marking Catalogue Number Type A IP65 T ype 3/3R/12 Black 88 mm x 88 mm 3-15/32 in. x 3-15/32 in. 194E-125…315A 194E-HE8A-175 130 mm x 130 mm 5-1/8 in. x 5-1/8 in. 194E-HE13A-175 Type I Red/Y ellow 88 mm x 88 mm 3-15/32 in. x 3-15/32 in. 194E-HE8I-175 130 mm x 130 mm 5-1/8 in. x 5-1/8 in. 194E-HE13I-175 Type G Black 90 mm x 90 mm 3-35/64 in. x 3-35/64 in. 194E-125…315A 194E-HE8G-175 135 mm x 135 mm 5-5/16 in. x 5-5/16 in. 194E-HE13G-175 Type N Red/Y ellow 90 mm x 90 mm 3-35/64 in. x 3-35/64 in. 194E-HE8N-175 135 mm x 135 mm 5-5/16 in. x 5-5/16 in. 194E-HE13N-175 Auxiliary Contacts—2 N.O./1 N.C. Use with Catalogue Number 194E-A125-160 194E-B125-160 194E-AB-P21-160 194E-A250-315 194E-B250-315 194E-AB-P21-315 194E-E125-160 194E-F125-160 194E-EF-P21-160 194E-E250-315 194E-F250-315 194E-EF-P21-315 Earthing/Grounding T erminal Use with Catalogue Number 194E-A135-160 194E-E135-160 194E-AE160-PE 194E-A250-315 194E-E250-315 194E-AE315-PE 194E-B135-160 194E-F135-160 194E-BF160-PE 194E-B250 194E-F250 194E-BF250-PE 194E-B315 194E-F315 194E-BF315-PE Neutral T erminal Use with Catalogue Number 194E-A125-160 194E-E125-160 194E-AE160-TN 194E-A250-315 194E-E250-315 194E-AE315-TN 194E-B125-160 194E-F125-160 194E-BF160-TN 194E-B250 194E-F250 194E-BF250-TN 194E-B315 194E-F315 194E-BF315-TN ON OFF O PE PE N N

Handles (continued) Legend Additional Name Plate and Frame T erminal Cover Use with Catalogue Number 194E-A125-160 194E-E125-160 2 covers per pole required 194E-AE125-C1 194E-A250-315 194E-E250-315 2 covers per pole required 194E-AE250-C1 194E-B125-160 194E-F125-160 2 covers per pole required 194E-BF125-C1 194E-B250-315 194E-F250-315 2 covers per pole required 194E-BF250-C1 Colour Legend Size Use with Legend Marking Catalogue Number 10 per package Gray/Black 19.2 mm x 49 mm 3/4 in. x 1-59/64 in. 88 mm x 88 mm 90 mm x 90 mm 130 mm x 130 mm 135 mm x 135 mm legend frames (Size 8,13) MAIN SWITCH 194L-G3515A HAUPTSCHALTER 194L-G3515B INTERR. PRINCIPALE 194L-G3515C INTERR. PRINCIPAUX 194L-G3515D INTERR. PRINCIPAL 194L-G3515E HUVUDBRYTARE 194L-G3515F WAHLSCHALTER 194L-G3515G Red/ Yellow EMERGENCY OFF 194L-G3515H

IEC Performance Data for 194E ➊ Valid for line with grounded common neutral termination, over voltage category III, pollution degree 3. Other values on request. ➋ Not suitable for load-switching applications (AC-20A) above 690V . 194E-125 194E-160 194E-250 194-315 Rated insulation voltage Ui: ➊ [V] 1000 1000 1000 1000 Rated impulse withstand voltage Uimp [ k V ] 8888 T est voltage 1 min [kV] 3.5 3.5 3.5 3.5 Rated voltage Ue ➊➋ [V] 1000 1000 1000 1000 Rated frequency [Hz] 50/60 50/60 50/60 50/60 Rated thermal current Ith open [A] 125 160 250 315 Rated thermal current Ithe enclosed [A] 125 160 250 315 Rated current Ie AC-1 / Non inductive or slightly induc. load [A] 125 160 250 315AC-21A Switching of resistive loads with slight overload Rated power Pe AC-23A Occasional switching of motor and other highly inductive loads 230V [kW] 30 30 37 55 400V [kW] 45 55 90 110 690V [kW] 37 37 45 45 AC-3 Squirrel-cage motors: starting and stopping of running motors 230V [kW] 22 30 37 45 400V [kW] 37 45 55 75 690V [kW] 30 37 45 45 Conditional rated short-circuit current 400/415V [kA] 30 30 30 30 Max. fuse rating of circuit (type g, G) [A] 125 160 250 315 Rated short-time current Icw 1S [A] 2500 3000 4600 5800 Rated breaking capacity 230V [A] 800 900 1600 1800 AC-23A (cos ϕ 0.45) 400V [A] 750 850 1380 1650 690V [A] 340 340 400 400

IEC Performance Data for 194E (continued) UL CSA Performance Data for 194E DC Switching Capacity 194E-125 194E-160 194E-250 194E-315 Rated current Ie Rated voltage [V] No. Poles in series DC-21A 60 3 [A] 125 160 250 315 For resistive loads T≤1 ms 110 3 [A] 110 140 220 280 220 3 [A] 45 55 85 110 Rated voltage [V] No. Poles in series 110 4 [A] 125 160 250 315 220 4 [A] 80 100 150 200 440 4 [A] 16 20 32 40 Rated power Pe Rated voltage [V] No. Poles in series DC-22A, DC-3 24 4 [kW] 3 3.8 6 7.5 For Inductive loads T≤2.5 ms 48 4 [kW] 6 7.5 12 15 60 4 [kW] 7.5 9.5 15 19 110 4 [kW] 10 12.5 20 25 220 4 [kW] 4.5 5.5 8 10 Rated Power Pe Rated voltage [V] No. Poles in series DC-23A, DC-5 24 4 [kW] 3 3.8 6 7.5 For Inductive loads T≤15 ms 48 4 [kW] 6 7.5 12 15 60 4 [kW] 7.5 9.5 15 19 110 4 [kW] 8.8 11 17.5 22 220 4 [kW] 2.5 3.5 5.5 7 194E-125 194E-160 194E-250 194E-315 Rated Insulation Voltage [V] 600 600 600 600 Rated voltage [V] 600 600 600 600 Continuous current [A] 150 200 250 300 Ampere rating for general use [A] 150 200 250 300 Heavy Pilot Duty [AC] Standard Duty [DC] Motor rating 60Hz 1-phase (2-poles) 120V, 1 P [FLA] 80 100 135 180 [ H P ] 7 . 51 01 52 0 240V, 1 P [FLA] 88 110 136 155 [HP] 20 25 30 35 480V, 1 P [FLA] 78 88 99 108 [HP] 35 40 45 50 600V, 1 P [FLA] 62 70 86 104 [HP] 35 40 50 60 3-Phase 120V, 3 P [FLA] 84 108 160 208 [HP] 15 20 30 40 240V, 3 P [FLA] 8 104 154 192 [HP] 30 40 60 75 480V, 3 P [FLA] 77 77 96 124 [HP] 60 60 75 100 600V, 3 P [FLA] 62 62 77 99 [HP] 60 60 75 100

➊ When provided with terminal covers. Approvals A = approved or test passed Z = accessories are covered by the approval for the switch 194E-125 194E-160 194E-250 194E-315 Actuators IP65 IP65 IP65 IP65 Protection class according to IEC 529 — — — — Front side Front unit IP65 IP65 IP65 IP65 Box lugs ➊ IP20 IP20 IP20 IP20 Bolt-on straight version ➊ IP20 IP20 IP20 IP20 bent version — — — — Mechanical life [Million operations] 0.1 0.1 0.075 0.075 Box lugs — max. wire gauges — — — — T erminal sizes according to IEC 947-1 Gauge No. B11 B11 B14 B14 Fine strands, 1 conductor Max. mm2 70 70 150 150 Min. mm2 16 16 25 25 Rigid wire, 1 conductor Max. mm2 95 95 185 185 Min. mm2 10 10 16 16 Wire gauges according to UL / CSA Max. AWG 3/0 3/0 — — MCM — — 350 350 M i n . A W G 8844 Catalogue No. or Designation UL-Listed (marked w/UL) UR-Recognized (marked w/UR) UL-Listed for Canada (marked with cUL) UR-Recognized for Canada (marked w/cUR) CE 194E-A125 194E-E125 A—A—A 194E-A160 194E-E160 A—A—A 194E-A250 194E-E250 A—A—A 194E-A315 194E-E315 A—A—A 194E-B125 194E-F125 —A—A A 194E-B160 194E-F160 —A—A A 194E-B250 194E-F250 —A—A A 194E-B315 194E-F315 —A—A A A u x . s w i t c h b l o c k s ZZZZZ G r o u n d t e r m i n a l ZZZZZ N e u t r a l t e r m i n a l ZZZZZ

Approximate Dimensions—mm (inches) Dimensions are not intended to be used for manufacturing purposes. Front-Installation Box Lugs, 3- and 4-Pole Switch Body 194E-E Front-Installation Bolt-on T erminals, 3- and 4-Pole Switch Body 194E-F [A] A B C D E F G H I 125 91 (3-19/32) 112 (4-13/32) (1-13/32) (1-1/2) (3-23/64) (3-7/16) (2-5/8) 108 (4-1/4) (3/16) 160 91 (3-19/32) 112 (4-13/32) (1-13/32) (1-1/2) (3-23/64) (3-7/16) (2-5/8) 108 (4-1/4) (3/16) 250 103 (4-3/64) 145 (5-23/32) (1-23/32) 52.5 (2-1/16) 185 (7-9/32) (3-7/16) (2-5/8) 120 (4-11/16) (3/16) 315 103 (4-3/64) 145 (5-23/32) (1-23/32) 52.5 (2-1/16) 185 (7-9/32) (3-7/16) (2-5/8) 120 (4-11/16) (3/16) [A] A B C D E F G H I L M N O P 125 91 (3-19/32) 112 (4-3/32) (1-1/2) 65.5 (2-9/16) (1/8) (3/32) (1-13/32) (3-7/16) (2-5/8) (13/32) (3-17/32) (2-17/32) (3/16) M10 (3/8) 160 91 (3-19/32) 112 (4-3/32) (1-1/2) 65.5 (2-9/16) (1/8) (3/32) (1-13/32) (3-7/16) (2-5/8) (13/32) (3-17/32) (2-17/32) (3/16) M10 (3/8) 250 103 (4-3/64) 145 (5-23/32) 52.5 (1-22/32) 60.4 (2-3/8) (5/32) (3/32) (1-23/32) (3-7/16) (2-5/8) (1/2) 100 (3-15/16) (2-3/4) (3/16) M12 (15/32) 315 103 (4-3/64) 145 (5-23/32) 52.5 (1-22/32) 60.4 (2-3/8) (5/32) (3/32) (2-1/16) (3-7/16) (2-5/8) (1/2) 100 (3-15/16) (2-3/4) (3/16) M12 (15/32) GF H C B A D E max. mm I M L N PGF O H CB A D E I

Approximate Dimensions—mm (inches) Dimensions are not intended to be used for manufacturing purposes. Base-Mounting Box Lugs, 3- and 4-Pole Switch Body 194E-A Base-Mounting Bolt-on T erminals, 3- and 4-Pole Switch Body 194E-B [A] A B C D E F G H I L 125 91 (3-19/32) 112 (4-13/32) (1-1/2) (3-23/64) (3/32) 118 (4-5/8) 6.4 (1/4) 108 (4-1/4) (2-17/32) (1-13/32) 160 91 (3-19/32) 112 (4-13/32) (1-1/2) (3-23/64) (3/32) 118 (4-5/8) 6.4 (1/4) 108 (4-1/4) (2-17/32) (1-13/32) 250 98 (3-27/32) 145 (5-23/32) 52.5 (1-23/32) 185 (7-9/32) (3/32) 140 (5-1/2) 6.4 (1/4) 126 (4-15/16) (2-3/4) (2-1/16) 315 98 (3-27/32) 145 (5-23/32) 52.5 (1-23/32) 185 (7-9/32) (3/32) 140 (5-1/2) 6.4 (1/4) 126 (4-15/16) (2-3/4) (2-1/16) [A] A B C D E F G H I L M N O P Q 125 91 (3-19/32) 112 (4-13/32) (1-1/2) 36.5 (1-7/16) (1/8) (3/32) (3) (1-13/32) (3/4) (3-17/32) (2-17/32) (13/32) M10 (3/8) (1-13/32) 6.4 (1/4) 160 91 (3-19/32) 112 (4-13/32) (1-1/2) 36.5 (1-7/16) (1/8) (3/32) (3) (1-13/32) (3/4) (3-17/32) (2-17/32) (13/32) M10 (3/8) (1-13/32) 6.4 (1/4) 250 98 (3-27/64) 145 (5-23/32) 52.5 (1-23/32) 38.6 (1-1/2) (5/32) (3/32) (3-1/8) (1-23/32) (1-1/64) 100 (3-15/16) (2-3/4) (1/2) M12 (15/32) (1-23/32) 6.4 (1/4) 315 98 (3-27/64) 145 (5-23/32) 52.5 (1-23/32) 38.6 (1-1/2) (5/32) (3/32) (3-1/8) (1-23/32) (1-1/64) 100 (3-15/16) (2-3/4) (1/2) M12 (15/32) (2-1/16) 6.4 (1/4) D max. mm A BC E E L F G HI D B A C E F F G HI LM N OPQ

Approximate Dimensions—mm (inches) Dimensions are not intended to be used for manufacturing purposes. Box Ground and Neutral T erminal Switch Body 194E-F Bolt Ground and Neutral T erminal Switch Body 194E-F Auxiliary Contacts [A] A B C D E F 125 37.8 (1-1/2) (2-17/32) 108 (4-1/4) 37.8 (1-1/2) (2-17/32) 108 (4-1/4) 160 37.8 (1-1/2) (2-17/32) 108 (4-1/4) 37.8 (1-1/2) (2-17/32) 108 (4-1/4) 250 52.3 (2-1/16) 71.1 (2-25/32) 126 (4-15/16) 52.3 (2-1/16) 80.6 (3-1/8) 126 (4-15/16) 315 52.3 (2-1/16) 71.1 (2-25/32) 126 (4-15/16) 52.3 (2-1/16) 80.6 (3-1/8) 126 (4-15/16) [A] A B C D E F G H I L M N 125 37.8 (1-1/2) (2-17/32) (13/32) M10 (13/32) (3-17/32) (1/8) 37.8 (1-1/2) (2-17/32) (13/32) M10 (13/32) (3-17/32) (1/8) 160 37.8 (1-1/2) (2-17/32) (13/32) M10 (13/32) (3-17/32) (1/8) 37.8 (1-1/2) (2-17/32) (13/32) M10 (13/32) (3-17/32) (1/8) 250 52.3 (2-1/16) (2-21/32) (1/2) M12 (15/32) 100 (3-15/16) (5/32) 52.3 (2-1/16) (2-21/32) (1/2) M12 (15/32) 100 (3-15/16) (5/32) 315 52.3 (2-1/16) (2-21/32) (1/2) M12 (15/32) 100 (3-15/16) (5/32) 52.3 (2-1/16) (2-21/32) (1/2) M12 (15/32) 100 (3-15/16) (5/32) A B FRONT BASE C D E F G H I L M N FRONT BASE 14 14 50 50

Approximate Dimensions—mm (inches) Dimensions are not intended to be used for manufacturing purposes. T erminal Cover Switch Body 194E-F Door Clutches AB 125 76.2 (3) (3-3/4) 160 76.2 (3) (3-3/4) 250 88 (3-15/32) 109.5 (4-5/16) 315 88 (3-15/32) 109.5 (4-5/16) A B L 5.4 mm (7/32) (3-15/32) (2-11/16) fl 27 (1-1/16) L for Standard Shaft Shaft must be cut to length at installation.93…199 mm

Approximate Dimensions—mm (inches) Dimensions are not intended to be used for manufacturing purposes. Actuators (T ype 194E-HE-8A-8I-8G-8N) Actuators (T ype 194E-HE-13A-13I-13G-13N) Additional Name Plate Frame and legend snaps on to actuator bezel. Fits size 8 and 13 actuators. (1-15/16) 1-4 mm (1/32-1/8) 1-4 mm (1/32-1/8) (1-49/64) 88 x 88 (2-11/16) (2-11/16) 92 x 92 (1-5/8 x 1-5/8) fl 12 (15/32) fl 5.3 (7/32) (2-11/16) 1-4 mm (1/32-1/8) 1-4 mm (1/32-1/8) (2-5/32) 130 x 130 (5-1/8 x 5-1/8) 135 x 135 (5-5/16 x 5-5/16) (2-11/16) (2-11/16) fl 20 (15/32) fl 5.3 (7/32) (3-5/16) G3515 (23/32) 6.7 (9/32)